4.2.4 MANUAL CONTROL
Press both and for about 5 seconds.
Four lines are shown on the display and then the % of the 0-10V regulation.
Release and (the led of the two buttons flash).
Press to increase the regulation value.
Press to decrease the regulation value.
The regulation % remains fixed at the desired point.
BACK TO THE AUTOMATIC MODE
Press both and for about 5 seconds.
Four lines are shown on the display and then the ambient temperature is displayed (the leds of the two buttons switch off).
4.2.5 SETTING OF THE CONSTANT DATA
Press both and for about 5 seconds.
Four lines are shown on the display and then the message
CONF.
is displayed.
Press to scroll the setting menu.
Parameters:
P.r.o.b.
Cor.t
. = temperature probe correction
SCAL
= °C/°F Celsius or Fahrenheit degree
Air
SP.Lo
= % of minimum speed
SP.Hi
= % of the maximum speed
P.b
. = proportional band of regulation
t.Lo.A
= minimum temperature alarm
t.Hi.A
= maximum temperature alarm
d.SE.t
= temperature alarm relays hysteresis
AnEM.
=0-1 activation/deactivation wind block
d.SE.r
= on/off anemometer block hysteresis
t.Int.
= 0-10V integration time
ImP.
= number of pulses per revolution
Circ.
= blade circumference
Unit
= unit of measure 0=m/s 1=mph 2=km/h
Star
= % minimum starting speed
Press twice : the anemometer block setting (
SET = 3.0v
) is displayed.
Press or to increase / decrease.
By activating in
CONF
. the function (
ANEM.=1
) and by connecting the anemometer, when the wind speed goes over the set level, the 0-10V signal is inhibited.
4.3 ANEMOMETER BLOCK
-
Press : the diagram is displayed followed by the maximum registered temperature value. Keeping pressed for more than 3 seconds, the word
CLEA. is shown and the memory is cleared.
Press : the diagram is displayed followed by the minimum registered temperature value. Keeping pressed for more than 3 seconds, the word
CLEA. is shown and the memory is cleared.
4.4 MEMORY OF THE REGISTERED TEMPERATURE (the values are retained even with the controller switched off)
-
+
+
+
-
4.5 SYSTEM RESET
-
+
Disconnect the controller from the main power supply.
Connect the controller to the main power supply and keep pressed until the word BOOT is displayed.
Release and wait for the reset.
Attention: Any setting will return to the default.
+
+