22
• If Yes, inspect end of level wand for debris or damage, replace if needed. (The float at bottom of the wand
should have free movement, up and down.
• If No, inspect wire for damage. If no damage visible inspect internal wiring. (See NO POWER TO UNIT,
POWER PRESENT AT RECEPTACLE 1 thru 10 above)
4.
If no resolution is found, record Serial / Model numbers and call customer service
LOW LEVEL ALARM STAYS ON
1.
Disconnect level wand connection and short across connectors with screw driver. (this is low voltage and not
dangerous)
2.
This turns off the alarm. There is a problem with the wand itself.
3.
Inspect the float end of the level wand.
4.
If the float is free moving replace wand.
5.
Shorting the connecter does not turn off alarm. Inspect internal wiring. (See
NO POWER TO UNIT, POWER
PRESENT AT RECEPTACLE 1 thru 10 above)
6.
Still no resolution record Model / Serial numbers and call customer service.
Maintenance
Maintenance and care will depend upon the usage and environment in which the system is subjected to.
The following is the suggested regular maintenance required to keep the glycol feed system operating
properly:
TANK AND PLUMBING
Periodically check the piping and tubing to insure proper discharge of the glycol solution. The strainer
should be periodically checked for clogging and wear. The level wand should be removed and cleaned to
prevent clogging.
GEAR PUMP
Check for proper operation. If any pump/motor noises, leaks or changes in operation are detected, the
pump should be removed and examined by a certified technician. Gear pump repairs can be difficult and
should only be attempted by qualified personnel. Improper repairs or assembly can result in pump failure
and nullification of the warranty. No lubrication is required.
PRESSURE RELIEF VALVE
Periodic checking and replacement of the adjustment seal is the only maintenance required.
17
Note:
Dual Digital Glycol Feeders utilize one controller monitoring two separate pressures sensors. The
menu will have additional selections for each function. Both pressure readings will be displayed in the Run
screen: "P1: 060 P2045 psi".
Dual Digital Glycol Feeder (WCD-370302)
No. 530
Calibrated Pressure Relief Valve
Features
A calibrated adjustment feature for setting the valve to the relief pressure required.
All Bronze construction
All stainless steel springs
Specifications
Sizes ½” and ¾” (15 and 20 MM)
Inlet (bottom) is male threaded, NPT
Outlet (side) is female threaded, NPT.
Design
Wats No. 530 is spring operated bronze relief valve designed to be used
as protection against excessive pressure of water, oil or air.
This device is designed for emergency safety relief and shall not be used
as an operation control.
Buna-N disc on machined body seat.
Application
Ideally suited as a by-pass thermal expansion relief valve.
There are a wide variety of applications where the valve is used as a
protective device. One such application would be on various pipelines.