9. Maintenance – Grundfos UPM3 Flex 130 AS Pump

The following steps should be followed if 
servicing the Grundfos UPM3 Flex 130 AS pump:

DANGER
Electric shock

Death or serious personal injury

•  Before starting any work at the pump, 

switch off the power supply. Make 
sure that the power supply cannot be 
switched on accidentally.

•  Be aware that capacitors will be live 

up to 30 seconds after the power 
supply has been switched off.

DANGER
Electric shock

Death or serious personal injury

•  Before dismantling the complete 

pump set, switch off the power 
supply at least 5 minutes prior to 
commencing work and ensure that 
it cannot be switched on again 
unintentionally.

WARNING
Strong magnetic fi eld in the rotor area

Danger of death for persons with 
pacemaker.

•  Keep a safety distance of at least 

0.3m during disassembly.

CAUTION
Hot surface

Minor or moderate personal injury.

•  Before starting to work on the pump, 

let the pump casing cool down to 
ambient temperature.

All service work must be carried out by 
an instructed service technician.
Before dismantling the pump, drain the 
system and close the isolating valves on 
the unit.

Maintaining the product

UPM3 pumps are maintenance-free. However, 
it might be necessary to deblock or to open the 
pump, for example, if it is blocked by impurities.
De-blocking is possible by opening the de-
blocking screw at the front.
1.  Unscrew the de-blocking screw at the front 

of the pump head.

CAUTION
Pressurised system

Minor or moderate personal injury

•  Be aware of splashing hot water

2. De-block the pump with a screwdriver.

Cleaning

If the impeller or pump housing has to be 
cleaned from impurities, proceed as follows:
1.  Drain the sidestream unit and close the 

isolating valves.

CAUTION
Pressurised system

Minor or moderate personal injury

•  Be aware of splashing hot water

2. Remove the screws that hold the pump head.
3. Check impeller and pump housing and 

remove the impurities.

4. Place the pump head in the desired position, 

fi t the screws and tighten them securely.

Spares:

 The 

MagnaClean CMX Nano

Pumped Sidestream is designed and built 
to be a reliable and high quality product 
but in the event of spares being required, 
please contact ADEY Customer Services 
on +44 (0) 1242 546 717.

10. Environment Protection

This product assembly contains valuable materials which can be recovered or recycled. At the end 
of the product’s useful life, please leave it at an appropriate local civic waste collection point.

Содержание MagnaClean CMX

Страница 1: ...1 Nano Pumped Sidestream Installation and servicing ...

Страница 2: ... temperature sensing with full BMS alarm connectivity this solution is designed to actively monitor the filter and the filtration of heating and chilled systems in a sidestream configuration for 24 hours a day even when the system pumps aren t running Storage If this product is not to be installed immediately on receipt ensure that it is stored in a dry frost and vibration free location in its ori...

Страница 3: ...ot be made by children without supervision Children should be supervised to ensure that they do not play with the appliance Please read installation details carefully as they are intended to ensure this product provides long trouble free service Failure to install the unit in accordance with the installation instructions will lead to invalidation of the warranty 1 Checklist IMPORTANT With the appl...

Страница 4: ...e locations 2 MagnaClean CMX Nano Filter Grundfos UPM3 Flex AS 130 Pump This pumped sidestream solution has been designed to provide complete flexibility across a plant room environment offering high performance sidestream filtration when space is a premium and or where it isn t possible to install a filter across a pump on any heating or chilled system 3 Grundfos Differential Pressure Temperature...

Страница 5: ...grated pump the inlet outlet connections must both be connected to EITHER the main system flow OR the system return The inlet outlet connections must not be connected across the system flow and system return or across a system pump as would be the case in a standard sidestream installation configuration If the unit is installed incorrectly it may result in the unit not operating as intended The inl...

Страница 6: ...e should be made to the relevant regulations concerning this subject to ensure compliance Connections The unit must be connected to a dedicated fused SPUR via a lockable isolator to avoid unauthorised disconnection The electrical connection must be made adjacent to not behind the Pumped Sidestream unit to allow disconnection of the electrical supply should the pump module or controller need to be ...

Страница 7: ...attern is always maintained If the supply cord is to be changed or is damaged it must be replaced with a special cord assembly available from ADEY or one of their approved repairers On disassembly note the cord retention and routing system Re assemble to the same pattern For information on cable connection consult the wiring diagram below Fig 5 L E N 230 Volts Switch Grundfos UPM3 Flex AS Pump ADE...

Страница 8: ... alarm alerting the persons responsible for monitoring the heating or chilled system that the installed cartridge filter is full and needs changing The pump is deactivated and the controller will not clear until a new service date is entered System temperature can also be monitored by the DPS sensor providing warning alarms should the water temperature fall below or above the programmable low high...

Страница 9: ...on Default Range Service Date Adjust future service date Day Month Year Press hold SET to cycle across values Will pass onto next parameter once complete Last Service Date Automatically updates when a new service date has been entered and will be visible next time user accesses parameters 1 Cartridge Present Monitors presence of a filter cartridge No Yes No 2 Magnet Only Service Warning Daily week...

Страница 10: ... 0 0 99 16 Battery Activation Enable or disable the Battery Maintains date and time settings if power is lost to the controller on first power up battery will automatically activate No Yes No NOTE PARAMETER 1 If Parameter 1 Cartridge Present is set to YES Parameters 2 3 are not activated If Parameter 1 Cartridge Present is set to NO Parameters 2 3 are activated and the timer will be active from th...

Страница 11: ...ead write word 16 bits Value X C Par 10 120 Par 10 120 See note 4 40011 Parameter Pump Required read write word 16 bits 4 No 5 Yes 4 5 4 5 40012 Parameter Current Sense Active read write word 16 bits 4 No 5 Yes 4 5 4 5 40013 Parameter Alarm Relay Contact Type read write word 16 bits 0 Normal Open 1 Normal Close 0 1 0 1 40014 Parameter Pump Hours read write word 16 bits Value X h 0 9999 0 9999 4001...

Страница 12: ... Differential Pressure read word 16 bits 0 Normal Open 1 Normal Close 0 1 0 1 40036 Alarm Irregular Flow read word 16 bits 0 Not Active 1 Active 0 1 0 1 40037 Alarm Maximum Pump Activity read word 16 bits 0 Normal Open 1 Normal Close 0 1 0 1 40038 Alarm Low Temperature read word 16 bits 0 Not Active 1 Active 0 1 0 1 40039 Alarm High Temperature read word 16 bits 0 Normal Open 1 Normal Close 0 1 0 ...

Страница 13: ...zzer ON LED Light ON Common Alarm OFF Pressure Differential Alarm Pressure Differential Alarm value has been reached Control will not clear error until new service date entered Filter Service Required N Pump OFF Buzzer ON LED Light ON Common Alarm ON Low Temperature Alarm Low temperature alarm value reached Low Temperature Warning Y Pump ON Buzzer ON LED Light ON Common Alarm ON High Temperature A...

Страница 14: ...across the filter as there is no distinguishable pressure drop across the filter without a cartridge installed even when it is full of captured magnetic debris These time based alarms are important as ADEY always recommend that when a MagnaClean CMX filter is installed onto an existing heating or chilled system the filter should initially be configured with magnets only This is to ensure that cart...

Страница 15: ...ession nut 2 Close both isolation valves at the base of the unit to isolate the filter from the main system 5 Unscrew compression nut remove cartridge filter if installed and put safely to one side 8 Offer up the filter body to the lid assembly ensuring that the O ring is positioned and re installed correctly 3 Connect hose to the drain port and slowly open the valve to release any residual pressu...

Страница 16: ...e unit Maintaining the product UPM3 pumps are maintenance free However it might be necessary to deblock or to open the pump for example if it is blocked by impurities De blocking is possible by opening the de blocking screw at the front 1 Unscrew the de blocking screw at the front of the pump head CAUTION Pressurised system Minor or moderate personal injury Be aware of splashing hot water 2 De blo...

Страница 17: ... 100 C Connections Inlet outlet 28mm compression Pump Pump model Grundfos UPM3 FLEX AS 25 70 130 Pump type Circulation PWM A Pump head material Electrocoated Cast Iron Impeller material Composite PES 30 GF Minimum inlet pressure 0 5 bar System Monitoring Differential Pressure Temperature monitoring Grundfos DP Sensor Housing Composite PPS Sensing element Silicon based MEMS Sensor Response time 0 5...

Страница 18: ...nput new service interval date Pump is blocked with impurities Unblock the pump and remove impurities Pump is defective Replace pump contact ADEY Customer Services PUMP RUNS AT MAX SPEED CANNOT BE CONTROLLED No signal from signal cable Check cable is connected to pump controller If connected correctly replace the cable contact ADEY Customer Services NOISE IN THE PUMP There is air in the pump Let t...

Страница 19: ...ty is defined by the sequence of the table Operating Panel LED1 LED2 LED3 LED4 LED5 Indication Pump Operation Remedy Rotor is blocked Trying to start again every 1 33 seconds Wait or unblock the rotor shaft Supply voltage too low Warning only Pump runs Control the supply voltage Electrical error Pump stopped due to low supply voltage or serious failure Control the supply voltage Replace the pump c...

Страница 20: ...nd carries the UKCA mark accordingly The product also complies with the requirements of the WEEE Directive 2013 and carries the WEEE symbol accordingly Conformity to the essential requirements of the legislation s have been demonstrated by using the following standards EMC EN 55014 1 EN 55014 2 EN 61000 3 2 EN 61000 3 3 Safety EN ISO 12100 EN 60335 1 EN 60335 2 51 EN 62233 EN 60529 1 Technical doc...

Страница 21: ...21 ...

Страница 22: ...22 ...

Страница 23: ...23 ...

Страница 24: ... Modwen Park Stonehouse GL10 3EZ EU ADEY Innovation SAS 119 Bis Rue de Colombes 92600 Asnières sue Seine France Produced from recycled material A carbon neutral company All ADEY marks are trademarks of Adey Holdings 2008 Limited Please visit adey com trademarks for a list of ADEY marks Copyright Adey Holdings 2008 Limited 2021 All rights reserved ...

Отзывы: