Total Access 3000 23-Inch Chassis Installation and Maintenance Practice
4
61181001L1-5E
• Insulated 10-gauge wire for power connections, in colors dictated by the CO for battery to
the Total Access 3000 Chassis and return
• Insulated 8-gauge wire for frame ground
• Lugs for the 10-gauge power wire and Frame Ground connection
• Data cables terminated at the Total Access 3000 Chassis in 64-pin amphenol connectors,
and (depending on the mechanics of the MDF and DSX cross-connect panels) at the distant
end in either stubs or 64-pin amphenol connectors
• If required, coaxial cable appropriate for DS3 or STS-1 network input to the Total Access
3000 Chassis
WARNING
To prevent electrical shock, do not install equipment in a wet
location or during a lightning storm.
CAUTION
Electronic modules can be damaged by static electrical discharge.
Before handling modules, wear an antistatic discharge wrist strap
to prevent damage to electronic components. Place modules in
antistatic packing material when transporting or storing. When
working on modules, always place them on an approved antistatic
mat that is electrically grounded.
Unpacking and Inspecting the Chassis
Each Total Access 3000 chassis is shipped in its own cardboard shipping carton unless it was
ordered as a fully racked system. Open each carton carefully and avoid puncturing the carton
with sharp objects. After pulling the chassis out of the carton, remove the foam endcaps and
slip the chassis out of the cardboard shipping sleeve and protective plastic bag.
After unpacking the unit, inspect it for damage. If damage is found, file a claim with the
carrier, then contact ADTRAN Customer Service. For more information, refer to
.