![Adey MagnaClean CMX Скачать руководство пользователя страница 12](http://html1.mh-extra.com/html/adey/magnaclean-cmx/magnaclean-cmx_installation-and-servicing_2850948012.webp)
12
X Variable
Address
Denomination
Type
X Variable
Format
Data Conversion
Units
Equivalent
Range
Range of
X Variable
Notes
40029
Last Serviced Date
Month
read
word 16 bits
Value = X
1-12
1-12
40030
Last Serviced Date Year
read
word 16 bits
Value = X
0-99
0-99
40031
Pump Status
read
word 16 bits
0 = OFF 1 = ON
0-1
0-1
40032
Common Alarm Status
read
word 16 bits
0 = OFF 1 = ON
0-1
0-1
40033
Led Alarm Status
read
word 16 bits
0 = OFF 1 = ON
0-1
0-1
40034
Alarm Pump Failure
read
word 16 bits
0 = Not Active
1 = Active
0-1
0-1
40035
Alarm Excessive
Differential Pressure
read
word 16 bits
0 = Normal Open;
1 = Normal Close
0-1
0-1
40036
Alarm Irregular Flow
read
word 16 bits
0 = Not Active
1 = Active
0-1
0-1
40037
Alarm Maximum Pump
Activity
read
word 16 bits
0 = Normal Open;
1 = Normal Close
0-1
0-1
40038
Alarm Low Temperature
read
word 16 bits
0 = Not Active
1 = Active
0-1
0-1
40039
Alarm High Temperature
read
word 16 bits
0 = Normal Open;
1 = Normal Close
0-1
0-1
40040
Warning Differential
Pressure
read
word 16 bits
0 = Not Active
1 = Active
0-1
0-1
40041
Magnet Only Service
Warning
read
word 16 bits
0 = Not Active
1 = Active
0-1
0-1
40042
Pressure
read
word 16 bits
Value = X/10
Par.3-Par.4
Par.3-Par.4
40043
Temperature
read
word 16 bits
Value = X
0-120
0-120
40044
Flow
read
word 16 bits
Not used
Содержание MagnaClean CMX
Страница 1: ...1 Nano Pumped Sidestream Installation and servicing ...
Страница 21: ...21 ...
Страница 22: ...22 ...
Страница 23: ...23 ...