Power Quality Analyzer Model 3945-B
15
Measurement selection:
RMS
True RMS Measurement
THD
Total Harmonic Distortion
CF
Crest Factor
max/min
Maximum and Minimum values
Simultaneous display of the various measurements
in alphanumeric form
Phasor diagram
The calculation of the DPF, Tan, KF,
Φ
, UNB, Min, Max, VAR, Harmonics, PST,
and DF parameters and the frequency measurement can only be performed if
voltage with a frequency of 41 to 70 Hz is applied to the Ch1 voltage input.
Selection of waveforms to be displayed (use the
buttons to select):
•
3U
displays the 3 phase-to-phase voltages U
1-2
, U
2-3
, U
3-1
•
3V
displays the 3 phase-to-neutral voltages V
1N
, V
2N
, V
3N
•
3A
displays the 3 phase currents
•
4A
displays the 3 phase currents and the neutral current
•
L1, L2
or
L3
displays the voltage and current, on phase 1, 2 or 3, when
selected
Protocol:
U: Signifies phase-to-phase voltage
V: Signifies phase-to-neutral voltage
L1, L2, L3: Refer to the phases (A,B,C or other)