Electrical Installation/Earthing (Cont.)

RS 485 Modbus – BMS Connection:

 RS 485 is available on this product for BMS connection directly 

into the unit controller.

Fuses:

 A 5 Amp replacement fuse size should be used. The complete unit is fused via the live 

terminal block contained within the upper electrical compartment.

Supply cord replacement:

 The supply cord and internal wiring within the terminal box are routed 

and secured to ensure compliance with the electrical standard EN60335-1. It is essential that prior 
to any disturbance of this internal wiring, all cable routing and securing details are carefully noted 
to ensure re-assembly to the same factory pattern is always maintained. If the supply cord is to be 
changed or is damaged, it must be replaced with a special cord assembly available from ADEY or 
one of their approved repairers. On disassembly note the cord retention and routing system. Re-
assemble to the same pattern.
For information on cable connection consult the wiring diagram below:

Fig. 5

L E

N

230 Volts

Switch

Grundfos

UPM3 Flex AS 

Pump

ADEY DEK1001

Modbus Controller

Grundfos

DP Sensor

12v LED

Fused

Terminal Block

L E

N

230 Volts

Switch

Grundfos

UPM3 Flex AS 

Pump

ADEY DEK1001

Modbus Controller

Grundfos

DP Sensor

12v LED

Fused

Terminal Block

L E

N

230 Volts

Switch

Grundfos

UPM3 Flex AS 

Pump

ADEY DEK1001

Modbus Controller

Grundfos

DP Sensor

12v LED

Fused

Terminal Block

L E

N

230 Volts

Switch

Grundfos

UPM3 Flex AS 

Pump

ADEY DEK1001

Modbus Controller

Grundfos

DP Sensor

12v LED

Fused

Terminal Block

Содержание MagnaClean CMX

Страница 1: ...1 Nano Pumped Sidestream Installation and servicing ...

Страница 2: ... temperature sensing with full BMS alarm connectivity this solution is designed to actively monitor the filter and the filtration of heating and chilled systems in a sidestream configuration for 24 hours a day even when the system pumps aren t running Storage If this product is not to be installed immediately on receipt ensure that it is stored in a dry frost and vibration free location in its ori...

Страница 3: ...ot be made by children without supervision Children should be supervised to ensure that they do not play with the appliance Please read installation details carefully as they are intended to ensure this product provides long trouble free service Failure to install the unit in accordance with the installation instructions will lead to invalidation of the warranty 1 Checklist IMPORTANT With the appl...

Страница 4: ...e locations 2 MagnaClean CMX Nano Filter Grundfos UPM3 Flex AS 130 Pump This pumped sidestream solution has been designed to provide complete flexibility across a plant room environment offering high performance sidestream filtration when space is a premium and or where it isn t possible to install a filter across a pump on any heating or chilled system 3 Grundfos Differential Pressure Temperature...

Страница 5: ...grated pump the inlet outlet connections must both be connected to EITHER the main system flow OR the system return The inlet outlet connections must not be connected across the system flow and system return or across a system pump as would be the case in a standard sidestream installation configuration If the unit is installed incorrectly it may result in the unit not operating as intended The inl...

Страница 6: ...e should be made to the relevant regulations concerning this subject to ensure compliance Connections The unit must be connected to a dedicated fused SPUR via a lockable isolator to avoid unauthorised disconnection The electrical connection must be made adjacent to not behind the Pumped Sidestream unit to allow disconnection of the electrical supply should the pump module or controller need to be ...

Страница 7: ...attern is always maintained If the supply cord is to be changed or is damaged it must be replaced with a special cord assembly available from ADEY or one of their approved repairers On disassembly note the cord retention and routing system Re assemble to the same pattern For information on cable connection consult the wiring diagram below Fig 5 L E N 230 Volts Switch Grundfos UPM3 Flex AS Pump ADE...

Страница 8: ... alarm alerting the persons responsible for monitoring the heating or chilled system that the installed cartridge filter is full and needs changing The pump is deactivated and the controller will not clear until a new service date is entered System temperature can also be monitored by the DPS sensor providing warning alarms should the water temperature fall below or above the programmable low high...

Страница 9: ...on Default Range Service Date Adjust future service date Day Month Year Press hold SET to cycle across values Will pass onto next parameter once complete Last Service Date Automatically updates when a new service date has been entered and will be visible next time user accesses parameters 1 Cartridge Present Monitors presence of a filter cartridge No Yes No 2 Magnet Only Service Warning Daily week...

Страница 10: ... 0 0 99 16 Battery Activation Enable or disable the Battery Maintains date and time settings if power is lost to the controller on first power up battery will automatically activate No Yes No NOTE PARAMETER 1 If Parameter 1 Cartridge Present is set to YES Parameters 2 3 are not activated If Parameter 1 Cartridge Present is set to NO Parameters 2 3 are activated and the timer will be active from th...

