ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)

  

IMPORTANT

:

  

NOTES

: A.

 B.
 
 
 C.

208 VAC AND 230/240 VAC ARE NOT THE SAME.  When ordering,
specify exact voltage.

When fuses are used they must be dual element, time delay, current

limiting, class RK1 or RK5 ONLY.  Calculate/determine correct fuse

value, by applying either local and/or National Electrical Codes to

listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY.  For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.

SERVICE

VOLTAGE

PHASE

WIRE

SERVICE

APPROX.

AMP DRAW

CIRCUIT

BREAKER

60 Hz

50 Hz

208

3

12

15

240

3

10

15

230

3

8

15

380

 4

*

6

15

400

 4

*

5

15

416

 4

*

5

15

460

3

6

15

480

3

6

15

Electrical Connections

The only electrical input connections to the dryer are the
3-phase (3ø) power leads (L1, L2, and L3), GROUND, and
in the case of 4-wire service, the NEUTRAL.  These electrical
connections are made at the terminal block located in the
service/relay box at the rear, upper right hand corner of the
dryer.  To gain access into this service box, the service cover
must be removed.

The “LINE POWER” and the “GROUND” connections to the
dryer must be made through the knockout hole at the top of
the electric service/relay box.  A strain relief must be used
where the line power ground wires go into the electric
service/relay box.

Electrical Service Specifications

IMPORTANT: 

Figures shown are for reversing models

only.

Gas Models Only

*  3-Wire is available, contact the factory for information.

10/21/14

Grounding

A ground (earth) connection must be provided and installed
in accordance with state and local codes.  In the absence of
these codes, grounding must conform to applicable
requirements of the National Electrical Code ANSI/NFPA NO.
70-LATEST EDITION, or in Canada, the installation must
conform to applicable Canada Standards: Canadian Electrical
Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION.
The ground connection may be to a proven earth ground at
the location service panel.

For added personal safety, when possible, it is suggested
that a separate ground wire (size per local codes) be
connected from the ground connection of the dryer to a
grounded cold water pipe.  Do not ground to a gas pipe or
hot water pipe.  The grounded cold water pipe must have
metal-to-metal connection all the way to the electrical ground.
If there are any nonmetallic interruptions, such as, a meter,
pump, plastic, rubber, or other insulating connectors, they
must be jumped out with a wire (size per local codes) and
securely clamped to bare metal at both ends.

IMPORTANT: 

For personal safety and proper operation,

the dryer must be grounded.

NOTE: 

A grounding connection (terminal lug) is provided in

the dryer’s electrical service/relay box at the rear, upper
right hand corner of the dryer.

Grounding via metallic electrical conduit (pipe) is not
recommended.

Provisions are made for ground connection in each dryer at
the electrical service connection area.

Providing local codes permit, power connections to the dryer
can be made by use of a flexible UL listed power cord/pigtail
(wire must conform to ratings of the dryer), or the dryer can
be hard wired directly to the service breaker.  In all cases, a
strain relief must be used where the wire(s) enter the dryer’s
electrical service (relay) box.

IMPORTANT: 

A separate protected circuit must be

provided to each dryer.

Gas Information _______________________

It is your responsibility to have all plumbing connections
made by a qualified professional to ensure that the gas
plumbing installation is adequate and conforms to local
and state regulations or codes.  In the absence of such
codes, all plumbing connections, materials, and
workmanship must conform to the applicable requirements
of the National Fuel Gas Code ANSI Z223.1-LATEST
EDITION, or in Canada, the Canadian Installation Codes
CAN/CGA-B149.1-M91 (Natural Gas) or CAN/CGA-B149.2-
M91 (Propane Gas) or LATEST EDITION.

In Australia, the fuel gas code is AS/NZS5601, local authority,
gas, electricity, and any other relevant statutory regulations.

IMPORTANT: 

Failure to comply with these codes or

ordinances, and/or the requirements stipulated in this
manual, can result in personal injury and improper
operation of the dryer.

The dryer and its individual shutoff valve must be
disconnected from the gas supply piping system during
any pressure testing of that system at test pressures in
excess of 1/2 psig (3.5 kPa).

Содержание ML-96

Страница 1: ... des incendies L installation et l entretien doivent être assurés par un installateur ou un service d entretien qualifié ou par le fournisseur de gaz WARNING FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in serious injury death or property damage Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT ...

Страница 2: ...your order is processed accurately and promptly These instructions are only valid if the following country code is on the appliance If this code is not present on the appliance it is necessary to refer to the technical instructions which will provide the necessary information concerning the modification of the appliance to the condition of use for the country In accordance with EN ISO 3166 1 the n...

Страница 3: ...Do not dry mop heads in the dryer Do not use dryer in the presence of dry cleaning fumes The dryers must not be installed or stored in an area where it will be exposed to water and or weather The wiring diagram for the dryer is located in the front electrical control box area List of Acronyms _____________________________ D M S Drill Measurement Size DSI Direct Spark Ignition HVAC Heating Ventilat...

Страница 4: ...oid the warranty Under no circumstances should the dryer door switch es lint door drawer switch es or heat safety circuit s ever be disabled This dryer is not to be used in the presence of dry cleaning solvents or fumes Remove articles from the dryer as soon as the drying cycle has been completed WARNING Articles left in the dryer after the drying and cooling cycles have been completed can create ...

Страница 5: ..._______________________________________________________ ____________________________________________________________ NOTES _____________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ ________________________________________...

Страница 6: ... CONNECTION DIAMETER 16 40 64 cm COMPRESSED AIR CONNECTION 1 4 Quick Connection COMPRESSED AIR VOLUME 4 25 cfh 0 12 cmh INLET PIPE CONNECTION 1 F N P T 1 F B S P T CE and Australia Only VOLTAGE AVAILABLE N A APPROX NET WEIGHT APPROX SHIPPING WEIGHT AIRFLOW EXHAUST CONNECTION DIAMETER COMPRESSED AIR CONNECTION COMPRESSED AIR VOLUME OVEN SIZE kW Btu hr kcal hr VOLTAGE AVAILABLE N A APPROX NET WEIGHT...

Страница 7: ...dclaundry com 7 Specifications _____________________________________________________________________ NOTE The manufacturer reserves the right to make changes in specifications at any time without notice or obligation ...

Страница 8: ...ryer must be installed with a proper exhaust duct connection to the outside as noted in this manual refer to Exhaust Requirements section The dryer must be located in an area where correct exhaust venting can be achieved as noted in this manual refer to Exhaust Requirements section IMPORTANT The dryer should be located where a minimum amount of exhaust ducting will be necessary The dryer must be i...

Страница 9: ...dryer base To reinstall the top console module reverse the above steps NOTE After reinstalling top console module assure electric phase sequence is correct and motors are turning in the proper direction refer to Preoperational Test section A 40 inches 101 6 cm for optimum opening of load door B The maximum thickness of the bulkhead is 4 inches 10 16 cm For electric dryers the maximum thickness of ...

Страница 10: ...e duct all the way around The duct must be centered within this opening As per the National Fuel Gas Code Exhaust ducts for type 2 clothes dryers shall be constructed of sheet metal or other noncombustible material Such ducts shall be equivalent in strength and corrosion resistance to ducts made of galvanized sheet steel not less than 26 gauge 0 0195 inches 0 50 mm thick Fresh Air Supply Requireme...

Страница 11: ...lbows used for outside protection from the weather no more than 1 elbow should be used in the exhaust duct run If more than 1 elbow is used the cross sectional area of the ductwork must be increased Outside Ductwork Protection To protect the outside end of the horizontal ductwork from the weather a 90 elbow bent downward should be installed where the exhaust exits the building If the ductwork trav...

Страница 12: ...nd conforms to local and state regulations or codes In the absence of such codes all electrical connections materials and workmanship must conform to the applicable requirements of the National Electrical Code ANSI NFPA NO 70 LATEST EDITION or in Canada the Canadian Electrical Codes Parts 1 2 CSA C22 1 1990 or LATEST EDITION For personal safety the dryer when installed must be electrically grounde...

Страница 13: ...ssible it is suggested that a separate ground wire size per local codes be connected from the ground connection of the dryer to a grounded cold water pipe Do not ground to a gas pipe or hot water pipe The grounded cold water pipe must have metal to metal connection all the way to the electrical ground If there are any nonmetallic interruptions such as a meter pump plastic rubber or other insulatin...

Страница 14: ... gas dryer is not provided with an internal gas supply shutoff and an external gas supply shutoff must be provided Technical Gas Data Gas Specifications For Australia refer to data plate back panel Shaded areas are stated in metric equivalents Measured at outlet side of gas valve pressure tap when gas valve is on Shaded area is stated in metric equivalent D M S equivalents are as follows Natural G...

Страница 15: ... rear of the dryer A flexible supply line coupling must be used in an effort to avoid damaging the electric water solenoid valve NOTE The 3 4 11 5 NH is a standard hose coupling screw thread It is not to be confused with 3 4 N P T The sealing of an NH connection is made with a washer opposed to the mating threads of an N P T assembly The 2 thread designs are not compatible It is recommended that a...

Страница 16: ...e water connection for the manual bypass is made to the T or three way fitting which has a 3 8 F P T and a coupling must be used to provide the minimum 1 2 inch 12 7 mm supply feed line If the rear area of the dryer or the water supply is located in an area where it will be exposed to cold freezing temperatures provisions must be made to protect these water lines from freezing Electrical Requireme...

Страница 17: ...sed parameter program selections If computer program changes are required refer to the computer programming manual which was shipped with the dryer Tumbler Coating The tumbler is treated with a protective coating We suggest dampening old garments or cloth material with a solution of water and nonflammable mild detergent and tumbling them in the tumbler to remove this coating WARNING ELECTRICAL SHO...

Страница 18: ... valve burner area 3 Phase 3ø Electric Service Check the electric service phase sequence 3 phase 3ø models only While the dryer is operating check to see if the blower fan is rotating in the proper direction Looking from the front the blower fan should spin in the clockwise direction if it is the phasing is correct If the phasing is incorrect reverse 2 of the 3 leads at connections L1 L2 and L3 of...

Страница 19: ...s or refunds will be issued and the merchandise will be discarded Service Parts Information __________ Service Service must be performed by a qualified trained technician service agency or gas supplier If service is required contact the reseller from whom the equipment was purchased If the reseller cannot be contacted or is unknown contact the Service Department for a reseller in your area NOTE Wh...

Страница 20: ...lation in and around the motor s casing opening NOTE To prevent damage avoid cleaning and or touching ignitor flame probe assembly Every 6 Months Inspect and remove lint accumulation in customer furnished exhaust ductwork system and from dryer s internal exhaust ducting NOTE The accumulation of lint in the exhaust ductwork can create a potential fire hazard Do not obstruct the flow of combustion a...

Страница 21: ...n Coin Models Upon completing installation of the replacement microprocessor controller computer board reestablish power to the dryer Start the drying cycle by pressing any of the preset cycles in letters A F Verify that the applicable indicator lights on the microprocessor controller computer board are lit Refer to the illustration below Theory of Operation Start the drying cycle When the gas bur...

Страница 22: ... Allows the manufacturer to gather information on your particular dryer 3 Type of Heat This describes the type of heat for your particular dryer gas either natural gas or propane gas electric or steam 4 Heat Input For Gas Dryers This describes the heat input in British thermal units per hour Btu hr or kilowatts kW 5 Orifice Size For Gas Dryers Gives the number drill size used 6 Electric Service Th...

Страница 23: ...ront right side of the burner box WARNING Discontinue power to dryer before attempting to reset hi limit NOTES _____________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________________ ____________________________________________________...

Страница 24: ...ADC Part No 113362 25 09 17 21 ...

Отзывы: