FR
W-MBus Modems/Receiver/Repeater- Guide utilisateur / User guide version V1.8.2
39
Page
of of 50
EN
CONFIGURATION TABLE :
Type
SW1
SW2
SW3
SW4
Configuration
Gas
Off
Off
Off
Off
Pulse weight 100 dm3 /Periodicity sending frame index = 10s
Off
Off
Off
On
Pulse weight 100 dm3 /Periodicity sending frame index = 12h
Off
Off
On
Off
Pulse weight 100 dm3 /Periodicity sending frame index = 10s
Off
Off
On
On
Pulse weight 100 dm3 /Periodicity sending frame index = 10min
Off
On
Off
Off
Pulse weight 100 dm3 /Periodicity sending frame index = 12h
Off
On
Off
On
Pulse weight 10 dm3 /Periodicity sending frame index = 10s
Off
On
On
Off
Pulse weight 10 dm3 /Periodicity sending frame index = 10min
Off
On
On
On
Pulse weight 10 dm3 /Periodicity sending frame index = 12h
Water
On
Off
Off
Off
Pulse weight 100 L /Periodicity sending frame index = 10s
On
Off
Off
On
Pulse weight 100 L /Periodicity sending frame index = 12h
On
Off
On
Off
Pulse weight 10 L /Periodicity sending frame index = 10s
On
Off
On
On
Pulse weight 10 L /Periodicity sending frame index = 10min
On
On
Off
Off
Pulse weight 10 L /Periodicity sending frame index = 12h
On
On
Off
On
Pulse weight 1 L /Periodicity sending frame index = 10s
On
On
On
Off
Pulse weight 1 L /Periodicity sending frame index = 10min
On
On
On
On
Pulse weight 1 L /Periodicity sending frame index = 12h
Electricity
On
Off
On
Off
Periodicity sending frame index = 10s
On
Off
On
On
Periodicity sending frame index = 10 min
On
On
Off
Off
Periodicity sending frame index = 12h
7.3.2 Wiring of the product
Slide the sensor(s) or cable (s) through the gland. Warning, there are different housing versions for 1 or 2 sensors.
For connection procedure, connect all wires and finish by the green wire (mandatory).
4 configuration switches
Green LED : startup and opera-
tion status
Meter #1 pulse : white
GND meter#1 : brown
Fraud meter#1 : green
«sens/HF» meter#1 : yellow*
Direction meter#1 : grey*
Meter #2 pulse : white
GND meter#2 : brown
Fraud meter#2 : green
«sens/HF» meter#2 : yellow*
Direction meter#2 : grey*
* : depending on configuration
Switch 1 ON = water
OFF = gas