41
APAX-5000 I/O Series User Manual
Chapter 5
D
igital Module
5.1.1.2
Digital Input:
Channels:
8
Digital Input:
–
Dry Contact:
Logic level 1: close to Iso.GND
Logic level 0: open
–
Wet Contact:
Rated voltage: 24V
DC
Logic level 1: 10~30 V
DC
and -10~-30V
DC
Logic level 0: -3~3V
DC
Input Delay:
–
From logic 0 to 1: 4ms
–
From logic 1 to 0: 4ms
Digital Filter:
3ms
5.1.1.3
Protection
Isolation Voltage:
2,000V
DC
5.1.1.4
Environment
Operation Temperature:
-10~60°C (vertical mounted)
Storage Temperature:
-40~85°C
Relative Humidity:
5~95% (non-condense)
5.1.2
LED Indicator
Figure 5.2 WISE-5051 Module LED Indicator
LED
Color
Indication
Behavior
Power
Green
ON
Power on
Run
Green
ON
EtherCAT connection
Green
Blink
When TX/RX data in transmission
DI0~7
Green
ON
Dry/Wet Logic "1"
OFF
Dry/Wet Logic "0"