8
GroundFlex™ Adapter Model 6474
Start by identifying each sensor using the identification rings (brown, red, orange,
yellow) supplied with the device.
Connect the calibration loop between terminals H and E of the Model 6472.
•
Connect the Model 6472 and 6474 together using the connection cable.
•
Connect the GroundFlex
•
™
sensor with the brown ring to input 1 of the Model
6474, the one with the red ring to input 2, the one with the orange ring to input
3, and the one with the yellow ring to input 4.
Coil the GroundFlex
•
™
sensor four times around in the calibration loop and
close it using its screw connector. Place the connector as far as possible from
the calibration device.
NOTE:
• The sensors have arrows to indicate a direction.
• All sensors should face the same direction.
(clockwise or counter-clockwise)
• All sensors should have the same number of wraps.
• Sensors should encircle both leg AND ground system.
6472
6474