9
Calibration
Control Set
Setpoint 500.0
Diff 050.0
Direction: Rise
High Alarm 700.0
Low Alarm 300.0
Limit hh:mm
Display Units: PSI
Decimal: XX.XX
4mA = 00.00
20mA = 99.99
Timer Set
Pulse
Run After 0100
Run Time mm:ss
Post Control
010% of Cntrl
Limit Time hh:mm
With Control
Limit Time hh:mm
Alarm Control
Batch
Run Tim mm:ss
28-Day (Bio)
A: All Days
A: All Weeks
A: Start 12:00a
A: Run Time hh:mm
A: Prbld hh:mm
A: Lkout hh:mm
B: All Days
B: All Weeks
B: Start 12:00a
B: Run Time hh:mm
B: Prbld hh:mm
B: Lkout hh:mm
Recycle
Off Time hh:mm
Run Time mm:ss
Utility
Only shows
if WM active
Water Meter
Clock Set
Force Set
Diagnostics
Password 0000
Reset Meter? N
Set Time
Force On: Both
Nano-4-20
Hi Lvl: Close
Meter Units
Set Date
FW: ?.?.?
DigIn: Drum 1&2
Meter Value
Set Day & Week
Test Keypad
Meter Debounce
Test Display
R1 Cntrl mm:ss
Reset Cal? N
R2 Timer mm:ss
Feed OK w/Ctrl
No Feed No Flow
Raw A/D: ????
Digi 0/1
If Yes is selected the
current calibration A/D
values are stored.
If a Reset Cal is done
these A/D values are
restored for the 4 & 20.
0-32,767 scale
Identify logic
state of vaious
digital inputs.
Only shows
if WM active
4-20 Output
4 mA = 00.00
Sim 4mA: OFF
20mA= 99.99
Sim 20mA: OFF
Set 4 and 20mA
out at desired
sensor reading.
Sim 4 and 20mA
will force output
to either 4 or 20
regardless of
reading.
4mA applied: N
4mA In: 04350
20mA applied: N
20mA In: 21350
Press Enter only
if a 4mA or 20mA
signal is being
received when in
those calibration
screens.
Set the decimal
for displayed
numerical format
and the 4mA and
20mA for what the
value of that range
desired at those
two mA values
CAL 20: 2948
CAL 4: 0590
Set Default? N
Increase the
Debounce to
prevent false
contacts.
Set to 0 when
a paddle wheel
meter is used.
The CAL 4 or 20
can be used to
change the signal
of either the 4 or
20 value to match
those two points
with the recieving
device
Disabled
Select WM or
Drum Level for
relay 1 , relay
2 or 1 & 2
VI. NanoTron mA Menu Map
NanoTron conductivity units have a main menu circle that includes:
Calibration
- Calibrating the reading
Control Set
- Setting the set point, sample method and
alarms
Timer Set
- Select the timer type and run values
Configure
- Password, flow switch direction, units of
measure and more
4-20 Output
- Calibrate and set the range of the mA output
Pulse Output
- Set the range and speed of the pulse output
Water Meter
- Reset totalizer and setting contact value
Clock Set
- Set time, date and week
Force Set
- Set the force on time for manual relay
activations
Diagnostics
- Tests and calibration reset