Advantage Controls MicroTron O Series Скачать руководство пользователя страница 4

4

II. Unpacking

The Advantage MicroTron™ pump has been shipped to you as a complete package, ready for installation. 

If shipping carton shows any signs of damage, notify the shipping company immediately upon receipt. 

Advantage Controls cannot be held responsible for damage from shipping.  Unpack the carton and insure 

that the following items are present:

1.  Metering pump                                    

 4.  

Injection fitting

2.  Suction, discharge and priming tubing            5.  

Instruction manual

3.  Foot valve and weight

III. Safety Considerations

 

NOTE:   All MicroTron™ pumps are primed with water before leaving the factory. If the solution to 

be pumped is not compatible with water, disassemble the pump fluid end before use. After 

disassembly, thoroughly dry the pump head, valves, and seals before pump is reassembled 

and used.

  A.  Chemical Compatibility

MicroTron™ metering pumps are designed to work with most liquid chemicals depending upon your 

pump’s liquid end materials of construction. A chemical resistance chart is available for determining 

specific compatibility with a wide variety of chemicals. If you have further compatibility questions, contact 

Advantage Controls’ service department at 1-800-743-7531.

 

B.  Safety and Preparation

Always wear the proper protective clothing and gear when working around chemicals and chemical 

metering pumps. Safety glasses, gloves, and aprons are critical in preventing accidental exposure 

to dangerous chemicals. Liquids under pressure can present a special hazard when a line or seal is 

punctured resulting in the spraying of chemical many yards away. If a chemical spillage occurs, consult 

the Material Safety Data Sheet (MSDS) for specific instructions regarding the chemical being used.

IV. Installation

 

 

A. Location

Select a mounting location convenient to the chemical supply and power for the pump. Do not install the 

pump in a location where the ambient temperature exceeds 120 degrees F (50

o

C). Higher temperatures 

will affect the output as well as the useful life of the pump. While the MicroTron™ pump is suitable for 

most outdoor installations, do not use the standard poly tubing in direct sunlight. If you must mount pump 

in direct sunlight or under bright fluorescent lights, consult your distributor or the factory. Accessory 

item R00225 (plastic mounting bracket) is recommended for a secure installation.

 

 

B. Electrical

1.  Standard MicroTron™ pumps have a voltage regulated internal power supply capable of  operating  

  in the range of approximately 95 to 135 VAC. Use a supply voltage of 100 to 120 VAC for best  

  results. The 3-wire grounded plug  must be used in a 3-wire wall plug.

  CAUTION:  Never  remove ground wire from plug!

 

2.  With a 220 volt option, the  MicroTron™ pump has a voltage regulated internal power supply capable 

 

    of operating in the range of approximately  195 to 260 VAC. Use a supply voltage of 210 to 250   

    VAC for best results. 

Содержание MicroTron O Series

Страница 1: ...arold Abitz Dr Muskogee OK 74402 Phone 918 686 6211 Fax 888 686 6212 www advantagecontrols com email support advantagecontrols com 05 2019 MicroTron Series O Chemical Metering Pump Installation Maintenance Repair Manual Manual ...

Страница 2: ...eyond their intended functionality intentionally or otherwise or any unauthorized repair Advantage is not responsible for damages injuries or expense incurred through the use of its products The above warranty is in lieu of other warranties either expressed or implied No agent of ours is authorized to provide any warranty other than the above 30 Day Billing Memo Policy Advantage Controls maintains...

Страница 3: ...r S 316 Stainless Seat Material V Viton F Teflon H Hypalon Check Ball C Ceramic D Ceramic single on discharge S Stainless Tubing Connections 1 3 8 PE 75 200 psi 2 PE 250 psi models P MNPT V 3 8 Clear flexible suction tubing Special Options S 3 function injection valve NOTES This list represents our most popular options If you have an option not covered contact the factory or your dealer for more d...

Страница 4: ... gloves and aprons are critical in preventing accidental exposure to dangerous chemicals Liquids under pressure can present a special hazard when a line or seal is punctured resulting in the spraying of chemical many yards away If a chemical spillage occurs consult the Material Safety Data Sheet MSDS for specific instructions regarding the chemical being used IV Installation A Location Select a mo...

Страница 5: ... TUBING ADAPTER IMPORTANT THE END OF THE TUBING MUST EXTEND 1 4 BEYOND ADAPTOR CAUTION 1 There are live circuits inside the controller even when the power switch on the front panel is in the OFF position Never open the front panel without first disconnecting power from the outlet Prewired controllers are supplied with an 8 foot 18 AWG power cord with USA style plug A 1 Phillips driver is required ...

Страница 6: ... the tubing and foot valve in a vertical position at the bottom of the tank Do not allow the foot valve to lay horizontally in the chemical container This defeats the action of the valve and causes the pump to lose prime Keep suction tubing reasonable short and avoid high spots or bends 7 Injection Valve Installation The injection valve is designed to prevent a back flow and to inject chemical int...

Страница 7: ...rther priming is required If fluid is not moving open bleed valve until fluid begins to move When suction line fills close bleed valve Do not over tighten bleed valve damage may occur Thumb and forefinger are all that are required to tighten valve Further tightening will cause damage to bleed valve which will result in flow loss B Adjusting feed rate The standard Model B allows for the exact setti...

Страница 8: ...switch closure it strokes once up to its maximum strokes per minute rate 2 Hall Effect Meter Pacing This option is like the external pacing only the pump divides the incoming switch closures by 9 before stroking on time This is a three wire connection D C voltage signal and ground 3 External Stop Pumps with this option are allowed to stroke as long as they see a closed condition from a dry contact...

Страница 9: ...houlder of shaft It is not necessary to tighten further 8 Replace fluid end Make sure that screws are evenly tightened 9 Reconnect plumbing and power Prime the pump B Suction and Discharge Check Valve Replacement 1 Disconnect suction tubing from pump 2 Unscrew fitting from pump head 3 Remove check valve from suction fitting and replace 4 Remove O ring from cavity in fluid end 5 Remove check valve ...

Страница 10: ... Complete Head Kit 2 Injection Valve 3 Foot Valve 4 Suction Valve 5 Discharge Valve 6 Bleed Valve Assembly 7 Pump Head 8 Pump Diaphragm 9 Support Ring 10 Shaft Seal 11 Head Bolts 12 Priming Tube 13 Suction Tubing 14 Discharge Tubing 15 Weight Complete Head Kit includes items 4 5 6 7 8 and 11 ...

Страница 11: ...sembly INJ __ __ __ __ Optional 3 Function Injection Valve 3FV __ __ __ __ 3 Foot Valve Assembly FTV __ __ __ __ 4 Suction Valve Assembly SUC __ __ __ __ 5 Discharge Valve Assembly DIS __ __ __ __ 6 Priming Valve Assembly PRI __ __ __ __ Body Seat Ball Connection K Kynar V Viton C Ceramic 1 3 8 Tube S 316 Stainless F Teflon D Single 2 1 4 Tube H Hypalon S Stainless 3 3 8 Tube K 3 8 Tube P 1 4 Pipe...

Страница 12: ...stable rate check settings Readjust as required Worn or contaminated check valves Inspect clean or replace as necessary Obstruction in suction line Check suction line for obstructions clogging kinks or pinch points Clogged foot valve screen Clean or replace foot valve screen Output system pressure too high Relocate the injector to a lower pressure part of the system Diaphragm worn or torn Replace ...

Страница 13: ...13 Application Notes ...

Страница 14: ...14 Application Notes ...

Страница 15: ...15 Application Notes ...

Страница 16: ... of your water treatment equipment needs Cooling Tower Controllers Boiler Blow Down Controllers Blow Down Valve Packages Solenoid Valves Water Meters Chemical Metering Pumps Corrosion Coupon Racks Chemical Solution Tanks Solid Feed Systems Feed Timers Liquid Level Controllers Glycol Feed Systems Pre Fabricated Systems Get the Advantage ...