PDK-13010-v.6.0 Edge VS5010 and VS5051 User manual 

page 7

3  Connect cables from the alarm panels, voice panels and alarm 

transmitters to the terminal PCBA to the appropriate connections, 

see section 7.5 “Connecting voice panels and alarm transmitters”. 

4  Finish this procedure by contacting the ARC to verify and test 

alarm transmissions. 

7.4

 

Connecting power

 

Power to the terminal must be provided from a power supply providing 

10.5 to 28V DC with a recommended 1.6A current. The power supply must 

be able to be connected using the screw terminals. 

For the VS5051 only: 

If you have enabled the emergency light function, the 

power supply must be connected to the same fuse as the elevator car light. 

This also applies when the terminal is powered by the elevator controller.

 

IMPORTANT

: You can connect the power supply but DO NOT APPLY 

POWER TO THE TERMINAL NOW. Power will be applied later.

 

7.5

 

Fitting backup batteries for VS5051

 

Connect the internal battery to the PCBA battery connector (22), see 

section 6, “Board Configuration”.  

Note: 

Only use battery packs provided by AddSecure.

 

7.6

 

Connecting voice panels and alarm transmitters 

 

All voice panels or alarm panels sited in elevators use the two-wire Dial 

Capture port (21), see section 6, “Board Configuration”. For the best voice 

quality make sure the voice panel is configured with full duplex 

Note:

 The two-wire connection has no polarity so it can be connected 

either way round. 

 

Connect the voice panels or the alarm panels to the Dial Capture port (25), 

see section 6, “Board Configuration”. 

7.7

 

Connecting the terminal

 

Connect cables to the terminal PCBA to the appropriate connections, see 

section 6, “Board Configuration”. 

7.7.1

 

Power Outputs

 

The terminal supports a battery backed, 12V DC output, rated 500mA 

continuous operation. This supply is shared via the following, independently 

switchable outputs, see section 6, "Board Configuration": 

 Vout1, Emergency light If power to the Edge terminal is lost, the emergency 

power will turn on. 

 Vout2, Buzzer 

If the alarm button connected to the voice panel is 

pressed and held for minimum 5 seconds, the terminal 

will start calling the ARC, and then the buzzer will start 

buzzing for 10 seconds. This time can be adjusted by 

Addsecure technical support. 

Содержание Edge VS5010

Страница 1: ...PDK 13010 v 6 0 Edge VS5010 and VS5051 User manual Edge VS5010 and VS5051 User Manual...

Страница 2: ...ackup batteries for VS5051 7 7 6 Connecting voice panels and alarm transmitters 7 7 7 Connecting the terminal 7 7 7 1 Power Outputs 7 7 8 Powering up the terminal 8 8 Configuring the terminal 8 8 1 Ch...

Страница 3: ...1 AddSecure Connect AddSecure Connect is a cloud based platform that uses a secure private LINK network via the on board eSIM and does not require the installer to add a SIM card It provides secure a...

Страница 4: ...u can analyse and setup an installation remotely over AddSecure Connect You can read more about AddSecure Connect on www addsecure com 4 Before you start Ensure that a subscription to AddSecure Connec...

Страница 5: ...Light BT Not in use DC power in PNL Panel LED Expansion port PWR Power LED TTL serial port CEL Cellular LED Pin inputs 4 ETH Ethernet LED RS232 port SYS System LED Case Tamper input Cellular diversit...

Страница 6: ...erminal in the enclosure using the fixing kits supplied 2 Connect cables from the alarm panels voice panels and alarm transmitters to the terminal PCBA to the appropriate connections see section 7 6 C...

Страница 7: ...figuration Note Only use battery packs provided by AddSecure 7 6 Connecting voice panels and alarm transmitters All voice panels or alarm panels sited in elevators use the two wire Dial Capture port 2...

Страница 8: ...contact AddSecure 8 Configuring the terminal The terminal does not need to be configured All the configuration and activation is done by AddSecure directly to the unit 8 1 Checking signal strength A g...

Страница 9: ...Local connection Internet accessible Ethernet OK Polling OK data activity System No power System fault System OK 9 Configuration of the voice panels For details about the configuration of specific vo...

Страница 10: ...s required by EU directive 2014 33 11 2 Maintaining data AddSecure keep the information about the location of the plant phone numbers and related information updated based on input from the owner or s...

Страница 11: ...Connection MMCX socket for antenna on PCBA On VS5051 additional SMA socket on the outside of the enclosure Fault detection Loss of registration with network IP TCP ports outbound 53165 Alarms and Poll...

Страница 12: ...tronic protection 2 2A polyfuse Number of switchable outputs 3 Voltage at which fault is reported 10V Voltage at which fault is restored 11V Power storage device Type 7 2V NiMH rechargeable batteries...

Страница 13: ...output pin 14 Conformance The terminal complies with the following European Directives and standards 2014 53 EU Radio Equipment Directive 2002 96 EC WEEE 2011 65 EC ROHS No 1907 2006 REACH EN81 28 EN8...

Страница 14: ...ht No part of this document may be reproduced or used except as authorized by contract or other written permission from AddSecure The copyright and foregoing restriction on reproduction and use extend...

Отзывы: