3.3.4 Inputs
The display presents a list of the programmable inputs along with their current settings.
[Input Settings]
PROG INPUT 1:
.
NOT IN USE
.
PROG INPUT 2:
NOT IN USE
PROG INPUT 3:
Use the
buttons to highlight the required input and
then press the
button to select / change it.
The table below details each available input and the
programmable settings.
The default setting for all inputs is NOT IN USE except:
KEY-SWITCH 1 = LEVEL 2 ACCESS
KEY-SWITCH 2 = MODE SELECT
Inputs
29
Setting Options
Comments
PROG INPUT 1
NOT IN USE
The Input is not used.
PROG INPUT 2
*
SOUND ALARMS
Activating an input with this setting will cause all sounder outputs to operate as
programmed.
PROG INPUT 3
*
SILENCE ALARMS
Activating an input with this setting will cause all sounder outputs to be Silenced
(where permitted).
PROG INPUT 4
*
RESET
Activating an input with this setting will cause the panel to be reset (if permitted).
KEY-SWITCH 1
EXT. FAULT
Activating an input with this setting will register a fault condition on the panel.
KEY-SWITCH 2
MANUAL TRIGGER
Activating an input with this setting will initiate the manual release activated
condition.
PRESSURE
Activating an input with this setting will register a pressure warning condition.
VALVE MON
Activating an input with this setting will register a Valve Monitor warning
condition.
MODE SELECT
Activating an input with this setting will select MANUAL ONLY mode. Note: When
multiple inputs are defined as mode select, then any switch in the active state will
set the system into MANUAL ONLY mode.
HOLD
Activating an input with this setting will stop the activated condition countdown
timer preventing the release of the extinguishant.
ABORT
Activating an input with this setting will abort the activated condition.
*
LEVEL-2 ACCESS
Activating an input with this setting will enable Level-2 Control Keys and Menu
functions. A password is not required.
START EXTRACT
Activating an input with this setting will turn on any output configured as an
Extract output. The output will remain on for the programmed time.
KEEP EXTRACT ON
Activating an input with this setting will turn on any output configured as an
Extract output. The output will remain on irrespective of any programmed
operation or times.
DISABLE GAS
Activating one or more inputs with this setting will disable extinguishing (in the
same manner as the level-2 Disable/Enable menu option). Manual and automatic
triggering of gas release will be inhibited.
*
DISABLE ZONES
Activating one or more inputs with this setting will disable all detection zones.
DISABLE AUTO ZN
Activating one or more inputs with this setting will disable all detection zones
which can affect an automatic release of gas (zones included in the cause &
effect logic).
29
For compliance with EN54-13 monitoring requirements, Inputs 1-4 shall only be used for EN12094-
1 functions. Functions marked with a ‘*’
should not be used.