ADAM-5080 Counter/Frequency Module
23
User's Manual
#aaSi
#aaSi
Name
Read All Channel Counter (Frequency) Data
Description Return the input value of all channels for the specified
input module for a specified system in engineering unit
only.
Syntax
#aaSi(cr)
# is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.
Si is the I/O slot of ADAM-5000 system you want to
read.
(cr) is the terminating character, carriage return (0Dh)
Response
>(data) (data) (data) (data) (cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exists.
> is a delimiter character.
? is a delimiter character indicating the command being
invalid.
(data) is the input value in engineering units of the
interrogated module of the specified system. If the
numbers of (data) are ten ,counter/frequency mode is in
decimal format.If the numbers of (data) are
eight,counter/frequency mode is in hexdecimal format.
If (data) = “ ”, it means the channel is invalid.
(cr) is the terminating character, carriage return (0Dh).