ADAM-5080 Counter/Frequency Module
21
User's Manual
$aaSiB
$aaSiB
Name
Read Configuration.
Description The command requests the Configuration of slot
Syntax
$aaSiB(cr)
$ is a delimiter character.
aa (range 00-FF) represents the 2-character hexadecimal
address of the ADAM-5000 system you want to
interrogate.
Si identifies the desired slot i
B represents the configuration status command
(cr) is the terminating character, carriage return (0Dh).
Response.
!aarrff(cr) if the command is valid.
?aa(cr) if an invalid operation was entered.
There is no response if the module detects a syntax error
or communication error or if the specified address does
not exist.
! delimiter character indicating a valid command is
received.
? delimiter character indicating the command is invalid.
aa (range 00-FF) represents the 2-character hexadecimal
address of an ADAM-5000 system.
rr=00 represents Bi-direction counter mode.
rr=01 represenrs UP/DOWN counter mode.
rr=02 represents Frequency mode.
ff indicates which format is
ff=00 represents the engineer format.
ff=02 represents the hexdecimal format.
(cr) is the terminating character, carriage return (0Dh).