background image

 

 

   

     

    

 Pa

ge

 3

 -

 Ch

ap

te

r:

 

C

on

ne

ct

io

5.3.3  Parallel connection “Double Power” 

Power supply can be paralleled to increase the output 
power, devices can be paralleled for 1+1=2 to obtain 
the  double  power  of  a  single  unit.  The  possibility  to 
put in parallel connection it is only in SIZE 3 devices 
in  the  specific  “P”  version  (i.e.CBI1235AP, 
CBI2420AP,  CBI4810AP),  to  attain  the  sum  of  the 
current at the same output voltage. It is necessary to 
use  a  standard  UTP  or  order  Cable  code: 
ERJ.CBI.004 for RJ45, and connect by Aux2 of each 
device.  The  communication  protocol  is  based  on 
CAN2.0A standard.  

In this way the system has only One output for the Load and One output for the battery. 
a) Use separate input fuses for each CBI.  
b)  Make  sure  that  the  two  CBI  have  the  same  settings:  Battery  type,  Charging  level  current,  Time 
buffering, Life test... 
c)  Automatic  configuration,  Master-Slave.  The  devices  decide  themselves  their  Master  and  Slave 
assignment  randomly.  The  assignment  is  done  at  every  power  on,  or  after  the  connection  of  the cable 
RJ45. Master device provide all the visual signals, the Slave device maintain the diagnosis LED always 
ON. 
d) Use the alarm contacts of both the two devices and deliver them at will. 
e) For Start Battery there are two way, without mains voltage: 
- push start button on both units 
- connect Cable "RTCONN" on position 5, to connect pushbutton on a front panel. 

5.3.4  Series connection: 

It is possible to connect as many units in series as 
needed,  provided  the  sum  of  the  output  voltage 
does  not  exceed  150Vdc.  b)  Voltages  with  a 
potential above 60Vdc are not SELV anymore and 
can be dangerous. Such voltages must be installed 
with  a  protection  against  touching.  c)  For  serial 
operation use power supplies of the same type. d) 
Earthing of the output is required when the sum of 
the  output  voltage  is  above  60Vdc.  e)  Keep  an 
installation clearance of 10 mm (left/right) between 
two  power  supplies  and  avoid  installing  the  power 
supplies  on  top  of  each  other.  Note:  Avoid  return 

voltage (e.g. from a decelerating motor or battery) which is applied to the output terminals. 

5.4  OUTPUT LOAD (MAINS INPUT ON) 

The output Load in normal mode, Mains Input Vac Voltage present, follow the charging battery dc output 
voltage. The minimum and maximum range stabilized are the following: 
CBI 12xx:11 – 14,4 Vdc; 15,5 Vdc for NiCd (Without battery connected out. Voltage fixed at 12Vdc) 
CBI 24xx:22 – 28.8 Vdc; 30 Vdc for NiCd (Without battery connected out. Voltage fixed at 24Vdc) 
CBI 48xx:44 – 57.6 Vdc; 62 Vdc for NiCd (Without battery connected out. Voltage fixed at 48Vdc) 
Thanks  to  the  All  In  One  units,  it  will  be  possible  to  manage  the  power.  The  available  power,  is 
automatically  allocated  between  load  and  battery:  supplying  power  to the  load  is  the first  priority  of  the 
unit; thus it is not necessary to double the power and also the power available for the battery will go to the 
load if the load requires it. 
In “Power Boost Mode” the maximum current on the load output is the 2 times the rated current 2 x In 
(Iload = In+ Ibatt) in continuous operation and 3 times the rated current 3 x In (Iload = 2In+ Ibatt) for 4 
seconds; after this parameter the devices is electrically protected against overload and short circuit. 

  In “Power Boost Mode”, if the the battery provide current to the load for a time more than 4 minutes, 

the  device  give  message  (8  Blink),  this  consequently  means  that  the  battery  is  discharging.  If  the 
Mains  Input  Voltage  fall  below  a  Threshold  level  (50%  of  the  Typ.  Vac  input)  the  battery  is 
immediately connected to the Output Load, without any interruption. 

  Voltage dips: In this situation the voltage in the output load it is the same of the battery.  

 

To Avoid deep battery discharge

, the battery will supply the load until battery voltage reaches 1.5 

V/cell. Below this level the device automatically switches off to prevent Deep discharge and battery 
damage. 

Содержание ALL IN ONE CBI Series

Страница 1: ...y efficiency reduces risk of battery damage and allows a safe operation in permanent connection Predefined curves can be selected by jumpers or DIP switch to optimize the charge of different battery t...

Страница 2: ...or Load DC Bus one Input Output for connection to the battery N 1 battery 12 Vdc for CBI 12xx N 2 battery 12 Vdc connected in Series for CBI 24xx N 4 battery 12 Vdc connected in Series for CBI 48xx 5...

Страница 3: ...installation clearance of 10 mm left right between two power supplies and avoid installing the power supplies on top of each other Note Avoid return voltage e g from a decelerating motor or battery w...

Страница 4: ...45 min 20 h Load 12 A No 3 min 12 min 30 min 600 min Load 15 A No No 9 min 20 min 400 min Load 20 A No No 7 min 13 min 240 min 6 LAY OUT AND CONNECTIONS 7 INPUT AND OUTPUT LOAD AND BATTERY CONNECTION...

Страница 5: ...wer 2 See Diagnosis Led 8 1 4 Relay Contact Rating Max DC1 30 Vdc 1 A AC1 60 Vac 1A Resistive load EN 60947 4 1 Min 1mA at 5 Vdc Min permissive load 8 1 5 Charging Mode STATUS Status Led Diagnosis No...

Страница 6: ...Acid Gel Ni Cd option They guarantee battery reliability in time by continuously testing the internal impedance status avoids any possible risk of damages and grants a permanent reliable and safe conn...

Страница 7: ...er Position Size 1 Jumper Position Size 2 Jumper Position Size 3 Dip Switch Position Size 4 Float charge Volt Cell Fast charge Volt Cell Open Lead 2 23 2 40 AGM Low 2 25 2 40 Gel Battery 2 30 2 40 NiC...

Страница 8: ...he quality resistance on the battery connection is checked every 60 sec This to detect if the cable connection has been properly made Battery in Open Circuit or Sulphated In Float charging mode the Al...

Страница 9: ...STICS The unit is a SLAVE in a MODBUS network The slave units are compliant to the following specifications Transmission mode MODBUS RTU Electrical Interface RS485 half duplex serial line Baud rate 48...

Страница 10: ...onnection Diagram Size3 CBI500 DPYCONN500 is a special cable for the connection of CBI Size3 and the other device max leght 0 5m RJ45COUPLER is e T connection RJ45 for daisy Chain with CBI Size3 RJCON...

Страница 11: ...ections to the external device like RTU PC DPY351 For the connection to RTU PLC or similar devices refer to the instruction manuals Modbus specifications_R14 Web Site www adelsystem com For configurat...

Страница 12: ...ity to EN60950 UL60950 1 and CSA C22 2 No 60950 1 07 Information Technology Equipment Safety Part1 General Requirement Device is intended to be installed in a cabinet protected from external shocks or...

Отзывы: