background image

 12 

TROUBLE SHOOTING GUIDES 
General Refrigeration Circuit 

SYMPTOM

POSSIBLE CAUSE

1. Power off, loose electrical connections or fuse open.
2. Compressor contactor not closing.

3. Internal compressor thermal overload open.

4. Compressor defective.

5. High or low pressure switch open or defective.

6. Oil pressure control open or defective.

1. Low refrigerant charge
2. Airflow restricted.

3. Restriction in liquid line.

4. Defective low pressure switch.

1. Refrigerant overcharge.

2. Condenser fan control has incorrect setting.

3. Fan motor defective.

4. Condenser coil inlet obstructed or dirty.

5. Air or non-condensables in system.

6. Defective high pressure switch.

7. Restriction in discharge or liquid line.

1. Low voltage.

2. Sustained high discharge pressure.

3. High suction and discharge pressures.

4. Defective compressor overload.

5. Defective run capacitor.

6. Improper refrigerant charge.

7. Bearings or pistons too tight.

8. Allow time for compressor to cool.

1. Low oil level.

2. Defective oil pump.

3. Defective control.

4. Liquid refrigerant is entering crankcase.

1. Scroll compressors are rotation sensitive.

2. Refrigerant overcharge.

3. Excessive or insufficient oil in compressor

3. Check oil level in hermetic compressors. Check total e

crankcase.

4. Liquid floodback.
5. Tubing rattle.

6. Compressor defective.

4. Compressor will be wet. Check crankcase heater or cause for liquid feedback.

6. Check internal parts (semi-herm.)

1. Reverse wiring at disconnect switch, recheck for correct evaporator blower rotation.

2. Check pressures and subcooling.

4. Check TXV setting. Check for refrigerant overcharge. oil as recommended.
5. Dampen tubing vibration by taping or clamping. Bend tubing away from contact where possible.

8. Check dome temperature of the compressor.

1. Check crankcase sightglass - add oil to bring level to midway in sightglass.

2. Check oil pump.

3. Check oil failure control for calibration.

4. Allow compressor to cool for two hours if compressor is hot. Recheck for open circuit.

5. Check run capacitor for compressor and fan motor.

6. Check subcooling.

7. Check for low oil level.

7. Check discharge and liquid line pressures, check TXV.

1. Check voltage.

2. Check running amperage and conditions described under “high discharge pressure.”

3. Check TXV setting, check for air in system.

3. Check fan motor.

4. Check coil and inlet clearances and for possible air recirculation.

5. Check high side equalized pressure reading with equivalent outdoor temperature.

6. Check calibration of switch.

5. Check calibration of high or low pressure switch, re-calibrate or replace.

4. Check calibration of switch.

1. Check pressures, charge by sub cooling.

2. Check calibration of low ambient control.

1. Check sightglass and check pressures.
2. Check for dirty evaporator coil, dirty filters, dampers closed, iced evaporator, proper belt 
adjustment, proper motor amps, duct design

3. Check head pressure, check and adjust TXV if not functioning properly, check pressure drop 
across filter drier.

6. Check oil failure control. See oil failure control below.

1. Check disconnect switch, fuses and wiring. Replace parts or repair as necessary.

REMEDY

3. If compressor is hot, allow 2 hours to cool. See thermal overload below.

4. Check compressor for electrical failure. Compressor may be seized, check for L.R.A.

2. Check voltage to contactor coil, transformer, slave relay, system. Replace parts as necessary. 

E. Compressor cuts out on oil failure 
control (semi-herm.)

F. Noisy compressor.

A.Compressor will not start

B.Compressor starts but cuts out on 
low pressure switch.

C. Compressor starts but cuts out on 
high pressure switch.

D. Compressor cuts out on thermal 
overload.

 

 

Содержание B

Страница 1: ...sate Piping 5 Gas Piping and Venting 5 6 Cooling System Options 6 8 Hot Gas Bypass 6 Head Pressure Control 6 Variable Speed Control 6 Adjustable High and Low Pressure 7 Hot Water Heat Recovery 7 8 Mechanical Adjustments 9 10 Evaporator Blower Fan 9 10 Electrical System Options 10 Air Flow Switch 10 Clogged Filter Indicator 10 Convenience Outlet 10 Exhaust Fan Interlock 10 Power Through the Curb 10...

Страница 2: ...e anualmente sus equipos y realice el mantenimiento siempre que sea necesario usando exclusivamente piezas de repuesto de ADDISON Información adicional A través de los distribuidores de Addison está disponible la información sobre aplicaciones guías detalladas sobre diseño de sistemas e instalación y funcionamiento de los productos Por favor contacte con nosotros si necesita más información o si r...

Страница 3: ...Product Labeling Signal words are used in combination with colors and or pictures on product labels Following are examples of product labels with explanations of the colors used WARNING Electric Shock Hazard Turn Off All Power Before Servicing DANGER Fire Hazard Use copper wire only Failure to observe could result in property damage bodily injury or death WARNING Cuts and Abrasion Hazard Wear glov...

Страница 4: ...vice end and clearance at this point should be maintained A 36 clearance must be allowed for access to the compressor and electrical panel A 24 clearance must be maintained for the air inlet to the condenser coil s Do not locate the unit under an overhang that will short circuit hot air to the coil intakes When installed at ground level the unit should be mounted on a level concrete slab which sho...

Страница 5: ...Connections Power wiring should be connected to the main power terminal block located within the unit main control section Power wiring connections on units with factory disconnects should be made at the line side of the disconnect switch Low voltage wiring connections are made to the remote mounted controller or time clock DO NOT TAMPER WITH FACTORY WIRING Contact your local representative or the...

Страница 6: ... or metal be provided to prevent any possible damage to the roof If condensate is to be piped into the building drainage system the drain line must penetrate the roof external to the unit Refer to local codes for additional requirements CAUTION Units with high internal and external static pressure drops will require a deeper trap Use the graph and table in Figure 2 GAS PIPING AND VENTING For DC un...

Страница 7: ... discharge pressure will permit stable operation in ambients down to 32F The operating pressure switch is adjustable to match customer needs it is factory set to re energize the fans when discharge pressure drops to 295 psig and energize them when pressure increases to 430 psig Variable Speed Control The VARISPEED Fan Control System controls the compressor discharge pressure The speed control modu...

Страница 8: ... 0psig 150 psig and is factory set to open at 60 psig and close at 35psig The high pressure switch is adjustable between 200 psig And 610psig and factory set to open at 600psig and to close at 550 psig MECHANICAL ADJUSTMENTS SET FAN RPM All evaporator motor sheaves are set when tested and shipped from the factory Actual rpm must be set and verified with a tachometer Refer to the following Blower P...

Страница 9: ...off easily 7 Remove the belt Do NOT pry off belt 8 Loosen set screw s on the outer half of the adjustable pulley 9 The unit has one of two different types of adjustable pulleys 10 Remove key if unit has a keyway type pulley 11 To set the blower for a desired CFM L s first turn the outer half of the adjustable pulley clockwise until it meets the inner half of the pulley 12 Turn the outer half of th...

Страница 10: ...a sleeve can be installed in the compressor section to bring power wiring inside the curb preventing a separate roof penetration The sleeve must be sealed after wiring is completed with a suitable mastic to prevent water from entering the space Firestat This control mounted in the return air section de energizes the unit when return air reaches 135 F It is a manual reset control Sure Trip This con...

Страница 11: ...ermistor The Electronic solid state control center measures the sensor s change in resistance and sends a varying DC current to the Modulator Regulator valve to adjust the gas input as required 5 The flame sensor proves the presence of the pilot flame generating a DC current of 0 2 microamp or greater to the ignition control The ignition control s internal switch action then de energizes the spark...

Страница 12: ...ance Bearings Small ECW s smaller than ECW666 are provided with no maintenance inboard bearings These bearings should require no maintenance during the life of the equipment Larger ECW s come equipped with an external flanged bearing which should be greased annually Use a petroleum based lubricant Drive Motor The drive motors should require no maintenance Replacement motors may be purchased from n...

Страница 13: ...dome temperature of the compressor 1 Check crankcase sightglass add oil to bring level to midway in sightglass 2 Check oil pump 3 Check oil failure control for calibration 4 Allow compressor to cool for two hours if compressor is hot Recheck for open circuit 5 Check run capacitor for compressor and fan motor 6 Check subcooling 7 Check for low oil level 7 Check discharge and liquid line pressures c...

Страница 14: ...usted expansion valve 4 Check superheat and adjust TXV 5 Dirty filter 5 Check filter and evaporator coil 6 Too little air flow or low entering air temperature 6 Check airflow and entering air wet bulb conditions 7 Restriction in suction or liquid line 7 Check refrigerant circuit for restriction 1 Insufficient refrigerant charge 1 Check subcooling check for leak 2 Defective or improperly adjusted e...

Страница 15: ...r motor not running N Supply air temperature too high O Supply air temperature P Liquid line too hot R Suction line frosting Varispeed Condenser Head Pressure Control SYMPTOM POSSIBLE CAUSE REMEDY 1 Input pressure is below operating range 1 No problem normal operation 2 No 24 volt control voltage 2 Check for 24 V AC at control 3 No input pressure to control 3 Check alignment of capillary fitting S...

Страница 16: ...al equalizer passage 5 Worn or eroded regulator seat A Erratic pressure control E Regulator fails to close D Regulator will not provide pressure control C Regulator hunting chattering large fluctuations in controlled pressures B Regulator leakage 4 Locate and remove stoppage Install strainer 5 Replace defective part 2 Increase superheat setting Dampen bulb response by repositioning 2 Readjust the ...

Страница 17: ...er supply must be 24V AC 2 MR valve installed backward 2 Arrow on MR valve should point in direction of gas flow 2 Install properly 1 Room Override Thermostat if used calls for heat 1 Remove T115 wires from amplifier terminals 3 and 14 1 If proper operation is obtained check thermostat wiring for shorts Rotate thermostat dial above and below room temperature to prove thermostat function 2 Open cir...

Страница 18: ...obstruction in gas pipe ahead of controls Increase gas pressure if possible H Incorrect discharge air temperature 1 Calibration 1 Check seal on calibration potentiometer 1 Recalibrate per Temperature Calibration procedure 1 Dirty or sticking plunger 1 Examine Plunger should be clean smooth and operate freely in solenoid sleeve 1 Clean or replace plunger if necessary 2 Loose or broken wiring 2 Insp...

Страница 19: ...19 ...

Отзывы: