NOTES:

1. Never remove 

ground wire from 

plug.

2. Advantage 

Controls 

recommends that 

adequate surge 

protection be 

used to protect 

products from 

voltage changes in 

your application.

C. Plumbing

  

1.  Tubing Connections

The MicroTron™ pump uses carefully matched components to achieve a predictable  

metering output. This predictability can only be maintained if all fitting sizes remain 

 

unaltered.  

Do not

 attempt to reduce tubing size. All tubing connections should be  

double checked to insure against leakage. If hazardous chemicals are being pumped, 

use shielding around discharge tubing. 

NOTES: 

1. Clear flexible tubing is not intended for pressurized use.

 

2. When cutting lengths of tubing for your installation, ensure a clean, square cut. 

Use short lengths of tubing and as few connections as possible.

 

3. There is an approximate 2.5 psi capability lost for ever 1 foot of vertical rise of the 

discharge tubing to the injection point

.

  

2.  Tubing Nuts

Do not over-tighten the tubing connectors. Tighten the fittings no more than 1/4 turn    

after the fitting contacts the seal. Hand tighten only. Do not use a wrench or pliers    

as they may damage the fittings. Do not use Teflon tape except on NPT fittings. Be    

sure to observe applicable local plumbing codes.

WARNING: Clear flexible tubing is not intended for pressurized use.

3. 

Tubing Connections

3/8"

1/4"

TUBING MUST SLIP OVER NIPPLE

1/4" TUBING 
ADAPTER

IMPORTANT 

THE END OF THE TUBING

MUST EXTEND 1/4" BEYOND ADAPTOR

CAUTION

1.  There are live circuits inside the controller even when the power switch on the front panel is in 

the OFF position. Never open the front panel without first disconnecting power from the outlet. 

Prewired controllers are supplied with an 8 foot, 18 AWG power cord with USA style plug. A #1 

Phillips driver is required to open the front panel.

2. 

Low voltage signal wires (probes, flow switch, water meter,  etc.) should never be run    

in conduit with high voltage (like 115VAC) wires.

3. 

Never attempt to land connections to the controller without first disconnecting power from the outlet.

4. 

Do not block access to disconnect power during mounting and installation.

5.  The controller should be connected to its own isolated circuit breaker, and for best  

 

results,  the ground should be a true earth ground, not shared. Any attempt to bypass the grounding 

will compromise the safety of users and property.

6. 

The  electrical  installation  of  the  controller  must  be  performed  by  trained  personnel  only  and 

conform to all applicable National, State and Local codes.

7. 

Operation of this product in a manner not specified by Advantage Controls may result in damage 

to equipment or persons. 

8. 

Avoid  mounting  in  locations  that  expose  the  controller  to  direct  sunlight,  vapors,  vibration, 

liquid  spills  or  extreme  temperatures;  less  than  0°F  (-17.8°C)  or  greater  than  120°F  (50°C). 

EMI(electromagnetic interference) from radio transmissions and electric motors can also cause 

damage or interference and should be avoided.

!

!

Содержание MicroTron O Series

Страница 1: ...arold Abitz Dr Muskogee OK 74402 Phone 918 686 6211 Fax 888 686 6212 www advantagecontrols com email support advantagecontrols com 05 2019 MicroTron Series O Chemical Metering Pump Installation Maintenance Repair Manual Manual ...

Страница 2: ...eyond their intended functionality intentionally or otherwise or any unauthorized repair Advantage is not responsible for damages injuries or expense incurred through the use of its products The above warranty is in lieu of other warranties either expressed or implied No agent of ours is authorized to provide any warranty other than the above 30 Day Billing Memo Policy Advantage Controls maintains...

Страница 3: ...r S 316 Stainless Seat Material V Viton F Teflon H Hypalon Check Ball C Ceramic D Ceramic single on discharge S Stainless Tubing Connections 1 3 8 PE 75 200 psi 2 PE 250 psi models P MNPT V 3 8 Clear flexible suction tubing Special Options S 3 function injection valve NOTES This list represents our most popular options If you have an option not covered contact the factory or your dealer for more d...

