3.2.3 Connection cables
The below requirements on the AC/DC cables for connection to the corresponding inverter models should be taken into
account:
Model
DC side
AC side
Min. cross-section
area, mm²
(length ≤50m)
Min. cross-
section area, mm²
(length >50m)
Mini cross-section
mm² (length ≤50m)
L
N/PE
AS-IC01-4000 / AS-IC01-4000-2 / AS-IC01-
5000 / AS-IC01-5000-2/ AS-IC01-6000-2 /
AS-IC01-8000-2 / AS-IC01-10000-2
4
6
4
Table 9: Cable specifications
3.2.4 Micro breakers
In order to ensure safe operation of the inverter and circuits, it is recommender to place micro breakers or fuses on the
DC input end and on the AC output end of the inverter.
The wiring shall follow local electric codes. Choose proper cables for power input and output lines.
Input and output cables shall be solar cables suitable for outdoor use.
Micro breaker specifications:
Model
DC input
AC output
Recommended breaker
specification
Recommended breaker
specification
AS-IC01-4000 / AS-IC01-4000-2 / AS-IC01-5000 /
AS-IC01-5000-2 / AS-IC01-6000-2
DC1000V, C16A, 2P
AC400V, C16A, 4P
AS-IC01-8000-2 / AS-IC01-10000-2
DC1000V, C25A, 2P
AC400V, C25A, 4P
Table 10: Breaker specifications