15
APAX-5000 I/O Series User Manual
Chapter 3
Infrastructure
Figure 3.7 Wiring for WISE-5001 Power Input
3.1.6
Object Description and Parameterization
3.1.6.1
Status of Power Supply (0x6000-0x6FFF)
Index (hex) Name
Meaning
Data type Flags Default
value
6000:01
Over_Voltage_1
Voltage 1 > 28.8V (24*1.2)
UINT
RO
0x00
6000:02
Under_Voltage_1
Voltage 1 < 19.2V (24*0.8)
UINT
RO
0x00
6000:03
Over_Voltage_2
Voltage 2 > 28.8V (24*1.2)
UINT
RO
0x00
6000:04
Under_Voltage_2
Voltage 2 < 19.2V (24*0.8)
UINT
RO
0x00
6000:05
Over_Current
Current > 2A
UINT
RO
0x00
6000:06
DI0
The digital input channel 0
UINT
RO
0x00
6000:07
DI1
The digital input channel 1
UINT
RO
0x00
6000:08
DI2
The digital input channel 2
UINT
RO
0x00
6000:09
DI3
The digital input channel 3
UINT
RO
0x00
6000:11
Voltage_1
The value of the Voltage 1
REAL
RO
0x00
6000:12
Voltage_2
The value of the Voltage 2
REAL
RO
0x00
6000:13
Current
The value of the Current
REAL
RO
0x00
Содержание WISE-5000 Series
Страница 1: ...User Manual WISE 5000 Series EtherCAT Slice I O Modules ...
Страница 8: ...APAX 5000 I O Series User Manual viii ...
Страница 9: ...Chapter 1 1 Introduction ...
Страница 12: ...WISE 5000 Slice I O Series User Manual 4 ...
Страница 13: ...Chapter 2 2 Hardware Installation ...
Страница 16: ...APAX 5000 I O Series User Manual 8 ...
Страница 17: ...Chapter 3 3 Infrastructure ...
Страница 32: ...APAX 5000 I O Series User Manual 24 ...
Страница 33: ...Chapter 4 4 Analog Input Output Modules ...
Страница 46: ...APAX 5000 I O Series User Manual 38 ...
Страница 47: ...Chapter 5 5 Digital Module ...