ADAM-5080 Counter/Frequency Module
13
User's Manual
Command Syntax
Command Name
Description
$aaSiCj6
Clear Counter
Clear the counters of
the specified
counter/frequency
module
$aaSi7
Read Overflow Flag
The command
requests the
addressed module to
return the status of the
overflow flag of
counter.
@aaSiCjP(data)
Set Initial Counter
Value
Set initial counter value
for counter of the
specified counter
module.
@aaSiCjG
Read Counter Initial
Value
Read initial of the
specified counter
module.
$aaSiCjAhEs
Set Alarm
Disable/Latch
The addressed counter
module is instructed to
set alarm disable or
latch.
$aaSiCjAh
Read Alarm
Disable/Latch
Returns the alarm
mode for the specified
channel.
$aaSiCjCh
Clear Alarm Status
Returns the alarm
status to normal
$aaSiCjAhCSkCn
Set Alarm Connection
Connects the High/Low
alarm of the specified
input channel to the
specified digital output
in the addressed
ADAM-5000 system
$aaSiCjRhC
Read Alarm
Connection
Returns the High/Low
alarm limit output
connection of a
specified input channel
in the addressed
ADAM-5000 system
Содержание ADAM-5000 Series
Страница 1: ...ADAM 5000 Series ADAM 5080 4 channel Counter Frequency Module User s Manual...