6.1 Troubleshooting (continued) 

Fan System 

 

Please use caution when troubleshooting or repairing all electrical components. Be certain that 
all power is disconnected from the

 

COOL-

SPACE

®

 

unit before the cooling pads or fan guard 

are removed to gain access to the fan.

 

 

Direct & Belt Drive Models 

 

Problem 

Check 

Solution 

Fan won't run and makes no 
sound. 

Power cord, extension cord, 
switches, circuit breaker, GFI 
ground fault. 

Reconnect power or extension 
cord. Reset breaker. 

Fan motor won

t run and makes 

a humming sound. 

Blade in contact with shroud. 
Motor stalled (will not turn by 
hand). 

Re-center blade hub. 
Replace motor. 

Breaker trips or fuse blows when 
fan is started. 

Motor stall. 
Check power source for min. 
220v/10 amp. Extension cord. 

Replace motor. 

Upgrade power supply. 
Replace with heavier cord. 

Motor overheating and shutting 
off. Restarting several minutes 
later. 

Extension cord gauge too small 
Inlet air obstructed or too 
close to wall 
Faulty motor 
Loose belt 

Replace with heavier cord 
Provide minimum 1 metre 
inlet clearance. 
Replace motor. 
Tighten belt 

Fan motor won

t run and switch 

makes soft clicking sound. 

Switch making good contact. 

Replace switch. 

Fan blade doe

sn’t turn 

and unit 

makes squealing sound. 

Motor stall (as above). Fan 
belt loose or broken. 
Fan pulley spinning on shaft. 

Replace motor. 
Tighten or replace fan belt. 
Tighten pulley set screw. 

Fan belts do not last very long. 

Motor and fan pulleys alignment. 

Realign motor and fan pulleys. 

Fan will not reach speed but 
turns and makes humming 
sound. 

Capacitor (where visible) and 
motor electrical connections. 
Extension cord to small. 

Replace capacitor or motor. 
Increase cord gauge. 

 

 

 

 

 

 

 

 

 

Содержание COOL-SPACE CS5-16

Страница 1: ...16 CS6 36 CS5 48 220V 60HZ GLACIER AVALANCHE BLIZZARD IMPORTANT SAFETY INFORMATION INSIDE Serious Injury or death possible Read understand and follow all safety information and instructions in the manual before using or servicing this product ...

Страница 2: ... adjusting the water flow 4 5 0 Maintenance and storage 4 5 1 Removing the cooling media accessing the inside of the unit 4 5 2 Daily maintenance 4 5 3 Periodic maintenance 5 5 4 Storage 5 6 0 Troubleshooting Repair 6 6 1 Troubleshooting 6 9 6 2 Repair procedures 10 11 6 3 Technical support 11 7 0 Warranty 12 7 1 Warranty form 12 7 2 Warranty parts 12 7 3 Optional accessories and replacement parts...

Страница 3: ...ger units are shipped on a wooden skid with a cardboard cover and lid The cardboard cover simply lifts off the COOL SPACE unit The cooler must be lifted off the wooden skid 3 0 Set up of the COOL SPACE unit The COOL SPACE unit is factory tested and ready to use The unit should be placed on a level surface and the castors locked to prevent inadvertent movement Follow instructions below to connect w...

Страница 4: ...d is required refer to Table 2 for the proper 3 conducter heavy duty cord required Do not exceed the amperage ratings of the extension cord Undersized extension cords result in excessive drops in voltage which cause the electric motors to generate excessive heat This condition results in inefficient motor operation and premature motor failure WHICH WILL VOID THE WARRANTY Table 1 Electrical require...

Страница 5: ...hes may interfere with the air flow An attempt should be made to locate the unit in such a manner that interruption of the air pattern is held to a minimum Multiple units may be required to cover larger areas When the COOL SPACE unit is placed near a wall or other vertical obstruction it is recommended that there be a space of at least 1 metre between the back pad side of the unit and the obstruct...

Страница 6: ... without proper water treatment will create mineral deposit build up causing the pump to fail which is NOT COVERED BY WARRANTY Pump is equipped with a LOW WATER CUT OFF which may take up to 5 minutes to reset each time the power is turned on 5 0 Maintenance and storage ELECTRICAL SHOCK HAZARD Disconnect the power supply before performing any service or maintenance on the unit Failure to do so may ...

Страница 7: ...with either a towel or wet dry vacuum 6 Check belt for tightness if applicable 7 Remove the water spray bar and its plug Insure holes are free of debris 8 Reinstall pads and pad retainer 9 Reinstall rear guard if applicable To keep the COOL SPACE unit operating at peak efficiency ensure that the cooling pads are kept clean and dust free Dust and other particles have an adverse effect on the media ...

Страница 8: ... system has a problem you must define the associated problem e g the pump is not running Although this might seem a bit simplified several things may cause this particular problem So while defining the problem a careful check of all systems should be made to fully understand the extent of the problem If you have a complete understanding of all of the systems of the COOL SPACE unit and how they dep...

Страница 9: ...xtension cord Replace motor Upgrade power supply Replace with heavier cord Motor overheating and shutting off Restarting several minutes later Extension cord gauge too small Inlet air obstructed or too close to wall Faulty motor Loose belt Replace with heavier cord Provide minimum 1 metre inlet clearance Replace motor Tighten belt Fan motor won t run and switch makes soft clicking sound Switch mak...

Страница 10: ...sure is too high to allow float valve to shutoff 8 bar max Float valve is not seating properly Tighten connections and or replace hose washers Reduce water pressure by adding an inline reducer Check float valve Replace float orifice Check all hoses for leaks Water spitting from the unit Flow control Cracked Hose Valve Assembly Hose connection loose Reduce flow Replace Hose Valve Assembly Tighten h...

Страница 11: ...e running Object s in impellor impellor loose Pump bearings bad Remove object s Replace pump Breaker trips or fuse blows when switch is turned on Check power cord length and breaker rating Check for locked up pump Refer to page 2 for unit amperage draw and to determine required cord gauge Replace pump Pump won t run and power is available Pump is functional Make certain switch is working Is water ...

Страница 12: ...e new fan assembly 4 Secure with 4 nuts and bolts 5 Replace any wire ties that were removed when taking out the old fan assembly 6 Replace the black motor wiring plate AVALANCHE CS6 36 Series Variable Speed Direct Drive Models 1 Remove cap off rear of motor Disconnect wires Clip wire ties 2 Remove 4 fan mounting bolts from the front Support fan to ensure it doesn t fall 3 Pull the fan out of the u...

Страница 13: ...tly until the belt is tight but not tight enough to overload the motor then tighten the four bracket bolts 9 Replace the motor wires as marked from step 5 Replace wire ties to prevent cord from getting in fan blade 10 Replace motor wiring cover plate and inspect to be certain that the rubber seal is properly seated 11 Replace cooling pads and guards and reconnect power and test motor Pump Replacem...

Страница 14: ...u may fill out the warranty form supplied with your unity and fax it to 001 317 485 0118 or register online at www cool space com 7 2 Warranty parts Warranty replacement parts are available through your local distributor or supplier where you purchased your COOL SPACE unit If you have any questions or concerns please contact us direct at 001 317 577 0337 or at sales cool space com Please have your...

Страница 15: ...ssembly with Motor for GLACIER CS M36V 220 90cm 36 Variable Speed 60HZ for AVALANCHE CS M48 2B 60 220 120cm 48 Two Speed 60 HZ for BLIZZARD Switches CS E110 On Off Pump Single Speed Fan CS E111 Two Speed CS E180 Variable Speed CS6 36 VD 60HZ for AVALANCHE CS E199 VD 220 230 VD Controller for GLACIER Pump CS E173 1 CS5 16 VD CS6 36 VD CS5 48 2B 20cm 8 Pads CS H610 CS5 16 VD 2 required for GLACIER C...

Страница 16: ...nal Sales Office PO Box 6916 Bridgnorth WV16 9ED UK 00 44 7979 243154 www cool space com simon hartles cool space com DISTRIBUTOR Disposal This symbol on the product indicates that the appliance cannot be collection point for electric and electronic appliances ...

Отзывы: