www.advancedco.com
30
[Extinguish C&E]
Release Active When:-
TWO Z1&Z2 : √
.
TWO Z1&Z3 : X
TWO Z2&Z3 : X
ALL Z1&Z2&Z3 : --
Some options are mutually exclusive. Depending on the
options selected, some options are inhibited and cannot be
adjusted
– the current setting is shown as ‘- -‘.
The settings only apply to the AFD inputs. A Manual
Trigger input will immediately generate the activated
condition.
If all three ‘Two Zone’ parameters are enabled then the
activated condition is established when any two of the
three zones are in the fire condition.
IMMEDIATE Z1 : --
IMMEDIATE Z2 : --
IMMEDIATE Z3 : --
Use the
buttons to highlight the required option and then press the
button to select it. The table below
details each available option.
Parameter
Comments / Description
Options
Default
Setting
TWO Z1&Z2
Determines if the activated condition is established by a
fire condition in two zones
– Zones 1 and 2.
, X, --
TWO Z1&Z3
Determines if the activated condition is established by a
fire condition in two zones
– Zones 1 and 3.
, X, --
X
TWO Z2&Z3
Determines if the activated condition is established by a
fire condition in two zones
– Zones 2 and 3.
, X, --
X
ALL Z1&Z2&Z3
Determines if the activated condition is established only
when all three zone detection circuits are in a fire
condition.
28
, X, --
--
IMMEDIATE Z1
Determines if the activated condition is established when a
fire occurs on Zone 1
, X, --
--
IMMEDIATE Z2
Determines if the activated condition is established when a
fire occurs on Zone 2
, X, --
--
IMMEDIATE Z2
Determines if the activated condition is established when a
fire occurs on Zone 3
, X, --
--
3.3.3.3 Extract Set-Up
The display presents a menu of parameter options along with their current settings.
[Extract Settings]
EXTRACT MINS: 0
.
EXTRACT MODE:
MANUAL PROMPT
Use the
buttons to highlight the required option and
then press the
button to select it.
The table below details each available option.
Parameter
Comments / Description
Options
Default
Setting
EXTRACT MINS
Specifies the duration of the extract signal following
release of the extinguishant.
0
– 120 Minutes
0
EXTRACT MODE
Specifies whether the panel should prompt to start the
extract phase or whether the extract output should turn on
immediately following discharge.
MANUAL PROMPT
AUTOMATIC
MANUAL
PROMPT
3.3.3.4 Release Signal Termination (Test Function)
Section
4.21.5
A special Engineer function is provided to terminate an extended active extinguishing
control signal for the purposes of testing the system. This is provided at Level 2 using
the EXTINGUISHING menu option. When prompted, enter the Level 3 password
and a further option (STOP RELEASE: YES) is provided in the menu. Highlight this
option and press the
button to turn off the extinguishing control signal output.
28
This setting is not in accordance with BS EN 12094-1: 2003.