background image

11

19

Parts List

Содержание GF Series

Страница 1: ...al Model GF Digital Glycol Feeder with NANO Installation Maintenance Repair Manual Advantage Controls P O Box 1472 Muskogee OK 74402 Phone 918 6866211 Fax 888 686 6212 www advantagecontrols com 11 2018 ENTER ...

Страница 2: ...eads a solid state pressure transducer displays system pressure and uses a 16 character keyboard for the entry of control parameters The micro processor has built in real time clock and EEPROM back up for all user settings in case of power interruptions Setting for all functions are made using the keyboard readings are displayed on a back lit 16 character alphanumeric display Advantage Controls Gl...

Страница 3: ...d for transfer duty into tank LOOP SELECTION 0 No loop 1 Sch 80 PVC loop 100 PSI max 100 F max 2 Copper brass loop 100 PSI max 180 F max 3 Carbon steel loop 100 PSI max CONTROL SELECTION M ETL listed NANO N with alarm buzzer and dry contact N ETL listed NANO N controller with timer for relay 2 single loops OPTIONS 1 240V 2 4 20mA output of pressure on digital controller 3 Solenoid valve for pressu...

Страница 4: ...hile making any connections If power is supplied to the unit line voltage will be present on the relay cards 3 Low voltage signal wires transducer level alarm etc should never be run in conduit with high voltage wires Mounting Instructions Select a mounting location that provides the operator easy access to the unit and a clear view of the controller The location should be convenient to grounded e...

Страница 5: ...tside edge Note This is for mounting holes only Controller will extend beyond this depth GLYCOL STAND FOOT PRINT C D A B C D E 30 gal 113 5L 23 60 3 cm 51 129 5 cm 27 69 8 cm 25 64 7 cm 30 77 4 cm 55 gal 208 1L 27 69 8 cm 65 165 1 cm 27 69 8 cm 25 64 7 cm 32 81 2 cm 100 gal 378 5L 31 79 3 cm 66 167 6 cm 37 93 9 cm 35 88 9 cm 38 96 5 cm ...

Страница 6: ... Power Output J2 NanoTron N Logic Card Contrast Power 1 2 3 4 5 ON OFF If the mA OUT Power switch is on INT the unit s internal 24 VDC is applied to the output If set for EXT the external loop out power supplied is used on the output Pulse Out mA OUT Flow Switch WM or Dig In mA IN Internal 24 VDC Ext Out Loop Power Input Device Input Device Jump from 24 to mA IN Wiring for two wire input sensors t...

Страница 7: ...h menu selections or setting options Use left or right arrows to move cursor while making a numerical value change ENTER V System Operation Overview Description of Menus NanoTron controllers have three modes of operation Run Menu and Force All menus are circular Pressing the DOWN key will display the next line of information on the display Run This mode is for normal operation The control relays w...

Страница 8: ...Password 0000 Flow Sw Close DigIn W Meter Feed OK w Ctrl No Feed No Flow Pulse ON 4 20 Output 4 mA 000 0 Sim 4mA OF 20mA 999 9 Sim 20mA OF Set 4 and 20 out at desired sensor readin Sim 4 and 20 will force outp to either 4 or regardless of reading 4mA applied N 4mA In 04350 20mA applied N 20mA In 21350 Press Enter only if a 4mA or 20mA signal is being received when in those calibration screens Sele...

Страница 9: ... out at desired sensor reading Sim 4 and 20mA will force output to either 4 or 20 regardless of reading Set the decimal for displayed numerical format and the 4mA and 20mA for what the value of that range desired at those two mA values CAL 20 2948 CAL 4 0590 Set Default N Increase the Debounce to prevent false contacts Set to 0 when a paddle wheel meter is used The CAL 4 or 20 can be used to chang...

Страница 10: ...ve additional selections for each function Both pressure readings will be displayed in the Run screen P1 060 P2045 psi Dual Digital Glycol Feeder WCD 370302 No 530 Calibrated Pressure Relief Valve Features A calibrated adjustment feature for setting the valve to the relief pressure required All Bronze construction All stainless steel springs Specifications Sizes and 15 and 20 MM Inlet bottom is ma...

Страница 11: ...11 19 Parts List ...

Страница 12: ...p 1 Before removing the pump head loosen the six head screw a half turn 2 Replace blown fuse and energize pump 3 If this corrects issue de energize pump tighten six screw proceed with Star Up 4 If this doesn t solve issue the pump head should be removed and inspected for particles Because of tolerance in the gears it doesn t take a big particle to freeze the motor 5 Before removing the head be sur...

Страница 13: ...resolution record Model Serial numbers and call customer service Maintenance Maintenance and care will depend upon the usage and environment in which the system is subjected to The following is the suggested regular maintenance required to keep the glycol feed system operating properly TANK AND PLUMBING Periodically check the piping and tubing to insure proper discharge of the glycol solution The ...

Страница 14: ...ranty is in lieu of other warranties either expressed or implied No agent of ours is authorized to provide any warranty other than the above 30 Day Billing Memo Policy Advantage Controls maintains a unique factory exchange program to ensure uninterrupted service with minimum downtime If your unit malfunctions call 1 800 743 7431 and provide our technician with Model and Serial Number information I...

Страница 15: ...15 ...

Страница 16: ...ment needs Cooling Tower Controllers Boiler Blow Down Controllers Blow Down Valve Packages Solenoid Valves Water Meters Chemical Metering Pumps Corrosion Coupon Racks Chemical Solution Tanks Solid Feed Systems Feed Timers Filter Equipment Glycol Feed Systems Pre Fabricated Systems Get the Advantage 5 4 3 2 1 ENTER HELP 5 4 3 CHANGE RUN SET UP 0 9 8 2 1 7 6 HOME BACK ...

Отзывы: