8.2  START FROM BATTERY ONLY, NO INPUT MAINS VAC 

No. 9: Push-button, for 3 sec., in the front panel for switch ON the system without the “Mains input 
Vac” but only the battery connected. (Not present in CBI 2410XX and CBI 485XX) 
No.12:  (Jumper  n.5)  It  is  also  available  the  same function  for  remote  start from the  battery,  via 
RTCONN  cable  connected  in  the  Push-button  mounted  on  front  Panel  of  the  external  system. 

Standard  function  for  all  products,  Size  2  only  with  code  CBI2410A/S  and  CBI485A/S.  Do  not  leave 
jumper in this position, otherwise the system will discharge completely the battery. Only push button. 

8.3   BUFFERING TIME SETTING (SIZE 3-4) 

No.15: On Size 3 and Size 4 models, is possible to set a buffering time. It can be selected by setting the 
desired  value  on  the  rotary  switch  15. Buffering time is  initiated  when  the  mains  is  switched  OFF. The 
LOAD output will be ON for the selected time. 

Switch position 

Buffering Time (min.) 

 

0.5 

10 

15 

20 

30 

45 

60 

If the switch is in position 0, the LOAD output will be in ON state until the battery is completed discharged. 
Any  way  to  prevent  damage  risks,  the  unit  disconnects  the  batteries  when  a  minimum  voltage  level  is 
reached. 
The LOAD output will be in ON state until the battery it is completed discharged. It is however possible to 
request  factory customized versions  with  specific  buffering  time  setting, for  units Size  1  or  2,  you  have 
two choose the extension CBIxxxxASDx. 

9  BATTERY CARE 

The Battery Care philosophy is based on algorithms that implement rapid and automatic charging, battery 
charge  optimization  during  time,  flat  batteries  recovery  and  real  time  diagnostic  during  installation  and 
operation. Elements in short circuit, accidental reverse polarity connection, disconnection of the battery, 
can easily be detected and removed by help of Blink Code of Diagnosis Led; during the installation and 
after sell. Each device is suited for all battery types, it is possible setting predefined curves for Open Lead 
Acid,  Sealed  Lead  Acid,  Gel,  Ni-Cd  (option).  They  guarantee  battery  reliability  in  time  by  continuously 
testing  the  internal  impedance  status,  avoids  any  possible  risk  of  damages  and  grants  a  permanent, 
reliable and safe connection of the battery to the power supply. The system, through a battery stimulation 
circuit with algorithms of evaluation of the detected parameter, is able to recognize sulphated batteries or 
batteries with a short-circuited element. Battery Test: Automatic. Every 60 sec. check battery connection. 
Every 220 minute in Float charge, make the test of the battery efficiency is done. The Battery Fault will be 
monitored by relay and led blinking. 

9.1  BATTERY CHARGE IN TEMPERATURE COMPENSATED ENVIRONMENT 

No. 11 Remove the window label to find the connector: Auxiliary Output “AUX 1” 
It  is  possible  to  connect  the  Temperature  sensor  probe  and  apply  it  on  the  battery.The  function  of  the 
probe is for temperature battery compensation. With this it is possible to active the specifications of the 
EN54- fire certification. 

Size 1,2,3 

Size 4 

 

 

9.1.1  Battery Temperature Compensation Charge (not for NiCd) 

Connecting  to  Auxiliary  Output  AUX1  the  cable  RJTEMP  (supplied  separately),  the  CBI  will  vary  the 
voltage of battery charging depending on the temperature: 

Fast Charge 

Float charge 

 +/-5mV/°C x n. of Cells from -8°C to +60°C 
+140mV/Cell ÷ -200mV/Cell compared to the value at 
20°C 

+/-3mV/°C x n. of Cells from -20°C to +60°C 
+120mV/Cell ÷ -120mV/Cell compared to the value at 
20°C 

The device stops to charge the battery If the temperature is less than -20°C or greater than +60°C. The 
sensor placed on cable RJTEMP must be applied on the battery. 

9.2  CHARGING CURRENT LIMITER: 

No.3 In order to protect the battery from excessive charging currents, the device allows 
you to limit the maximum charge current by adjusting the trimmer. It allows you to limit 
from max In up to 20% of current In. To determine the maximum battery charge current, 
see the battery manufacturer's Data Sheet, If it is not possible, consider that on average 
the maximum charge current is 10% of Ah's rated battery current; The data is suitable 

for both Lead Acid and NiCd batteries. 

9.3  BATTERY MANAGEMENT CONFIGURATIONS (SIZES 1,2,3,4) 

No.18  Preliminary Operations: One device for all battery types. 

Содержание ALL IN ONE CBI Series

Страница 1: ...y efficiency reduces risk of battery damage and allows a safe operation in permanent connection Predefined curves can be selected by jumpers or DIP switch to optimize the charge of different battery t...

Страница 2: ...or Load DC Bus one Input Output for connection to the battery N 1 battery 12 Vdc for CBI 12xx N 2 battery 12 Vdc connected in Series for CBI 24xx N 4 battery 12 Vdc connected in Series for CBI 48xx 5...

Страница 3: ...installation clearance of 10 mm left right between two power supplies and avoid installing the power supplies on top of each other Note Avoid return voltage e g from a decelerating motor or battery w...

Страница 4: ...45 min 20 h Load 12 A No 3 min 12 min 30 min 600 min Load 15 A No No 9 min 20 min 400 min Load 20 A No No 7 min 13 min 240 min 6 LAY OUT AND CONNECTIONS 7 INPUT AND OUTPUT LOAD AND BATTERY CONNECTION...

Страница 5: ...wer 2 See Diagnosis Led 8 1 4 Relay Contact Rating Max DC1 30 Vdc 1 A AC1 60 Vac 1A Resistive load EN 60947 4 1 Min 1mA at 5 Vdc Min permissive load 8 1 5 Charging Mode STATUS Status Led Diagnosis No...

Страница 6: ...Acid Gel Ni Cd option They guarantee battery reliability in time by continuously testing the internal impedance status avoids any possible risk of damages and grants a permanent reliable and safe conn...

Страница 7: ...er Position Size 1 Jumper Position Size 2 Jumper Position Size 3 Dip Switch Position Size 4 Float charge Volt Cell Fast charge Volt Cell Open Lead 2 23 2 40 AGM Low 2 25 2 40 Gel Battery 2 30 2 40 NiC...

Страница 8: ...he quality resistance on the battery connection is checked every 60 sec This to detect if the cable connection has been properly made Battery in Open Circuit or Sulphated In Float charging mode the Al...

Страница 9: ...STICS The unit is a SLAVE in a MODBUS network The slave units are compliant to the following specifications Transmission mode MODBUS RTU Electrical Interface RS485 half duplex serial line Baud rate 48...

Страница 10: ...onnection Diagram Size3 CBI500 DPYCONN500 is a special cable for the connection of CBI Size3 and the other device max leght 0 5m RJ45COUPLER is e T connection RJ45 for daisy Chain with CBI Size3 RJCON...

Страница 11: ...ections to the external device like RTU PC DPY351 For the connection to RTU PLC or similar devices refer to the instruction manuals Modbus specifications_R14 Web Site www adelsystem com For configurat...

Страница 12: ...ity to EN60950 UL60950 1 and CSA C22 2 No 60950 1 07 Information Technology Equipment Safety Part1 General Requirement Device is intended to be installed in a cabinet protected from external shocks or...

Отзывы: