38
3.3.8 Zones
The Commission Zones option lists all the zones in use by the panel and allows the zone text description to be
changed.
[Commission Zones]
Zone Location
0001 BASEMENT WEST
0002 RECEPTION
0015 EAST WING
0018 TOWER BLOCK
To change the location text assigned to the Zone, press the
✔
button when the Zone Location Text is
highlighted. Refer to Section
for guidance on how to change text descriptions.
To select a different zone, use either the scroll up/down keys, or just type in the number of the required zone,
followed by the
✔
button. Note that only zones in use are displayed.
3.3.9 Exit
To exit the Commission Mode and return the panel to normal operation (ie level 2), select the “Exit” option. The
display will prompt for confirmation of the level 3 password. For example:
[Commission Menu 1]
Please Enter Your Password
Next Menu
If the password is incorrect (this will be indicated) or if the password is not entered within 5-seconds, the display
will revert to the Commission Level Menu and level-2 will not be entered.
After commissioning, the panel must always be returned to level 2 (or level 1) to give normal fire coverage.
3.3.10 Outputs
The “Cause and Effect” programming is a schedule of actions that will turn on one or more outputs dependant
on a set of input events.
The Outputs Option provides the means to create simple or complex “cause and effect” programming within the
panel. Delays can be introduced to allow a phased evacuation of a building (Note this is different to an
“Investigation Delay” which is detailed in section
This section describes the settings and options in detail for each parameter. Refer to
for a description of how to program a typical requirement.
More complex “Cause and Effect” programming may be undertaken using the PC Configuration tool.
When the OUTPUTS Option is selected, the display shows the cause and effect programming for Output Group
1. For example:
[Output Group 1] [ 3.9% Mem used]
ZONE GROUP CAUSE STYLE=Delay->MODE
1
1
ANY FIRE 00 - On
2 1 ANY FIRE 00 - On
3 1 ANY FIRE 00 - On
4 1 ANY FIRE 00 - On
To simplify the cause & effect programming, one or more outputs that will respond in the same way when the
same set of input events occurs can be grouped together. This association of outputs is called an Output Group.
The panel can support up to 200 of these Output Groups.
To select a different Output Group, highlight any group number and then enter the number of the output group
required using the
number
buttons. The display always shows the Output Group is shown in the top left corner.
www.acornfiresecurity.com
www.acornfiresecurity.com
Содержание MX-4200V
Страница 68: ...68 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Страница 69: ...69 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Страница 70: ...70 This page is intentionally left blank www acornfiresecurity com www acornfiresecurity com ...
Страница 71: ...71 USER NOTES www acornfiresecurity com www acornfiresecurity com ...
Страница 72: ...www acornfiresecurity com www acornfiresecurity com ...