28
ADAM-5080 Counter/Frequency Module
ADAM-5080 Counter/Frequency Module
$aaSiØ(data)
$aaSiØ(data)
Name
Set Digital filter Scale
Description Set the filter seconds to start to measure the input signal.
Syntax
$aaSiØ(data)(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system which is to be
calibrate.
Si identifies the sepcified slot.
Ø is the command for setting digital filter scale.
(data) represents filter secends from 8µs~65000 µs. Be
aware that (data) has 5 characters.
(cr) is the terminating character, carriage return (0Dh)
Response
!aa(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exists.
! delimiter character indicating a valid command was
received.
? delimiter character indicating the command was
invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
(cr) is the terminating character, carriage return (0Dh)