7.2 SELECT OUTPUT VOLTAGE (ONLY SIZE4 CBI280)
No.17: Caution: Switch off the system before Setting the Jumper. The Jumper is Read at the device
power-up only.
Output Voltage Selection
Jumper
24 Output Voltage
Output Voltage Selection
No Jumper
12 Output Voltage
8 DRIVE AND MONITORING
8.1 FAULT - STATUS CONDITIONS (ISOLATED RELAY):
8.1.1 STATUS: Mains or Backup: Input Mains On/Off.
•
No.5 Relay Contact: 5, 6, 7
•
No.6: Led
8.1.2 FAULT: Low Battery, Battery Replacement, Faulty Battery or Faulty System
•
No.4 Relay Contact: 8,9,10
•
No.8: Led DIAGNOSIS: Battery charger mode, or, Diagnosis of the system through “blinking code”
Light signal
8.1.3 Back Up and Fault: Relay and LED Conditions
Port N°5 - Led N°6 Mains/Back-Up
Port N°4 - Led N°7 Fault Battery
Relay:
5-6 Closed
5-7 Closed
8-9 Closed OK
8-10 Closed
Mains Input
Vac
ON
■ - led off
■ - led off
OFF
■ - led On (1)
■ - led off
Battery SOC
less than 30%
YES
■ - led On
■ - led On (2)
NO
■ - led On
■ - led off
Battery or
system Fault?
YES
■ - led off
■ - led On
NO
■ - led off
■ - led off
Note:
(1) Contact relay Mains/Back switch at least 5 seconds after disconnection of Power.
(2) See Diagnosis Led
8.1.4 Relay Contact Rating:
Max.DC1: 30 Vdc 1 A; AC1: 60 Vac 1A: Resistive load (EN 60947-4-1).Min.1mA at 5 Vdc: Min.
permissive load
8.1.5 Charging Mode STATUS
Status (Led)
Diagnosis (No.8)
Fault
Battery
(No.7)
Charging
Type
Float
1 Blink/2 sec
OFF
Absorption
1 Blink/sec
OFF
Boost
2 Blink/sec
OFF
Recovery
5 Blink/sec
OFF
8.1.6 Faulty Battery / Faulty System
S
yst
em
A
ut
o
D
ia
gn
osi
s
Reverse polarity or high battery Voltage
(over 32.5Vdc for CBI 24xxA)
1 Blink/pause
ON
Battery No connected
2 Blink/pause
ON
Element in Short Circuit
3 Blink/pause
ON
Over Load or short circuit on the load
4 Blink/pause
ON
Bad battery; Internal impedance Bad or Bad battery wire
connection
5 Blink/pause
ON
Life test not possible
6 Blink/pause
ON
Boost condition; battery discharge after 4 min. of overload.
8 Blink/pause
ON
Internal fault
9 Blink/pause
ON
Low battery (under 18.5Vdc for CBI 24xxA) Only if started from
battery, no Mains input, from Jumper N°5 or Push Bottom
10 Blink/pause
ON
Master-Slave connection lost between the master and slave on
parallel configuration, (AP device only)
11 Blink/pause
ON
Bad battery wire connection; Parallel mode on Slave Device
13 Blink/pause
ON
Boost condition; battery discharge after 4 min. of overload;
Parallel mode on Slave Device
15 Blink/pause
ON