Страница 4: ... gloves and aprons are critical in preventing accidental exposure to dangerous chemicals Liquids under pressure can present a special hazard when a line or seal is punctured resulting in the spraying of chemical many yards away If a chemical spillage occurs consult the Material Safety Data Sheet MSDS for specific instructions regarding the chemical being used IV Installation A Location Select a mo...

Страница 5: ... TUBING ADAPTER IMPORTANT THE END OF THE TUBING MUST EXTEND 1 4 BEYOND ADAPTOR CAUTION 1 There are live circuits inside the controller even when the power switch on the front panel is in the OFF position Never open the front panel without first disconnecting power from the outlet Prewired controllers are supplied with an 8 foot 18 AWG power cord with USA style plug A 1 Phillips driver is required ...

Страница 6: ... the tubing and foot valve in a vertical position at the bottom of the tank Do not allow the foot valve to lay horizontally in the chemical container This defeats the action of the valve and causes the pump to lose prime Keep suction tubing reasonable short and avoid high spots or bends 7 Injection Valve Installation The injection valve is designed to prevent a back flow and to inject chemical int...

Страница 7: ...rther priming is required If fluid is not moving open bleed valve until fluid begins to move When suction line fills close bleed valve Do not over tighten bleed valve damage may occur Thumb and forefinger are all that are required to tighten valve Further tightening will cause damage to bleed valve which will result in flow loss B Adjusting feed rate The standard Model B allows for the exact setti...

Страница 8: ...switch closure it strokes once up to its maximum strokes per minute rate 2 Hall Effect Meter Pacing This option is like the external pacing only the pump divides the incoming switch closures by 9 before stroking on time This is a three wire connection D C voltage signal and ground 3 External Stop Pumps with this option are allowed to stroke as long as they see a closed condition from a dry contact...

Страница 9: ...houlder of shaft It is not necessary to tighten further 8 Replace fluid end Make sure that screws are evenly tightened 9 Reconnect plumbing and power Prime the pump B Suction and Discharge Check Valve Replacement 1 Disconnect suction tubing from pump 2 Unscrew fitting from pump head 3 Remove check valve from suction fitting and replace 4 Remove O ring from cavity in fluid end 5 Remove check valve ...

Страница 10: ... Complete Head Kit 2 Injection Valve 3 Foot Valve 4 Suction Valve 5 Discharge Valve 6 Bleed Valve Assembly 7 Pump Head 8 Pump Diaphragm 9 Support Ring 10 Shaft Seal 11 Head Bolts 12 Priming Tube 13 Suction Tubing 14 Discharge Tubing 15 Weight Complete Head Kit includes items 4 5 6 7 8 and 11 ...

Страница 11: ...sembly INJ __ __ __ __ Optional 3 Function Injection Valve 3FV __ __ __ __ 3 Foot Valve Assembly FTV __ __ __ __ 4 Suction Valve Assembly SUC __ __ __ __ 5 Discharge Valve Assembly DIS __ __ __ __ 6 Priming Valve Assembly PRI __ __ __ __ Body Seat Ball Connection K Kynar V Viton C Ceramic 1 3 8 Tube S 316 Stainless F Teflon D Single 2 1 4 Tube H Hypalon S Stainless 3 3 8 Tube K 3 8 Tube P 1 4 Pipe...

Страница 12: ...stable rate check settings Readjust as required Worn or contaminated check valves Inspect clean or replace as necessary Obstruction in suction line Check suction line for obstructions clogging kinks or pinch points Clogged foot valve screen Clean or replace foot valve screen Output system pressure too high Relocate the injector to a lower pressure part of the system Diaphragm worn or torn Replace ...

Страница 13: ...13 Application Notes ...

Страница 14: ...14 Application Notes ...

Страница 15: ...15 Application Notes ...

Страница 16: ... of your water treatment equipment needs Cooling Tower Controllers Boiler Blow Down Controllers Blow Down Valve Packages Solenoid Valves Water Meters Chemical Metering Pumps Corrosion Coupon Racks Chemical Solution Tanks Solid Feed Systems Feed Timers Liquid Level Controllers Glycol Feed Systems Pre Fabricated Systems Get the Advantage ...