OPC8000 series
19
© ADS-TEC GmbH • Heinrich-Hertz-Str. 1 • 72622 Nürtingen
4 Installation
4.1 Installation option
This device is designed for integration. For installation and operation reasons (connector
access), the installation location must be accessible from the rear. The wall thickness of the
installation location must be between 2 and 13 mm. We recommend at least 3 mm for proper
installation with IP65 on the front.
ATTENTION
To avoid overheating in operation: The
device must not be exposed to direct
radiation by sunlight or any other light
source.
If the device is installed in a panel, casing or
similar, it must be ensured that no heat
accumulation occurs. The maximum
permissible ambient temperature must not be
exceeded.
Devices with data drives must only be
installed vertically. Any deviation must be
arranged with ADS-TEC GmbH.
IP 65 on the front is only achieved with
proper installation.
ATTENTION
When selecting the enclosure for integration,
the total power dissipation of the system
including installed PCBs must be taken into
account. The housing must be dimensioned
so that the max. permissible ambient
temperature is not exceeded.
Содержание OPC8008
Страница 21: ...OPC8000 series 21 ADS TEC GmbH Heinrich Hertz Str 1 72622 Nürtingen 4 3 External device dimensions OPC8008 ...
Страница 23: ...OPC8000 series 23 ADS TEC GmbH Heinrich Hertz Str 1 72622 Nürtingen 4 5 Installation layout OPC8013 ...
Страница 25: ...OPC8000 series 25 ADS TEC GmbH Heinrich Hertz Str 1 72622 Nürtingen 4 7 Installation layout OPC8015 ...
Страница 26: ...OPC8000 series 26 ADS TEC GmbH Heinrich Hertz Str 1 72622 Nürtingen 4 8 External device dimensions OPC8022 ...
Страница 27: ...OPC8000 series 27 ADS TEC GmbH Heinrich Hertz Str 1 72622 Nürtingen Fig 7 4 9 Installation layout OPC8022 ...