11
It allows to set the date and the time
Press OK to enter.
Use
or
to choose.
Press OK for setting and again to confirm.
Press ESC to go back to the previous menu.
The factory setting (DEFAULT) is YES because the QR230E is equipped with an
integral physical bypass.
Installer menu
1 Language
2 Date/Time
3 Bypass
4 Bypass settings
5 Free Cooling
Installer menu
1 Language
2 Date/Time
3 Bypass
4 Bypass settings
5 Free Cooling
Installer menu
1 Language
2 Date/Time
3 Bypass
4 Bypass settings
5 Free Cooling
It allows to set the Bypass/Free Cooling operation parameters
Press OK to enter.
Use
or
to choose “Desired Temperature”, “Tmax Free Heating”, “Tmin Free Cooling”
For definitions see “Free Cooling”, paragraph 7.3.
Press OK to select.
The setting ranges are:
Desired Temperature: 15°C ÷ 30°C
Tmax Free Heating: 25°C ÷ 30°C
Tmin Free Cooling: 15°C ÷ 20°C
Use
or
to increase or decrease the temperature.
Press OK to select.
Press ESC to go back to the previous menu.
The factory settings (DEFAULT) are:
Desired Temperature: 23°C
Tmax Free Heating: 28°C
Tmin Free Cooling: 18°C
Installer menu
1 Language
2 Date/Time
3 Bypass
4 Bypass settings
5 Free cooling
To be selected only in case Bypass is set on NO.
Press OK to enter.
Use
or
to choose NO or YES.
Press OK to select.
The factory setting (DEFAULT) is NO.
This function is enabled only if FREE COOLING is set on YES. When it is operating, the icon
is
displayed on LCD.
This function mitigates heat exchange when the combination of internal and external temperatures are such
that the heat exchange is not recommendable.
For temperature settings see previous point 4
Installer menu
6 Heating
7 Heating Threshold
8 Dehumidification
9 Speed Setting
10 Airflow Balancing
To be selected only in case an external heating element (not supplied) is present.
Press OK to enter.
Use
or
to choose NO/PRE/POST.
Press OK to select.
The factory setting (DEFAULT) is NO.
NO: HEAT output (Fig. 5.f) is never activated
PRE: the heating element is intalled at “intake air side” (Fig.7.a - ).
HEAT output (Fig. 5.f) is activated and heating icon displays on LCD when
T21 < HEATING THRESHOLD (Fig.7.a)
POST: the heating element is intalled at “supply air side” (Fig.7.a - ).
HEAT output (Fig. 5.f) is activated and heating icon
displays on LCD when
T11 < HEATING THRESHOLD (Fig.7.a)
A
C