The length of the bunch (combination of power supply and data cables) should be a
maximum 1.5 m. If the length of data cables exceeds 1.5 m or if the cable is leading
towards the switchboard, we recommend installing surge protectors.
–
Data cables must not have a reticular tension of
∼
230 V/50 Hz or
∼
120 V/60 Hz.
•
Sufficient space must be left between individual connectors for the handling of cables,
•
To ensure correct functioning of the router we recommend the use of an earth-bonding
distribution frame for the grounding of the power supply of the router, data cables and
antenna within the switchboard.
5.6
Removal from the DIN rail
The DIN rail clip is suitable for a DIN rail according to EN 60715 standard only. The default
position of metal rail clip, which is used for mounting the router on a DIN rail, is shown in
the following figure. Its position can be changed on some models (back or bottom). When
changing the position of the DIN rail clip, tighten the screws with max. 0.4 Nm torque.
Figure 14: Default position of metal DIN rail clip
To remove the router from the DIN rail, push the router down lightly, so the bottom part of
the DIN rail clip (hitched to the DIN rail) gets out of the rail and then pull out the bottom part of
the router away from the DIN rail.
Figure 15: Removal from the DIN rail