AE Conversion INV315-50EU Скачать руководство пользователя страница 6

6

INV315-50EU

11.2019

A power control is integrated in the inverter depending on the 
temperature. The following diagrams show the maximum input 
power of the inverter versus the ambient temperature and air 
velocity. 

      

 

See diagrams on page 16:
- Power reduction Ppv / T ambient 0m/s Air velocity
- Power reduction Ppv / T ambient 0.1 m/s air velocity

Please note that the performance of your PV module 
also decreases with increasing module temperature. 
As a rule with approx. 0.4% / °C.  This means that a 
module with 330W under STC conditions will only 
produce a maximum of 271W at 70°C and 1000 W/m². 

 

5.0 Product description

The AEconversion micro-inverter is connected directly behind 
one or two modules, depending on the power specification, 
and converts the direct current generated into grid-compliant 
alternating current. The individual conversion at each module 
enables the solar energy to be optimally utilised. In addition, 
the micro-inverter solves a widespread problem. Due to the 
series connection in systems with central or string inverters, 
the modules are dependent on each other in terms of power. If 
the power of a single module drops, for example due to partial 
shading or module mismatch, it negatively affects the power 
of an entire string. This is referred to as the domino effect. Due 
to the parallel connection in systems with micro-inverters, the 
outputs of the modules are independent of each other and allow 
each module to work at maximum output.

The „plug-and-play“ system avoids connection errors and makes 
installation simple and safe.  

 

 

 

 
There is no dangerously high DC voltage and installation time 
and costs are significantly reduced. Installations are effective for 
a wide range, from kilowatts to megawatts, from small family 
homes to building facades. Each photovoltaic system can be 
rearranged or upgraded, for example when power is increased 
or structural changes are made.

Zudem wird es durch den Micro-Wechselrichter möglich 
sein, die Leistungen der Photovoltaik-Anlage auf modularer 
Basis zu überwachen, was die Voraussetzung für eine genaue 
Anlagenüberwachung und eventuelle Problemerkennung 
schafft. So werden nicht nur die Leistungssteigerungen 
der Photovoltaik-Anlage gewährleistet, sondern auch 
eventuelle Leistungsverluste durch eine Früherkennung und 
Problemlokalisierung vermieden.

The housing of the micro-inverter is IP65 protected and 
designed for operating temperatures from -25°C to 70°C. If the 
temperature inside the enclosure exceeds a certain value, the 
inverter automatically regulates the maximum power to protect 
itself. Systems with micro-inverters are easy to design and install. 
Each inverter can be mounted on the mounting rack underneath 
the PV modules, but it is recommended to have a place where 
emergency service work can be easily carried out.  

 

 

       
 

3.3 Service

We have already placed special emphasis on the quality and 
durability of the inverter during the development phase. Despite 
all quality assurance measures, faults can occur in exceptional 
cases. In this case, AEconversion will provide you with the 
maximum possible support in order to eliminate the fault 
quickly and free of bureaucratic effort. Please contact our service 
department directly.

AEconversion -Service Phone: +49  2927 9194-10 

In order for our service department to be able to react quickly 
and correctly, the following information is absolutely necessary. 

1) Information on the inverter
The details of the type designation, as well as the article number 
and serial number of the inverter can be found on the type plate 
of 

the 

unit. 

 

     

 
Brief description of the fault: 

• 

Did the fault occur immediately during commissioning or only 
at a later point in time?

• 

Is the fault reproducible or does it occur sporadically?

• 

What were the ambient conditions (irradiation) at the time of 
the fault?

2) Information on the PV generator:

• 

Which module manufacturer and module type was installed?

• 

What does the system wiring look like?

• 

What is the open-circuit voltage (Voc) of the module?

4.0 Legal regulations and technical guidelines

The legal regulations and technical guidelines are listed below.

4.1 Derating

The service life can be extended by not operating the unit at 
maximum power, but by reducing this power. This is described 
below for the micro inverter. 

4.1.1 

Derating as a function of input voltage

The maximum value of the input current from the PV module of 
9.5A results in a maximum power that the inverter can convert 
depending on the input voltage. The limit of 9.5A is limited by 
the inverter and cannot be exceeded. 

This results in the following curve of the maximum absorbed 
power depending on the input voltage of the PV module.

See diagram on page 16 : Power reduction P pv / I pv

4.1.2 

Derating as a function of ambient tem. / wind speed

Depending on the installation location of the inverter, 
there are different environmental conditions. The ambient 
temperature and the air velocity around the inverter influence 
its 

performance. 

 

     

 

Содержание INV315-50EU

Страница 1: ...Micro Inverter English INV315 50EU ...

Страница 2: ...Assembly and operating instructions INV315 50EU Printed in Germany Copyright by AEconversion GmbH Co KG ...

Страница 3: ...Protection concepts 7 5 5 Network and system protection 7 6 0 Operating conditions 8 6 1 Dimensioning of the PV generator 8 7 0 Installation 8 7 1 Installation on PV racking 9 7 2 Mounting alternatives 9 8 0 Connections 9 8 1 Overview of connections 10 8 1 1 Connection areas of the inverter 10 8 2 AC Connection 10 8 1 2 AC Connection of many devices 11 8 3 DC Connection 11 8 4 Communication setup ...

Страница 4: ...tions of all parts and components of the system 2 1 General information and safety instructions The proper and safe operation of this device requires proper transport storage installation and assembly as well as careful operation and maintenance When operating this equipment certain parts of the equipment are under dangerous voltage which can cause serious bodily injury or death Therefore please f...

Страница 5: ...es not comply with the standards Improper operation Operating the units with defective protective devices Impact of foreign bodies and force majeure lightning overvoltage thunderstorms fire Insufficient or non existent ventilation of the unit Non observance of safety regulations Transport damage Use of non original PV mating plugs and sockets from the HELIOS H4 product series by Amphenol The insta...

Страница 6: ...signed for operating temperatures from 25 C to 70 C If the temperature inside the enclosure exceeds a certain value the inverter automatically regulates the maximum power to protect itself Systems with micro inverters are easy to design and install Each inverter can be mounted on the mounting rack underneath the PV modules but it is recommended to have a place where emergency service work can be e...

Страница 7: ...75sec OFF 0 25sec 1 cycle AC voltage not within tolerance range LED 1sec ON 0 75sec OFF 0 25sec 2 cycles DC voltage not within tolerance range LED 1sec ON 0 75sec OFF 0 25sec 3 cycles AC and DC voltages not within tolerance range LED 1sec ON 0 75sec OFF 0 25sec 4 cycles Internal overtemperature LED 1sec ON 0 75sec OFF 0 25sec 5 cycles Sequence ends 2 sec AUS Insulation measurement on the PV side I...

Страница 8: ... a 24V module The open circuit voltage of the entire PV generator must be less than 50 for INV315 UMpp 60 C input voltage 20 VDC for INV315 50EU The UMpp voltage of the connected string should not fall below the permitted input voltage range even at very high module temperatures 60 C If the temperature rises from 25 C to 60 C the UMpp voltage of 12 V modules drops by approx by approx 3 6 V per mod...

Страница 9: ...e help of accessories that are matched to the mounting frame As an example slot stones can be fastened to the mounting profiles at the positions below the inverter brackets with screws When mounting make sure that the inverter is mounted in the correct installation position the cover must face upwards connection plugs must point downwards 7 2 Installation alternative If mounting on the mounting fr...

Страница 10: ...reases during feed in operation This voltage is measured by the inverter If the voltage at the grid terminals exceeds the limit for grid overvoltage the inverter switches off due to grid overvoltage This circumstance must be taken into account in the AC wiring and when dimensioning the AC line When using several AC circuits in a PV system it is necessary to distribute the feed in phase symmetrical...

Страница 11: ...nnection before connecting it to the inverter Only use original mating plugs and sockets from the HELIOS H4 product range from Amphenol Observe the Amphenol assembly instructions for the DC connectors if you assemble the cables yourself Check that the PV generator is free of earth faults before connecting it to the inverter Before connecting the DC cables to the inverter check whether the maximum ...

Страница 12: ...of the inverter different procedures must be followed Please follow the communication setup procedure that is appropriate for your inverter 8 4 1 RF Communication If the micro inverter is equipped with RF communication the steps for setting up communication including wiring and monitoring are described below Communication via the RFC interface takes place via a frequency of 2 4 GHz In combination ...

Страница 13: ...e short circuit resistance of the switching devices 10 0 Switching off the inverter You must switch off the inverter for adjustment maintenance and repair work Proceed as follows Switch off the mains voltage deactivate the external fuse elements After switching off check that there is no voltage Follow the local regulations for work on electrical installations Danger to life due to electric shock ...

Страница 14: ... dirt 12 3 Laws regulations and technical rules When constructing solar installations the laws and regulations applicable to the respective country at state federal and European or international level must be observed In general the generally recognised rules of technology apply which are usually formulated in the form of standards guidelines regulations provisions and technical rules by state and...

Страница 15: ...ncy 96 European efficiency 95 MPPT efficiency 99 8 Mechanical Data Operating Temperature 25 C 70 C Night time power consumption 30 mW Max altitude a s l 2000 m DC Input Amphenol H4 AC Output female connector Wieland system RSTi mini Dimensions WxHxD 390mm x 100 mm x 30 mm Weight 0 8 kg Cooling natural convection Enclosure material aluminum Protection Degree IP65 iP67 NEMA4 50 Hz Version Nominal AC...

Страница 16: ...v T ambient 0m s P pv 30V P pv 35V P pv 40V P pv 25V 100 W 150 W 200 W 250 W 300 W 15 C 10 C 5 C 0 C 5 C 10 C 15 C 20 C 25 C 30 C PV input power T amb 0 1m s wind speed Derating diagramm Ppv T ambient 0 1 m s P pv 30V P pv 25V P pv 40V Derating diagrams for INV315 6 0 A 6 5 A 7 0 A 7 5 A 8 0 A 8 5 A 9 0 A 9 5 A 10 0 A 250 W 260 W 270 W 280 W 290 W 300 W 310 W 320 W 26 V 28 V 30 V 32 V 34 V 36 V 38...

Страница 17: ...mmen mit den Vorschriften folgender europäischer Richtlinien überein The indicated products are in correspondence with the following regulations of European Council Nummer Kurztitel Number Titel Eingehaltene Vorschriften Observed regulations 2014 30 EU EMV Richtlinie EMC Directive EN 61000 6 2 2005 EN 61000 6 3 2007 EN 61000 3 2 2006 A1 2009 A2 2009 EN 61000 3 3 2008 2014 35 EU Niederspannungsrich...

Страница 18: ...al 12 TR Turkey 13 LT Lithuania 14 LV Latvia 15 BG Bulgaria 16 CY Cyprus 17 SE Sweden 18 CH Switzerland 19 PL Poland 20 CZ Czech Republic 21 SK Slowakia 22 FI Finnland 23 AL Albany 24 IE Ireland 25 SI Slovenia 26 MT Malta 27 HR Croatia 28 RO Romania 29 XZ Kosovo 40 IL Israel 41 AU Australia 42 TN Tunisia 43 BB Barbados 44 CL Chile 45 ZA South Africa 46 IR Iran 47 CN China 48 KZ Kazakhstan 49 IN In...

Страница 19: ...19 11 2019 INV315 50EU AEconversion GmbH Co KG An der Helle 26 59505 Bad Sassendorf Germany Telefon 49 0 2927 9194 10 Telefax 49 0 2927 9194 50 www aeconversion de ...

Отзывы: