17
APAX-5000 I/O Series User Manual
Chapter 3
Infrastructure
3.2.1.2
Power Input
Rated Voltage:
24VDC (±20%)
Dual Power Input:
Supported
Max Current on Bus:
2A
Diagnosis Function:
–
Over/under voltage for input 1&2
–
Over current output on bus
Over Voltage LED Alarm:
Around 28.8V
Over Voltage Shutdown:
Around 36V
Under Voltage LED Alarm:
Around 19.2V
Under Voltage Shutdown:
Around 9V
3.2.1.3
EtherCAT Coupler
Function:
Coupling EtherCAT IO modules to 100BASETX EtherCAT network
Cable:
Ethernet/EtherCAT cable (min. Cat. 5), shielded
Distance between stations:
Max. 100 m (100BASETX)
Number of configurable IDs:
256 (2 x 16-bit ID switch)
Bus Interface:
2 x RJ45 (1 x Input, 1 x Output)
3.2.1.4
Environment
Operation Temperature:
-10~60°C (vertical mounted)
Storage Temperature:
-40~85°C
Relative Humidity:
5~95% (non-condense)
3.2.2
LED Indicator
Figure 3.9 WISE-5074 Module LED Indicator