57
SENSITIVITY ADJUST MODE (SMOKE )
[ Alarm = 192 ]
[ Mode = 2 ][ Pre-Alarm= 160 ]
[ Delay = 0s][ Min.Value= 0 ]
[SAM/SSM]
SPECIAL SENSITIVITY MODE (SMOKE )
[SSM/Clock = 1 ][ Alarm = 192 ]
[ Mode = 1 ][ Pre-Alarm= 160 ]
[ Delay = 0s][ Min.Value= 0 ]
[SAM/SSM]
5.5.1.3 V350 Heat Detector
The V350 can be configured as either a rate of rise or static response heat detector using the hand held
programmer (VPU100). The basic sensitivity is in accordance with EN54-5 A1R or a fixed high
temperature static response in accordance with EN54-5 BS.
SENSITIVITY ADJUST MODE (HEAT RISE )
[ Alarm = 192 ]
[ Pre-Alarm= 160 ]
[ Delay = 0s][ Min.Value= 0 ]
[SAM/SSM]
The alarm threshold is fixed at 192 for either the A1R (58°C static response level) or the BS (78°C static
response level) standard. The pre-alarm value can be modified and the static alarm delay can be changed. The
actual calculated thermal value on its heat element can be viewed (Sub Address 1).
Note: The device has a unique type code depending on its programmed operating characteristic.
5.5.1.4 LV100 Smoke Detector
The LV100 is the same as the V100 with the exception that it does not contain an isolator or a green LED
mode. It supports 4 sensitivity modes on the optical element the same as the V100.
5.5.1.5 LV200 Multi Detector
The LV200 is the same as the V200 with the exception that it does not contain an isolator or a green LED
mode. It supports the multi-mode, heat only and smoke only sensitivity modes as per the V200.
5.5.1.6 LV350 Heat Detector
The LV3500 is the same as the V350 with the exception that it does not contain an isolator or a green
LED mode.
NOTE: A maximum of only 32 LVxxx devices must be installed between the isolators of other devices.
5.5.1.7 Mounting Base VB100
5.5.1.8 Detector Magnet Testing
IN
OUT
Remote Indicator
Two marks on the base indicate the position of the test sensor on the
detector. Placing a magnet against the detector housing will cause the
detector to change its analogue value to 255 for approximately 5
seconds.
Mounting bases are 110mm (4¼”) diameter.
Refer to diagram above for basic loop wiring
information.
NOTE: The remote output operating current must
be limited by means of a series resistor to not
more than 20mA. The FI100 Remote indicator
can be connected directly.
This magnet test is not a substitute for
proper smoke or heat testing methods
but can aid in initial system testing.
Refer to the individual devices as to whether this
feature is supported.
www.acornfiresecurity.com
www.acornfiresecurity.com
Содержание MX-4200V
Страница 68: ...68 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Страница 69: ...69 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Страница 70: ...70 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Страница 71: ...71 USER NOTES www acornfiresecurity com www acornfiresecurity com ...
Страница 72: ...www acornfiresecurity com www acornfiresecurity com ...