 10 

SEQUENCE OF OPERATION 

Heating, Hydronic or Steam  

Both hydronic and steam heat require a one or two row 
coil generally located downstream of the evaporator coil. 

Controls for hydronic heat will involve a 3 way motorized 
mixing or blending valve, driven by a signal from a leaving 
air temperature thermostat. 

Controls for low-pressure steam heat contain a motorized 
throttling valve driven by a signal from a leaving air 
temperature thermostat 

 

Gas Heat 

 

See the gas furnace instruction manual for wiring and 
performance data. Additional information can be found on 
the furnace access door such as the rating and serial 
label, wiring and lighting instruction label. 
 

1.  Blower operation is confirmed by line voltage from the 

load side of the blower contactor to the gas furnace 
power supply terminals. 

2.  The furnace section is energized from the control 

terminal across the normally closed contacts of the 
combustion pressure switch, energizing pilot ignition 
time delay relay heater. After delay of approximately 
30-50 seconds the time delay relay’s switch closes 
energizing the furnace venter motor. As the venter 
operates, it causes the combustion pressure switch to 
open. The ignition control energizes the pilot valve 
solenoid in the combination gas valve. A high voltage 
electric spark lights the pilot flame. 

3.  The flame sensor proves the presence of the pilot 

flame generating a DC current of 0.2 microamp (or 
greater) to the ignition control.  The ignition control’s 
internal switch action then de-energizes the spark 
transformer and makes a circuit to the high fire 
solenoid of the combination gas valve. 

4.  When there is a call for gas furnace operation the 

discharge air temperature causes a change in the 
resistance of a discharge air sensor thermistor. The 
Electronic solid state control center measures the 
sensor’s change in resistance and sends a varying DC 
current to the Modulator-Regulator valve to adjust the 
gas input as required. 

5.  The flame sensor proves the presence of the pilot 

flame generating a DC current of 0.2 microamp (or 
greater) to the ignition control.  The ignition control’s 
internal switch action then de-energizes the spark 
transformer and makes a circuit to the high fire 
solenoid of the combination gas valve. 

 

 

 

Electric Heat 

 

1.  DC units that use the down flow discharge. The  

installer 

MUST

 use an “L” shaped discharge duct 

that does not have an outlet directly below the 
units discharge opening, per UL1995. To guard 
against the very rare occurrence of a piece of an 
electric heating element breaking away. A straight 
duct or outlet grill directly below the unit discharge 
may allow a hot fragment to land in a conditioned 
space and start a fire. 

2.  Blower operation is generally confined by an air 

pressure differential switch as part of the heater 
assembly. 

3.  A thermostat or thermostats in the entering outside 

air energize the strip heat as required. Unit leaving 
air temperature will vary depending on kW, the 
number of stages, and the entering air 
temperature. Calculate the temperature rise using 
the following formula: 

 

°F Rise  =  kW  x  3413 
 1.08 

CFM 

Where °F rise is the air temperature increase, kW is the 
heater capacity in kilowatts and CFM is the total airflow of 
the unit. 

Subtract the °F rise from the desired leaving air 
temperature and set the thermostat at that value. For 
multiple stages, calculate the °F rise for each stage and 
set thermostats subtracting each rise from the previous 
entering air temperature.  

For example:   

CFM 2000 

kW 

22.5, 3 stage, 7.5 kW each 

Leaving air desired 65°F 

 

°F Rise  

7.5  x  3413  =  11.7°F 

 

 

1.1  x  2000 

Set 1

st

 stage thermostat to energize at 65-11.7  =  53.3° F 

Set 2

nd

 stage to energize at 53.3 -11.7 =  41.6°F 

Set 3

rd

 stage to energize at 41.6-11.7  =  29.9°F

 

Содержание B

Страница 1: ...sate Piping 5 Gas Piping and Venting 5 6 Cooling System Options 6 8 Hot Gas Bypass 6 Head Pressure Control 6 Variable Speed Control 6 Adjustable High and Low Pressure 7 Hot Water Heat Recovery 7 8 Mechanical Adjustments 9 10 Evaporator Blower Fan 9 10 Electrical System Options 10 Air Flow Switch 10 Clogged Filter Indicator 10 Convenience Outlet 10 Exhaust Fan Interlock 10 Power Through the Curb 10...

Страница 2: ...e anualmente sus equipos y realice el mantenimiento siempre que sea necesario usando exclusivamente piezas de repuesto de ADDISON Información adicional A través de los distribuidores de Addison está disponible la información sobre aplicaciones guías detalladas sobre diseño de sistemas e instalación y funcionamiento de los productos Por favor contacte con nosotros si necesita más información o si r...

Страница 3: ...Product Labeling Signal words are used in combination with colors and or pictures on product labels Following are examples of product labels with explanations of the colors used WARNING Electric Shock Hazard Turn Off All Power Before Servicing DANGER Fire Hazard Use copper wire only Failure to observe could result in property damage bodily injury or death WARNING Cuts and Abrasion Hazard Wear glov...

Страница 4: ...vice end and clearance at this point should be maintained A 36 clearance must be allowed for access to the compressor and electrical panel A 24 clearance must be maintained for the air inlet to the condenser coil s Do not locate the unit under an overhang that will short circuit hot air to the coil intakes When installed at ground level the unit should be mounted on a level concrete slab which sho...

Страница 5: ...Connections Power wiring should be connected to the main power terminal block located within the unit main control section Power wiring connections on units with factory disconnects should be made at the line side of the disconnect switch Low voltage wiring connections are made to the remote mounted controller or time clock DO NOT TAMPER WITH FACTORY WIRING Contact your local representative or the...

Страница 6: ... or metal be provided to prevent any possible damage to the roof If condensate is to be piped into the building drainage system the drain line must penetrate the roof external to the unit Refer to local codes for additional requirements CAUTION Units with high internal and external static pressure drops will require a deeper trap Use the graph and table in Figure 2 GAS PIPING AND VENTING For DC un...

Страница 7: ... discharge pressure will permit stable operation in ambients down to 32F The operating pressure switch is adjustable to match customer needs it is factory set to re energize the fans when discharge pressure drops to 295 psig and energize them when pressure increases to 430 psig Variable Speed Control The VARISPEED Fan Control System controls the compressor discharge pressure The speed control modu...

Страница 8: ... 0psig 150 psig and is factory set to open at 60 psig and close at 35psig The high pressure switch is adjustable between 200 psig And 610psig and factory set to open at 600psig and to close at 550 psig MECHANICAL ADJUSTMENTS SET FAN RPM All evaporator motor sheaves are set when tested and shipped from the factory Actual rpm must be set and verified with a tachometer Refer to the following Blower P...

Страница 9: ...off easily 7 Remove the belt Do NOT pry off belt 8 Loosen set screw s on the outer half of the adjustable pulley 9 The unit has one of two different types of adjustable pulleys 10 Remove key if unit has a keyway type pulley 11 To set the blower for a desired CFM L s first turn the outer half of the adjustable pulley clockwise until it meets the inner half of the pulley 12 Turn the outer half of th...

Страница 10: ...a sleeve can be installed in the compressor section to bring power wiring inside the curb preventing a separate roof penetration The sleeve must be sealed after wiring is completed with a suitable mastic to prevent water from entering the space Firestat This control mounted in the return air section de energizes the unit when return air reaches 135 F It is a manual reset control Sure Trip This con...

Страница 11: ...ermistor The Electronic solid state control center measures the sensor s change in resistance and sends a varying DC current to the Modulator Regulator valve to adjust the gas input as required 5 The flame sensor proves the presence of the pilot flame generating a DC current of 0 2 microamp or greater to the ignition control The ignition control s internal switch action then de energizes the spark...

Страница 12: ...ance Bearings Small ECW s smaller than ECW666 are provided with no maintenance inboard bearings These bearings should require no maintenance during the life of the equipment Larger ECW s come equipped with an external flanged bearing which should be greased annually Use a petroleum based lubricant Drive Motor The drive motors should require no maintenance Replacement motors may be purchased from n...

Страница 13: ...dome temperature of the compressor 1 Check crankcase sightglass add oil to bring level to midway in sightglass 2 Check oil pump 3 Check oil failure control for calibration 4 Allow compressor to cool for two hours if compressor is hot Recheck for open circuit 5 Check run capacitor for compressor and fan motor 6 Check subcooling 7 Check for low oil level 7 Check discharge and liquid line pressures c...

Страница 14: ...usted expansion valve 4 Check superheat and adjust TXV 5 Dirty filter 5 Check filter and evaporator coil 6 Too little air flow or low entering air temperature 6 Check airflow and entering air wet bulb conditions 7 Restriction in suction or liquid line 7 Check refrigerant circuit for restriction 1 Insufficient refrigerant charge 1 Check subcooling check for leak 2 Defective or improperly adjusted e...

Страница 15: ...r motor not running N Supply air temperature too high O Supply air temperature P Liquid line too hot R Suction line frosting Varispeed Condenser Head Pressure Control SYMPTOM POSSIBLE CAUSE REMEDY 1 Input pressure is below operating range 1 No problem normal operation 2 No 24 volt control voltage 2 Check for 24 V AC at control 3 No input pressure to control 3 Check alignment of capillary fitting S...

Страница 16: ...al equalizer passage 5 Worn or eroded regulator seat A Erratic pressure control E Regulator fails to close D Regulator will not provide pressure control C Regulator hunting chattering large fluctuations in controlled pressures B Regulator leakage 4 Locate and remove stoppage Install strainer 5 Replace defective part 2 Increase superheat setting Dampen bulb response by repositioning 2 Readjust the ...

Страница 17: ...er supply must be 24V AC 2 MR valve installed backward 2 Arrow on MR valve should point in direction of gas flow 2 Install properly 1 Room Override Thermostat if used calls for heat 1 Remove T115 wires from amplifier terminals 3 and 14 1 If proper operation is obtained check thermostat wiring for shorts Rotate thermostat dial above and below room temperature to prove thermostat function 2 Open cir...

Страница 18: ...obstruction in gas pipe ahead of controls Increase gas pressure if possible H Incorrect discharge air temperature 1 Calibration 1 Check seal on calibration potentiometer 1 Recalibrate per Temperature Calibration procedure 1 Dirty or sticking plunger 1 Examine Plunger should be clean smooth and operate freely in solenoid sleeve 1 Clean or replace plunger if necessary 2 Loose or broken wiring 2 Insp...

Страница 19: ...19 ...

Отзывы: