19
Ö
/# 16 Strobe to Confirm Away Set
0 = NO
1 = YES
Ö
/# 28 Programme Tamper or
0 = Program Tamper
Alarm Abort Trigger
1 = Alarm Abort Trigger
Ö
/# 47 Tamper or Set Latch Trigger
0 = Tamper trigger output
1 = Set Latch trigger output
Ö
/# 50 Fire or Open/Close Trigger
0 = Fire
1 = Open/ Close (Set)
Ö
/# 86 Fault or Verified Alarm
0 = Fault Trigger
Trigger
01-99 = Verified Alarm
Engineer
Ö
/# 00 Engineer Code
Ö
/# 06 Technistore Version
Enter version number used by
Number
central station (000 - 255)
Ö
/# 15 Event Log Printout on
0 = NO
Exiting Programming
1= YES
Ö
/# 23 Tamper : Reset Type
0 = Customer
1 = Engineer Reset required
0 = Customer
Ö
/# 24 Alarm : Reset Type
1 = Engineer
2 = Technistore Reset
Zone Programming Options
Ö
/# 02 Zone 1-8 Response
Ö
/# 05 Zone 99 (
Ö
+ #) Panic
Assign zone type e.g. 06 or 07
Ö
/# 39 Zone 1-8 Forced Walk Test
(0)
(0)
( 4 1 1 0 )
(0 0)
(0 1)
(0 3) (0 3) (0 3)
(0 3)
(0 4)
(0 3)
(0 3)
(0)
(0)
(0)
(0)
(0)
(0)
(0)
(0)
(0)
Zone Responses
00 Not Used
01 Final Exit
02 Soak Test
03 Intruder
04 Walk Through
05 24 Hour Tamper
06 PA Silent
07 PA Audible
09 Fire
10 Intruder Isolated in Stay
12 Partition Intruder
13 Partition Entry / Exit
14 Partition Walkthrough
15 Walkthrough isolated in Stay
16 Final Exit isolated in Stay
17 Telephone Line Monitor
19 Comms Hold-Off Zone
20 Double Knock Intruder
(0)
(0)
If set toVerfied Alarm, enter time
window in minutes (01-99).
( 0 0 0)
(0)
(0)
(0)
Once enabled (set to 1),walk test of zone is required during unset period before setting.
www.PDF-Zoo.com
firealarmresources.com
Содержание VISTA 10
Страница 2: ...2 www PDF Zoo com firealarmresources com...
Страница 15: ...15 Figure 2 2 Telephone Line Connections www PDF Zoo com firealarmresources com...
Страница 16: ...16 www PDF Zoo com firealarmresources com...
Страница 26: ...26 www PDF Zoo com firealarmresources com...
Страница 27: ...27 www PDF Zoo com firealarmresources com...
Страница 28: ...28 IE1 4110 ISSUE A 30 7 99 www PDF Zoo com firealarmresources com...