Страница 11: ...ead write word 16 bits Value X C Par 10 120 Par 10 120 See note 4 40011 Parameter Pump Required read write word 16 bits 4 No 5 Yes 4 5 4 5 40012 Parameter Current Sense Active read write word 16 bits 4 No 5 Yes 4 5 4 5 40013 Parameter Alarm Relay Contact Type read write word 16 bits 0 Normal Open 1 Normal Close 0 1 0 1 40014 Parameter Pump Hours read write word 16 bits Value X h 0 9999 0 9999 4001...

Страница 12: ... Differential Pressure read word 16 bits 0 Normal Open 1 Normal Close 0 1 0 1 40036 Alarm Irregular Flow read word 16 bits 0 Not Active 1 Active 0 1 0 1 40037 Alarm Maximum Pump Activity read word 16 bits 0 Normal Open 1 Normal Close 0 1 0 1 40038 Alarm Low Temperature read word 16 bits 0 Not Active 1 Active 0 1 0 1 40039 Alarm High Temperature read word 16 bits 0 Normal Open 1 Normal Close 0 1 0 ...

Страница 13: ...zzer ON LED Light ON Common Alarm OFF Pressure Differential Alarm Pressure Differential Alarm value has been reached Control will not clear error until new service date entered Filter Service Required N Pump OFF Buzzer ON LED Light ON Common Alarm ON Low Temperature Alarm Low temperature alarm value reached Low Temperature Warning Y Pump ON Buzzer ON LED Light ON Common Alarm ON High Temperature A...

Страница 14: ...across the filter as there is no distinguishable pressure drop across the filter without a cartridge installed even when it is full of captured magnetic debris These time based alarms are important as ADEY always recommend that when a MagnaClean CMX filter is installed onto an existing heating or chilled system the filter should initially be configured with magnets only This is to ensure that cart...

Страница 15: ...ession nut 2 Close both isolation valves at the base of the unit to isolate the filter from the main system 5 Unscrew compression nut remove cartridge filter if installed and put safely to one side 8 Offer up the filter body to the lid assembly ensuring that the O ring is positioned and re installed correctly 3 Connect hose to the drain port and slowly open the valve to release any residual pressu...

Страница 16: ...e unit Maintaining the product UPM3 pumps are maintenance free However it might be necessary to deblock or to open the pump for example if it is blocked by impurities De blocking is possible by opening the de blocking screw at the front 1 Unscrew the de blocking screw at the front of the pump head CAUTION Pressurised system Minor or moderate personal injury Be aware of splashing hot water 2 De blo...

Страница 17: ... 100 C Connections Inlet outlet 28mm compression Pump Pump model Grundfos UPM3 FLEX AS 25 70 130 Pump type Circulation PWM A Pump head material Electrocoated Cast Iron Impeller material Composite PES 30 GF Minimum inlet pressure 0 5 bar System Monitoring Differential Pressure Temperature monitoring Grundfos DP Sensor Housing Composite PPS Sensing element Silicon based MEMS Sensor Response time 0 5...

Страница 18: ...nput new service interval date Pump is blocked with impurities Unblock the pump and remove impurities Pump is defective Replace pump contact ADEY Customer Services PUMP RUNS AT MAX SPEED CANNOT BE CONTROLLED No signal from signal cable Check cable is connected to pump controller If connected correctly replace the cable contact ADEY Customer Services NOISE IN THE PUMP There is air in the pump Let t...

Страница 19: ...ty is defined by the sequence of the table Operating Panel LED1 LED2 LED3 LED4 LED5 Indication Pump Operation Remedy Rotor is blocked Trying to start again every 1 33 seconds Wait or unblock the rotor shaft Supply voltage too low Warning only Pump runs Control the supply voltage Electrical error Pump stopped due to low supply voltage or serious failure Control the supply voltage Replace the pump c...

Страница 20: ...nd carries the UKCA mark accordingly The product also complies with the requirements of the WEEE Directive 2013 and carries the WEEE symbol accordingly Conformity to the essential requirements of the legislation s have been demonstrated by using the following standards EMC EN 55014 1 EN 55014 2 EN 61000 3 2 EN 61000 3 3 Safety EN ISO 12100 EN 60335 1 EN 60335 2 51 EN 62233 EN 60529 1 Technical doc...

Страница 21: ...21 ...

Страница 22: ...22 ...

Страница 23: ...23 ...

Страница 24: ... Modwen Park Stonehouse GL10 3EZ EU ADEY Innovation SAS 119 Bis Rue de Colombes 92600 Asnières sue Seine France Produced from recycled material A carbon neutral company All ADEY marks are trademarks of Adey Holdings 2008 Limited Please visit adey com trademarks for a list of ADEY marks Copyright Adey Holdings 2008 Limited 2021 All rights reserved ...

Отзывы: