4.0 Modes of Operation of an RELIANCE Remote

4.1 Frequency Scan

Initial State on a new remote from the factory.
State on delivery
On delivery, each new RELIANCE Remote that has not yet been logged on with a RELIANCE Master is in “frequency scan

mode”. For power-up mode (“On”), fail-safe mode (“On”) and Delayed Start/Stop (“Off”) it uses the factory settings, which are

given here in brackets (default values). RGL//Wig-wag remotes are pre-configured with “Blink” for power-up and fail-safe

mode.
Base state
A RELIANCE Remote that has been logged off from a circuit also reverts to frequency scan mode. However, for power-up

mode, fail-safe mode and Delayed Start/Stop it uses the most recent settings received from the RELIANCE Master (most

recent configuration). In frequency scan mode, a RELIANCE Remote, when it is installed in a series circuit and the latter is

turned on, searches on all frequency bands for a master telegram containing its serial number. If this search is successful, the

RELIANCE Remote logs on to the corresponding RELIANCE Master. When an RELIANCE Remote is logged off from a circuit, it

reverts to base state.

4.2 Operating Mode

After successfully logging on, a RELIANCE Remote automatically switches to “operating mode” (normal operation) and

receives its configuration parameters from the RELIANCE Master. All parameters are stored firmly in the AGLAS Remote. In

operating mode, all lights connected to the RELIANCE Remotes can be switched independently of each other via single or

block commands (i.e. a command switches a predefined group of lights).The switch commands can be “On”, “Off” or “Blink”.
When a RELIANCE Remote receives a switch command it returns the message “switch command executed” (block command)

or “switch command received” (single command). However, the real status of the lights is only determined at the next status

polling by the RELIANCE Master. In the RELIANCE Remote, each switching operation for the light is carried out first via an

electronic switch and then via a relay (“blink” mode is established with electronic switch only).
Each RELIANCE Remote monitors the status of the lights connected to it (maximum of two lights). The monitoring takes place

when the light is switched on by default. Whether the lamp should be monitored in the “Off” state too, is configurable. Once

a lamp failure has been detected (“Open”), the light is no longer monitored during this operation period and switch

commands for this light are ignored. It will not be checked again until the circuit has been switched off and on again or after

the reception of a reset command (software function) from the RELIANCE PC.

4.2.1 Self-test Mode

After the series circuit has been switched on, each RELIANCE Remote runs a self-test. If an error is detected through this test,

the RELIANCE Remote switches to error mode. This means that communication with a RELIANCE Master is not possible.
During normal operation, the remote also checks the switching and high voltage protection devices. If any problem should

occur with these devices (after 9 lightning strike for example), a specific error message is sent to the master.

4.3 Switch Status of the Connected Lights

One light can be connected to each single channel RELIANCE Remote, and up to two lights (“A” and “B”) can be connected to

each dual channel RELIANCE Remote. A light can assume the following types of status:

“Off” (light is switched off and not burning).

“On” (light is switched on and the electric circuit is closed).

“Open” (light is switched on but the electric circuit is not closed, i.e. the light filament is broken or the light is not

connected).

“Blink” (light flashing; no information as to whether the light is “On” or “Off” at the time of polling).

On the Graphical User Interface (GUI), the status of each light is indicated by the terms given in quotation marks.

96A0481, Rev. B, 2019/10/01

23

Copyright 

©

 ADB Safegate, All Rights Reserved

Содержание RELIANCE AGLAS-C

Страница 1: ...RELIANCE Intelligent Lighting Remote Control Device AGLAS C Remotes User Manual 96A0481 Rev B 2019 10 01 ...

Страница 2: ......

Страница 3: ...d are guaranteed to be merchantable and fit for the ordinary purposes for which such products are made ADB SAFEGATE L858 Airfield Guidance Signs are warranted against mechanical and physical defects in design or manufacture for a period of 2 years from date of installation per FAA AC 150 5345 44 applicable edition Note See your sales order contract for a complete warranty description All Products ...

Страница 4: ...SAFEGATE replacement parts or accessories Failing to make sure that auxiliary equipment complies with approval agency requirements local codes and all applicable safety standards if not in contradiction with the general rules Using materials or auxiliary equipment that are inappropriate or incompatible with your ADB SAFEGATE equipment Allowing unskilled personnel to perform any task on or with the...

Страница 5: ...stallation in a Transformer Pit 17 3 2 Connection to the Series Transformer and the Light Fitting s 18 3 3 Utility Remote Enclosure Wiring Diagram 20 3 4 Earth Grounding 21 3 5 Safety Instructions 21 3 6 Replacing an RELIANCE Remote 21 4 0 Modes of Operation of an RELIANCE Remote 23 4 1 Frequency Scan 23 4 2 Operating Mode 23 4 2 1 Self test Mode 23 4 3 Switch Status of the Connected Lights 23 4 4...

Страница 6: ...RELIANCE C Remote Control Device TABLE OF CONTENTS vi Copyright ADB Safegate All Rights Reserved ...

Страница 7: ...o observe this warning may result in personal injury death or equipment damage ARC Flash may cause blindness severe burns or death WARNING Wear personal protective equipment Failure to observe may result in serious injury WARNING Do not touch Failure to observe this warning may result in personal injury death or equipment damage CAUTION Failure to observe a caution may result in equipment damage Q...

Страница 8: ...afety devices as specified by applicable safety regulations If safety devices must be removed for installation install them immediately after the work is completed and check them for proper functioning prior to returning power to the circuit Failure to follow this instruction can result in serious injury or equipment damage Additional Reference Materials Important Information IEC International Sta...

Страница 9: ... trained and familiar with ADB SAFEGATE equipment are permitted to service this equipment An open airfield current circuit is capable of generating 5000 Vac and may appear OFF to a meter Never unplug a device from a constant current circuit while it is operating Arc flash may result Disconnect and lock out electrical power Always use safety devices when working on this equipment Follow the recomme...

Страница 10: ...RELIANCE C Remote Control Device Safety 4 Copyright ADB Safegate All Rights Reserved ...

Страница 11: ...e airfield lighting system The ALCMS may include Touch Screens for lighting control Maintenance Center s for data viewing and archiving Electrical Lighting equipment for CCR control and monitoring CCR Abbreviation for Constant Current Regulator The CCRs are located within the Airfield Lighting Vault ALV They produce a constant current output to the airfield series circuit that light the airfield l...

Страница 12: ...aircraft guidance in all weather conditions Supports safety of airport operations by integration in runway safety nets IEC Developed in accordance with IEC 61508 Introduction The RELIANCE Intelligent Lighting IL is ADB SAFEGATE s state of the art individual lamp control and monitoring system RELIANCE Intelligent Lighting provides a radical leap in performance over prior airfield power line carrier...

Страница 13: ...n a permanent background process New communication principle together with forward error correction drastically reduces signal disturbance caused by impulse and narrow band interferences Main system elements RELIANCE IL Master in the substation RELIANCE IL Remotes for individual control and monitoring of lights in the field In addition RELIANCE IL Utility Remote for communication with and energy s...

Страница 14: ... 10 distinct states with one power line message Can command all blocks to one state with one powerline message Switches up to 120 lights in 10 different groups in less than 1 second Switches 5 stopbar lead on lights simultaneously and presents real back indication in less than 1 second Status poll provides detailed Remote and lamp parameters Integrated System Control Overall system configuration a...

Страница 15: ...8 x 78 x 142 2 2 kg single Remote 2 3 kg dual 435 8 x 177 5 x 421 5mm 22 3 kg Lamp failure reaction Short is placed across isolation transformer as soon as lamp flament failure detected Power Storage after Power Off Remote does not reset and remains in operation if circuit power loss 1 5 sec Remote start up time is less than 1 sec Circuit Specifications Cable type L 824 is recommended for example ...

Страница 16: ...emote FAA Style 7 Initial Flash Off AGC4270 RELIANCE IL Single Channel Remote FAA Style 7 Initial Flash On AGC4370 RELIANCE IL Dual Channel Remote FAA Style 7 AGC5170 RELIANCE IL Dual Channel Remote FAA Style 7 Channel A Initial Flash On Channel B Initial Flash Off AGC5470 RELIANCE IL Utility Remote AGC6110 2 2 2 General The RELIANCE Remotes are intelligent powerline addressable field devices that...

Страница 17: ...bles for connection to the series transformer and the light The RELIANCE C Remote dual channel is supplied with three 12 inch 30 cm cord set cables 1 for connection to the series transformer and 2 for connection to the lights The RELIANCE C Remote single channel RGL is supplied with two 12 inch 30 cm cord set cables for connection to the series transformer and the light adjusted at the factory for...

Страница 18: ...connections Figure 3 View of the RELIANCE Remote Dual Channel X1 X4 X3 5 Reliance Remote Dual Channel 4 Ground Screw X2 6 Remote ID Label 1 Cable with 2 pin plug in compliance with FAA L 823 for connection to the series circuit isolation transformer X3 2 Cable with 2 pin socket in compliance with FAA L 823 for connection to the light on channel A X1 3 Cable with 2 pin socket in compliance with FAA...

Страница 19: ...LIANCE Utility Remote Cabinet Note See the remote cabinet wiring diagram for connections 2 2 6 1 Construction The AGLAS Remote is sealed to make it watertight and gas tight and must not be opened 96A0481 Rev B 2019 10 01 13 Copyright ADB Safegate All Rights Reserved ...

Страница 20: ...municate between controlling units on an airfield lighting series circuit A RELIANCE system typically consists of one high voltage modem or Master connected with the Constant Current Regulator CCR powering the airfield lighting circuit and many slave units or Remotes collocated with individual lights in the field A typical RELIANCE topology is provided in Figure 6 Figure 6 Typical RELIANCE Topolog...

Страница 21: ...Master shown in blue is the high voltage modem that communicates commands to and receives status from the fixtures There can be many masters in a given system Masters digest commands from the control system and provide status to it Masters also communicate amongst themselves to maintain communication timing synchronization Each master communicates with the fixtures on its respective circuit Figure...

Страница 22: ...RELIANCE C Remote Control Device RELIANCE Remote 16 Copyright ADB Safegate All Rights Reserved ...

Страница 23: ...um heat dissipation through the housing If the device is installed by suspension free air circulation must be provided for the RELIANCE Remote Note If several RELIANCE Remotes are installed in a single pit they should be spaced with a distance of at least 2 inch 50mm from each other and from the series transformers to have optimum communication signal separation Because the communication signal is...

Страница 24: ...rink sleeves To improve watertightness an optional watertight heat shrink sleeve can be installed at the junction of the plug and receptacle see Figure 10 Figure 10 Connection to series transformer and light fitting 1 Place the heat shrink sleeve over the light inset plug wire 2 Connect the inset light plug to the Remote receptacle designated CHANNEL A and CHANNEL B if used 3 Pull the heat shrink ...

Страница 25: ...Repeat steps 1 through 3 for the Remote plug designated TRANSFORMER and the transformer secondary receptacle 96A0481 Rev B 2019 10 01 19 Copyright ADB Safegate All Rights Reserved ...

Страница 26: ...3 3 Utility Remote Enclosure Wiring Diagram RELIANCE C Remote Control Device Installation 20 Copyright ADB Safegate All Rights Reserved ...

Страница 27: ...ver be opened otherwise warranty will be void 3 6 Replacing an RELIANCE Remote 1 In each case inspect the technical condition of the RELIANCE Remote which has to be removed or replaced or the RELIANCE Remote which is to be installed as a replacement device 2 If the old remote is still communicating with the master can be verified with the RELIANCE Configuration software it is recommended to logout...

Страница 28: ...it and verify if the replaced remote connected lamp s are functioning for RGL remotes blinking 8 Follow the change remote procedure as described in 96A0430 RELIANCE Configuration Software User Manual to make the replaced remote operational RELIANCE C Remote Control Device Installation 22 Copyright ADB Safegate All Rights Reserved ...

Страница 29: ...us polling by the RELIANCE Master In the RELIANCE Remote each switching operation for the light is carried out first via an electronic switch and then via a relay blink mode is established with electronic switch only Each RELIANCE Remote monitors the status of the lights connected to it maximum of two lights The monitoring takes place when the light is switched on by default Whether the lamp shoul...

Страница 30: ...ter or receives a failsafe telegram from it it switches the connected light s into a predefined status This status can be parameterized via the RELIANCE PC software as follows On Off Blink flashing Last Commanded State maintain the last operating status The duration of the interval before a communication problem is identified can be configured via the RELIANCE PC software as well The failsafe mode...

Страница 31: ...is circuit Remote name is automatically generated but may be altered to serve your own needs Max 50 characters are allowed Remember that this will be your only lead to identify and locate lights and remotes out of the AGLAS system Serial number is unique for every RELIANCE remote and is required to fill in Pit Name Nr for your own reference only Transfo type transformer type only for your referenc...

Страница 32: ...RELIANCE C Remote Control Device Modes of Operation of an RELIANCE Remote 26 Copyright ADB Safegate All Rights Reserved ...

Страница 33: ...el Remote FAA Style 7 Initial Flash On AGC4370 RELIANCE Dual Channel Remote FAA Style 7 AGC5170 RELIANCE Dual Channel Remote FAA Style 7 Channel A Initial Flash On AGC5470 RELIANCE Utility Remote AGC6110 5 1 Spare Components Table 4 Parts Description Part No RELIANCE Rack mount High voltage Filter Assembly 44A7352 10 GB Industrial Grade Flash Card 105A1155 92 CFM RELIANCE Master Fan Assembly 44A76...

Страница 34: ...RELIANCE C Remote Control Device Parts 28 Copyright ADB Safegate All Rights Reserved ...

Страница 35: ...all When you have an airfield lighting or system control system problem it is our goal to support airfield maintenance staff as quickly as possible To support this effort we ask that you have the following information ready before calling The airport code If not with an airport then company name prefer customer id number Contact phone number and email address Product with part number preferable or...

Страница 36: ... as supplier components and sub contractor operations ADB SAFEGATE offers a recycling program for our products to all customers worldwide whether or not the products were sold within the EU ADB SAFEGATE products and or specific electrical and electronic component parts which are fully removed separated from any customer equipment and returned will be accepted for our recycling program All items re...

Страница 37: ...act Tel 46 0 40 699 17 00 Fax 46 0 40 699 17 30 Email marketing adbsafegate com Internet www adbsafegate com ADB SAFEGATE Airfield Technologies Ltd China ADB SAFEGATE China Unit 603 D Block CAMIC International Convention Center No 3 Hua Jia Di East road ChaoYang district Beijing 100102 P R China Contact Tel 86 10 8476 0106 Fax 86 10 8476 0090 Email china safegate com Internet www adbsafegate com A...

Страница 38: ......

Отзывы: