AE Conversion INV315-50EU Скачать руководство пользователя страница 8

8

INV315-50EU

11.2019

Activate output via fibre optics:

• 

Switch off AC

• 

LED signals the start of the output sequence by „ON“ for 5 sec.

• 

LED outputs the data as a pulse pattern (duration approx. 50 
sec.)

• 

LED signals the end of the output sequence with 5 sec. „ON

• 

LED switches to normal signalling mode 

The LED output sequence must be recorded via a video 
(smartphone, digital camera, or similar) with a resolution of 
680x480DPI. This video is then analysed using PC software. The 
software can be found on the AEconversion website (http://
aeconversion.com/de/downloads.html). After successful analysis 
of the video, the set values are displayed in plain text. When 
recording, make sure that a few seconds of the start and end 
of the output sequence are recorded. If possible, the position 
of the LED on the screen must always remain the same. Please 
observe further instructions when running the software.

Additional option for versions with communication interface:

• 

Establish a data connection between the PC and the Micro 
Inverter

• 

Download AEsolar software

• 

Query the device via the corresponding menu item

6.0 Operating Conditions

The selection of the PV generator is of central importance in the 
design of a PV system. It is essential to ensure that the inverter 
also matches the PV module.

6.1 Dimensioning the PV generator

The number of PV modules connected in series must be selected 
so that the output voltage of the PV generator does not exceed 
the permitted input voltage range of the inverter, even at 
extreme outdoor temperatures. In Central Europe, module 
temperatures between -20°C and +70°C should be assumed. 
Depending on the mounting type of the generators and the 
geographical location, +60°C or +70°C is used in the voltage 
calculation. You should take the temperature coefficients of the 
PV modules into account. The following criteria must be fulfilled 
for the voltage of the PV generator:

- Uo (-15°C) < max. input voltage:
50 V and -15°C for an INV315-50EU / RF

The open-circuit voltage of the connected PV generator must 
be within the permitted input voltage range even at very low 
outdoor temperatures (-15°C). If the temperature is lowered 
from 25°C to -10°C, the open-circuit voltage of 12 V modules 
increases by approx. 2.8 V per module (5.6 V for a 24V module). 
The open-circuit voltage of the entire PV generator must be less 
than 50 for INV315.

- U

Mpp

 (+60 °C) > input voltage:

20 V

DC

 for INV315-50EU

The U

Mpp

  voltage of the connected string should not fall below 

the permitted input voltage range even at very high module 
temperatures (+60°C). 
If the temperature rises from 25°C to 
60°C, the UMpp voltage of 12 V modules drops by approx. 
by approx. 3.6 V per module (7.2 V for a 24 V module).

If the U

Mpp

 -voltage falls below the permitted input range, the 

system continues to operate without any problems. In this state, 
however, the maximum possible power is no longer fed into the 
grid, but slightly less.

It does not harm the inverter if a connected PV generator 
delivers a higher input current than the maximum usable input 
current, provided the input voltage is within the permissible 
range. It may happen that the inverter switches off for safety 
reasons if the PV generator briefly provides more than the max. 
DC input power of the inverter, especially during changing cloud 
cover and relatively low module temperatures.
Normally, however, the control of the inverter is so dynamic that 
it continues to operate without interruption.

In general, for an optimal energy yield of the 
PV generator in Central Europe, a southern orientation with an 
inclination of 30° should be selected. The optimal power factor 
for south-facing systems is between 1.10 and 1.25.
For an east-west system, the power factor can be selected up to 
1.30. The prerequisite is that all other limit values of the inverter 
are complied with. For exposed locations in the mountains or 
in southern regions, a corresponding reduction (< 1.15) of the 
power ratio is necessary. 

7.0 Installation

Select the mounting position so that the following points are 
observed:

• 

As good as possible access to the unit for installation work or any 
service work that may need to be carried out at a later date.                .

• 

Ensure a minimum distance of 20 mm between the upper 
edge of the roof and the underside of the inverter. We also 
recommend a distance of 25 mm between the back of the PV 
module and the top edge of the inverter. 

• 

The unit is designed to be mounted on the mounting frame 
under a PV module, but other mounting variants are possible.  
 

      

• 

The inverter is to be mounted so that the connection area of 
the inverter faces downwards

• 

The inverter is to be mounted so that the cover (type label) is 
always facing upwards

• 

The free air flow around the enclosure must not be obstructed. 
 

      

 

Содержание INV315-50EU

Страница 1: ...Micro Inverter English INV315 50EU ...

Страница 2: ...Assembly and operating instructions INV315 50EU Printed in Germany Copyright by AEconversion GmbH Co KG ...

Страница 3: ...Protection concepts 7 5 5 Network and system protection 7 6 0 Operating conditions 8 6 1 Dimensioning of the PV generator 8 7 0 Installation 8 7 1 Installation on PV racking 9 7 2 Mounting alternatives 9 8 0 Connections 9 8 1 Overview of connections 10 8 1 1 Connection areas of the inverter 10 8 2 AC Connection 10 8 1 2 AC Connection of many devices 11 8 3 DC Connection 11 8 4 Communication setup ...

Страница 4: ...tions of all parts and components of the system 2 1 General information and safety instructions The proper and safe operation of this device requires proper transport storage installation and assembly as well as careful operation and maintenance When operating this equipment certain parts of the equipment are under dangerous voltage which can cause serious bodily injury or death Therefore please f...

Страница 5: ...es not comply with the standards Improper operation Operating the units with defective protective devices Impact of foreign bodies and force majeure lightning overvoltage thunderstorms fire Insufficient or non existent ventilation of the unit Non observance of safety regulations Transport damage Use of non original PV mating plugs and sockets from the HELIOS H4 product series by Amphenol The insta...

Страница 6: ...signed for operating temperatures from 25 C to 70 C If the temperature inside the enclosure exceeds a certain value the inverter automatically regulates the maximum power to protect itself Systems with micro inverters are easy to design and install Each inverter can be mounted on the mounting rack underneath the PV modules but it is recommended to have a place where emergency service work can be e...

Страница 7: ...75sec OFF 0 25sec 1 cycle AC voltage not within tolerance range LED 1sec ON 0 75sec OFF 0 25sec 2 cycles DC voltage not within tolerance range LED 1sec ON 0 75sec OFF 0 25sec 3 cycles AC and DC voltages not within tolerance range LED 1sec ON 0 75sec OFF 0 25sec 4 cycles Internal overtemperature LED 1sec ON 0 75sec OFF 0 25sec 5 cycles Sequence ends 2 sec AUS Insulation measurement on the PV side I...

Страница 8: ... a 24V module The open circuit voltage of the entire PV generator must be less than 50 for INV315 UMpp 60 C input voltage 20 VDC for INV315 50EU The UMpp voltage of the connected string should not fall below the permitted input voltage range even at very high module temperatures 60 C If the temperature rises from 25 C to 60 C the UMpp voltage of 12 V modules drops by approx by approx 3 6 V per mod...

Страница 9: ...e help of accessories that are matched to the mounting frame As an example slot stones can be fastened to the mounting profiles at the positions below the inverter brackets with screws When mounting make sure that the inverter is mounted in the correct installation position the cover must face upwards connection plugs must point downwards 7 2 Installation alternative If mounting on the mounting fr...

Страница 10: ...reases during feed in operation This voltage is measured by the inverter If the voltage at the grid terminals exceeds the limit for grid overvoltage the inverter switches off due to grid overvoltage This circumstance must be taken into account in the AC wiring and when dimensioning the AC line When using several AC circuits in a PV system it is necessary to distribute the feed in phase symmetrical...

Страница 11: ...nnection before connecting it to the inverter Only use original mating plugs and sockets from the HELIOS H4 product range from Amphenol Observe the Amphenol assembly instructions for the DC connectors if you assemble the cables yourself Check that the PV generator is free of earth faults before connecting it to the inverter Before connecting the DC cables to the inverter check whether the maximum ...

Страница 12: ...of the inverter different procedures must be followed Please follow the communication setup procedure that is appropriate for your inverter 8 4 1 RF Communication If the micro inverter is equipped with RF communication the steps for setting up communication including wiring and monitoring are described below Communication via the RFC interface takes place via a frequency of 2 4 GHz In combination ...

Страница 13: ...e short circuit resistance of the switching devices 10 0 Switching off the inverter You must switch off the inverter for adjustment maintenance and repair work Proceed as follows Switch off the mains voltage deactivate the external fuse elements After switching off check that there is no voltage Follow the local regulations for work on electrical installations Danger to life due to electric shock ...

Страница 14: ... dirt 12 3 Laws regulations and technical rules When constructing solar installations the laws and regulations applicable to the respective country at state federal and European or international level must be observed In general the generally recognised rules of technology apply which are usually formulated in the form of standards guidelines regulations provisions and technical rules by state and...

Страница 15: ...ncy 96 European efficiency 95 MPPT efficiency 99 8 Mechanical Data Operating Temperature 25 C 70 C Night time power consumption 30 mW Max altitude a s l 2000 m DC Input Amphenol H4 AC Output female connector Wieland system RSTi mini Dimensions WxHxD 390mm x 100 mm x 30 mm Weight 0 8 kg Cooling natural convection Enclosure material aluminum Protection Degree IP65 iP67 NEMA4 50 Hz Version Nominal AC...

Страница 16: ...v T ambient 0m s P pv 30V P pv 35V P pv 40V P pv 25V 100 W 150 W 200 W 250 W 300 W 15 C 10 C 5 C 0 C 5 C 10 C 15 C 20 C 25 C 30 C PV input power T amb 0 1m s wind speed Derating diagramm Ppv T ambient 0 1 m s P pv 30V P pv 25V P pv 40V Derating diagrams for INV315 6 0 A 6 5 A 7 0 A 7 5 A 8 0 A 8 5 A 9 0 A 9 5 A 10 0 A 250 W 260 W 270 W 280 W 290 W 300 W 310 W 320 W 26 V 28 V 30 V 32 V 34 V 36 V 38...

Страница 17: ...mmen mit den Vorschriften folgender europäischer Richtlinien überein The indicated products are in correspondence with the following regulations of European Council Nummer Kurztitel Number Titel Eingehaltene Vorschriften Observed regulations 2014 30 EU EMV Richtlinie EMC Directive EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61000 3 2 2006 A1 2009 A2 2009 EN 61000 3 3 2008 2014 35 EU Niederspannungsrich...

Страница 18: ...al 12 TR Turkey 13 LT Lithuania 14 LV Latvia 15 BG Bulgaria 16 CY Cyprus 17 SE Sweden 18 CH Switzerland 19 PL Poland 20 CZ Czech Republic 21 SK Slowakia 22 FI Finnland 23 AL Albany 24 IE Ireland 25 SI Slovenia 26 MT Malta 27 HR Croatia 28 RO Romania 29 XZ Kosovo 40 IL Israel 41 AU Australia 42 TN Tunisia 43 BB Barbados 44 CL Chile 45 ZA South Africa 46 IR Iran 47 CN China 48 KZ Kazakhstan 49 IN In...

Страница 19: ...19 11 2019 INV315 50EU AEconversion GmbH Co KG An der Helle 26 59505 Bad Sassendorf Germany Telefon 49 0 2927 9194 10 Telefax 49 0 2927 9194 50 www aeconversion de ...

Отзывы: