Temperature Control Units : Sentra with VE Series Instrument
Page: 46
Advantage Engineering, Inc.
525 East Stop 18 Road Greenwood, Indiana 46142
317-887-0729 Fax: 317-881-1277
Service Department Fax: 317-885-8683
www.AdvantageEngineering.com
4
7
208/240
4
5
6
1
L1
7
2
L2
8
3
L3
9
460/480
1
L1
2
L2
3
L3
5
8
6
9
Figure 5.5D
Wiring schematics for 240 and 480 volt pump
motors
Transformer
Figure 5.5E
Figure 5.5C
Wiring schematics for 240 and 480 volt heaters Revised 4/11
Motor Starter and Overload
Block
Figure 5.5F
8.
Replace the motor starter and overload block. Adjust the overload block settings
for the current draw at the new voltage (figure 5.4F).
9.
Once a voltage change is complete, be certain the unit is properly connected to
the new voltage supply, as outlined in section 2.5 of this manual. Restart unit
operations according to section 3 of this manual.