background image

Ordering Code Notes

Light fixtures with internal remote allows for control and monitoring of the light fixture. Light fixtures with internal remotes

are only available as 1-connector option.

1

 Straight sections, Narrow Beam, < 350 m RVR.

2

 Lead-on/exit, Curved Beam, < 350 m RVR.

3

 Taxiway centerline, Wide Beam, < 350 m RVR.

4

 Taxiway centerline, straight sections, Wide Beam, < 350 m RVR.

5

 TW application includes Intermediate Holding Postion light which is Yellow/Blank with wide beam distribution.

6

 Includes standards NATO, EASA, STAC, TP 312 and MOS 139.

7

 TK application only.

8

 To assure the correct toe-in direction, per color, place the required color option in Side 1 (Left) and/or 2 (Right). Left and

right side determined by standing over fixture while looking towards the taxiway edge in the direction of the curve.

9

 TK CVR application only.

10

 2-cord set option available.

11

 All Style 1 corded fixtures will include a ground lug. All Style 6 and 3-pole corded fixtures will be provided with grounding

screw(s).

12

 Jacketed SO 2 core cable.

13

 Not valid option for unidirectional.

UM-5056, Rev. 1.0.17, 2022/12/08

45

Copyright 

©

 ADB Safegate, All Rights Reserved

Содержание AXON FAA L-852A

Страница 1: ...ch FAA L 852A L L 852B L L 852C L L 852D L L 852J L L 852K L Centerline L 852S L Stop Bar Triple Line Centerline Narrow Wide Curved ICAO Centerline Narrow Wide Curved Runway Entrance Light REL RWSL Enhanced Rapid Exit ICAO Stop Bar User Manual ...

Страница 2: ...UM 5056 Rev 1 0 17 2022 12 08 ...

Страница 3: ...efective Any returns under this guarantee are to be on a transportation charges prepaid basis For products not manufactured by but sold by ADB SAFEGATE warranty is limited to that extended by the original manufacturer This is ADB SAFEGATE s sole guarantee and warranty with respect to the goods there are no express warranties or warranties of fitness for any particular purpose or any implied warran...

Страница 4: ...right to revise this manual from time to time in the contents thereof without obligation of ADB SAFEGATE SWEDEN AB to notify any person of such revision or change Details and values given in this manual are average values and have been compiled with care They are not binding however and ADB SAFEGATE SWEDEN AB disclaims any liability for damages or detriments suffered as a result of reliance on the...

Страница 5: ...ssion Directions 22 5 0 Maintenance 23 5 1 Basic Maintenance Program 24 5 2 Recommended Maintenance Program for optimal Service Life 25 5 2 1 Recommendation 27 5 3 Workshop Maintenance 29 5 3 1 Opening a Light Fixture disconnecting the Bottom Pan from the Top Cover 29 5 3 2 Closing a Light Fixture connecting the Bottom Pan to the Top Cover 30 5 3 3 Replacing the Power Wire Harness 31 5 3 4 Replaci...

Страница 6: ...e Parts Stop Bar Light FAA 65 7 6 Spare Parts Stop Bar Light ICAO 67 7 7 Spare Parts Taxiway Status Takeoff Hold Intersection and Entry Light 70 7 8 Spare Parts Triple Line Taxiway Centerline Light 72 A 0 Winter Operations Snow Plowing Guidelines for inset Lights 73 B 0 INTEROPERABILITY 77 C 0 POWER TABLE 81 D 0 CABLE LOSS 83 E 0 SUPPORT 85 E 1 ADB SAFEGATE Website 85 E 2 Recycling 85 E 2 1 Local ...

Страница 7: ... 38 Figure 19 Converter 2 connector 39 Figure 20 Pressure relief screw removal 39 Figure 21 Taxiway Insets cord set options 53 Figure 22 8 inch left and 12 inch right 54 Figure 23 Top Cover Assemblies 8 inch 55 Figure 24 Top Cover Assemblies 12 inch 55 Figure 25 Bottom Pan gasket 8 inch and 12 inch 55 Figure 26 Bottom Pan assembly 8 inch 55 Figure 27 LED light engines wire harness package of 10 56...

Страница 8: ...e without clearance 75 Figure 37 Fig 4 Snowplow with support wheels 75 Figure 38 Fig 5 Snowplow without support wheels 75 AXON Taxiway Inset Lights 8 inch and 12 inch List of Figures viii Copyright ADB Safegate All Rights Reserved ...

Страница 9: ...1 Suggested Tools and Materials for Installation and Repair 19 Table 2 Interoperability matrix 12 inch 77 Table 3 Interoperability matrix 8 inch 78 UM 5056 Rev 1 0 17 2022 12 08 ix Copyright ADB Safegate All Rights Reserved ...

Страница 10: ...AXON Taxiway Inset Lights 8 inch and 12 inch List of Tables x Copyright ADB Safegate All Rights Reserved ...

Страница 11: ...al injury death or equipment damage ARC Flash may cause blindness severe burns or death WARNING Wear personal protective equipment Failure to observe may result in serious injury WARNING Do not touch Failure to observe this warning may result in personal injury death or equipment damage CAUTION Failure to observe a caution may result in equipment damage ELECTROSTATIC SENSITIVE DEVICES This equipme...

Страница 12: ...devices as specified by applicable safety regulations If safety devices must be removed for installation install them immediately after the work is completed and check them for proper functioning prior to returning power to the circuit Failure to follow this instruction can result in serious injury or equipment damage Additional Reference Materials Important Information IEC International Standards...

Страница 13: ...y devices as specified by applicable safety regulations If safety devices must be removed for installation install them immediately after the work is completed and check them for proper functioning Route electrical wiring along a protected path Make sure they will not be damaged by moving equipment Never operate equipment with a known malfunction Do not attempt to operate or service electrical equ...

Страница 14: ...of errors the ADB SAFEGATE Sales Representative will have information on which gasket goes with which base This information is also provided in the product Data sheets the User Manuals and the Spare Part Lists CAUTION Use of incorrect combination of gaskets bolts and nuts can create severe damages to the product installation and create multiple safety risks To obtain a safe and watertight installa...

Страница 15: ...xiway Centerline TC L 852D L Taxiway Centerline TD L 852J L Taxiway Centerline TJ L 852K L Taxiway Centerline TK L 852S L FAA Stop Bar SB Runway Entrance Light TS ICAO Taxiway Centerline Narrow Beam TC ICAO Taxiway Centerline Curved Beam TK ICAO Taxiway Centerline Enhanced Wide Beam TR ICAO Taxiway Centerline Wide Beam TW ICAO Stop Bar SB Triple Line Taxiway Centerline Light 3C 3N 3W 2 1 How to wo...

Страница 16: ...istration ICAO International Civil Aviation Organization IEC International Electrotechnical Committee ILCMS Individual Light Control and Monitoring System LED Light Emitting Diode NATO North Atlantic Treaty Organization STAC Service Technique de l Aviation Civile France STANAG Standardization Agreement NATO AXON Taxiway Inset Lights 8 inch and 12 inch About this Manual 6 Copyright ADB Safegate All...

Страница 17: ...superior communication interfacing with LINC 360 System NOTICE All our light fixtures are equipped with failed LED detection monitoring as required by FAA Engineering Brief 67 Figure 1 8 and 12 inch fixtures Taxiway Inset 8 2 bolt version 4 bolt not shown Taxiway Inset 8 with Style 1 jacketed cord set Taxiway Inset 8 with Style 6 cord set Taxiway Inset 12 Taxiway Inset 12 with Style 1 jacketed cor...

Страница 18: ...5049 5050 5051 5052 5054 5070 FAA AC 150 5345 46 and the FAA Engineering Brief No 67 X X X ICAO Annex 14 Volume 1 X X EASA CS ADR DSN X X Australia MOS 139 X X Canada TP 312 X X IEC 61827 X X X NATO STANAG 3316 X X STAC PRO STAC SE VIS X X UK CAP 168 X X X X X X X X AXON Taxiway Inset Lights 8 inch and 12 inch Introduction 8 Copyright ADB Safegate All Rights Reserved ...

Страница 19: ...ons 3C 3N 3W ICAO Triple Line Taxiway Centerline Light Applications ICAO SB ICAO Stop bar Applications FAA SB FAA and UFC L 852S L Stop bar Applications RS TS FAA Runway Status Light RWSL Applications L 850T L THL Runway Takeoff Hold Light L 850T L RIL Runway Intersection Light REL Runway Entry Light Note Refer to Runway manual UM 5055 for information on L 850T L UM 5056 Rev 1 0 17 2022 12 08 9 Co...

Страница 20: ...ce with high efficiency and low power consumption Reinforced top cover substantially exceeding standards to improve durability and longevity One single family of fixtures covering all runway taxiway and approach applications IP68 rated enclosure designed for harsh environments all fastenings are stainless steel Reinforced prism available as an option Compatible with existing infrastructure allowin...

Страница 21: ...are sold separately Check what gasket and bolts to order depending on base and installation Operating Conditions Operating temperature 60 C to 55 C 76 F to 131 F Storage temperature 60 C to 80 C 76 F to 176 F Humidity Up to 100 UM 5056 Rev 1 0 17 2022 12 08 11 Copyright ADB Safegate All Rights Reserved ...

Страница 22: ...mension ICAO SB TC TK TR TW 3C 3N 3W FAA SB TA TB TC TD TJ TK 3 kg 6 6 lb 8 in 203 mm 8 in ICAO SB TC TK TR TW 3C 3N 3W FAA SB TA TB TC TD TJ TK 6 8 kg 15 lb 12 in 305 mm 12 in Figure 2 8 inch Taxiway Lights AXON Taxiway Inset Lights 8 inch and 12 inch Introduction 12 Copyright ADB Safegate All Rights Reserved ...

Страница 23: ...Figure 3 12 inch Taxiway Lights UM 5056 Rev 1 0 17 2022 12 08 13 Copyright ADB Safegate All Rights Reserved ...

Страница 24: ...AXON Taxiway Inset Lights 8 inch and 12 inch Introduction 14 Copyright ADB Safegate All Rights Reserved ...

Страница 25: ...ixture where the control and monitoring function is to be activated at a later stage make sure to register product information such as PID SN and position of the light fixture in for example a site documentation table The information is required for remote activation and administration of control and monitoring functionality from a substation 4 2 Tools required The following tools are recommended ...

Страница 26: ...B steel base The 8 dia light is mounted in an 8 to 12 dia snow plow or adapter ring bolted onto the base The 12 fixture is directly mounted without a separate ring The bases are interconnected by means of conduits protecting the cables See FAA AC 150 5340 30 for additional design guidance on deep base cans The series transformer is installed under the light or in a separate pit See data sheet A 05...

Страница 27: ...R TYP HEATSHRINK OPTIONAL GROMMET TRANSFORMER SUPPORT TYP ISOLATION TRANSFORMER SIZE AS REQUIRED L868B SPACER RING S 2 PVC CONDUIT W BELL END 3 4 DRAIN HOLE CENTERED FIXTURE TOP EDGE TO BE 0 1 16 BELOW GRADE L 823 SECONDARY CONNECTOR In order to maintain 0 1 16 below grade per FAA installation tolerance a maximum of 3 spacers may be used per FAA EB 83 latest revision 1 Torque according to FAA EB 8...

Страница 28: ...here it is being used Follow all instructions for installing components and accessories Install all electrical connections in compliance with local and national codes and regulations Use only electrical wire of sufficient gauge and insulation to handle the rated current demand All wiring must meet local and national codes Route electrical wiring along a protected path Make sure it will not be dama...

Страница 29: ...s needed Novagard Silicone Versilube G322L P N 67A0009 used on O ring between top cover and inner pan assembly also may be applied to four nipples of inner pan assembly to install optical assembly 1 or 2 L 830 L 831 isolation transformer 1 Set of fiber brushes 1 Set of socket wrenches 1 2 12 7mm drive 4 3 7 Unpacking the Unit To reduce the possibility of damaging the light assembly unpack the ligh...

Страница 30: ...e in bases installed at an angle relative to the taxiway and use light fixtures with no built in toe in If bases which are installed at an angle are used provided that they are installed correctly straight light fixtures i e with no toe in should be used The following chapter only regards the case where light fixtures are installed in runway taxiway parallel bases i e where no toe in is achieved b...

Страница 31: ...xture correspond to the design requirements such as type color etc When installing a light fixture where the control and monitoring function is to be activated at a later stage make sure to register product information such as PID SN and position of the light fixture in for example a site documentation table The information is required for remote activation and administration of control and monito...

Страница 32: ...op cover in front of the prism Toe in is per the stamped directional arrow Figure 8 Light emission directions Left toe Straight uni directional Right toe Straight bi directional Curved Color Color code W Y G or F R B White Yellow Green Red Blue AXON Taxiway Inset Lights 8 inch and 12 inch Installation 22 Copyright ADB Safegate All Rights Reserved ...

Страница 33: ...DB SAFEGATE for assistance CAUTION Use of incorrect combination of gaskets bolts and nuts can create severe damages to the product installation and create multiple safety risks You need to know what base the light fixture will be installed in in order to chose the correct gasket bolts and nuts Failure to follow these cautions can result in equipment damage or aircraft FOD For more information see ...

Страница 34: ...m base and check for water ingress and corrosion Replace gasket between light fixture and base After snow removal Check for damaged light fixtures Any damaged light fixtures should be replaced and brought in and properly investigated and repaired A daily function check is referred to in the document ICAO Airport Services Manual Part 9 Airport Maintenance Practice and FAA AC 150 5340 26A Maintenanc...

Страница 35: ...s highly dependent on the location where it is installed on an airfield Three different areas have been defined by color categorization that are exposed to different degree of mechanical impact These three categories are used as a basis for the recommendation of inspections as well as for the expected lifetime of a light fixture RED Touch Down Area defined as 6m either side of the runway centerlin...

Страница 36: ... the cost of the repair You can also increase the service life of a light fixture by rotating the installation location of light fixtures in critical areas Regular inspections and well defined preventive maintenance planning will help to reduce the overall maintenance cost and reduce downtime from reactive maintenance tasks Figure 9 Preventive Maintenance AXON Taxiway Inset Lights 8 inch and 12 in...

Страница 37: ...on on light fixture and base especially around the mating surfaces For deep base installation L 868 check for water ingress if more than 6 inches please have it removed Inspect light and base for damage Replace gasket between light fixture and base NOTICE We recommend any maintenance work that requires the light fixture to be opened to be done back in the dedicated maintenance area We recommend th...

Страница 38: ... 100k Service Life 15 years RED Zone ATM 100k 200K Service Life 10 years RED Zone ATM 200k Service Life 7 years Note Contact to your local sales representative if you have any questions or would require some assistance to go through local conditions and see how we can help establish a well defined maintenance planning to optimize the expected service life of your investment AXON Taxiway Inset Ligh...

Страница 39: ...iver Flat head screwdriver 1 Place the light fixture upside down 2 Loosen the Pressure Release Screw 3 Unscrew the fixation screws Make sure you dispose the old screws and use new screws 4 Lift the Bottom Pan without damaging the connecting wires CAUTION Make sure you do not damage the cables when opening the light fixture 5 Disconnect the wires a Pull carefully to disconnect the wires between the...

Страница 40: ...wires a Press carefully to connect the wires lead in from the light engine on the converter b Press carefully to connect the wires lead in from the light engine on the converter if the heater kit is in place 4 Put the Top Cover onto the Bottom Pan Make sure the poke yoke alignment pin is in the placed correctly Important Do not pinch the wires or the gasket 5 Put the light fixture on a surface wit...

Страница 41: ...n the light Note Refer to the Opening a Light Fixture disconnecting the Bottom Pan from the Top Cover section 2 Remove the LED brackets 3 pieces M5 screws per bracket to access the connector of the LED wire Make sure you dispose the old screws and use new screws Figure 12 LED bracket removal 3 Disconnect the old wire harnesses Make sure you dispose the old wire harnesses and use new wire harnesses...

Страница 42: ...rews at 26 in lbs 3 Nm 6 Close the light Note Refer to the Closing a Light Fixture connecting the Bottom Pan to the Top Cover section AXON Taxiway Inset Lights 8 inch and 12 inch Maintenance 32 Copyright ADB Safegate All Rights Reserved ...

Страница 43: ...s 4 Use new screws to attach the light engine in star pattern at 31 inch pound 3 5 Nm 5 Retorque the screws in star pattern at 31 inch pound 3 5 Nm 6 Close the light Note Refer to the Closing a Light Fixture connecting the Bottom Pan to the Top Cover section 5 3 5 Replacing the Prism and its Gasket Tools to be used Screwdriver or variable speed Torque drill driver with T25 bit NOTICE Do not use an...

Страница 44: ... sure the prism is fully flush on the outside and the prism surfaces are clean without grease or dirt 6 Mount the light engine 7 Use new screws to attach the light engine in star pattern at 31 inch pound 3 5 Nm Figure 14 Sequence 8 Retorque the screws in star pattern at 31 inch pound 3 5 Nm 9 Close the light Note Refer to the Closing a Light Fixture connecting the Bottom Pan to the Top Cover secti...

Страница 45: ...nch pound 3 5 Nm 6 Retorque the screws in star pattern at 31 inch pound 3 5 Nm 7 Close the light Note Refer to the Closing a Light Fixture connecting the Bottom Pan to the Top Cover section 5 3 7 Replacing the Bottom Cover Assembly Tools to be used Screwdriver T25 bit Flat head screwdriver 1 Open the light Note Refer to the Opening a Light Fixture disconnecting the Bottom Pan from the Top Cover se...

Страница 46: ...cable release opening 3 Unscrew the Strain relief Bolt and its plate Make sure you dispose the old Strain relief Bolt and its plate and use the new material 4 Unscrew the cable clamp Make sure you dispose the old bolt washer and lock washer and use the new material 5 Remove the secondary cable Make sure you dispose the old secondary cable and use the new secondary cable 6 Replacement a Pull the se...

Страница 47: ... Bottom Pan from the Top Cover section 2 Disconnect the cable a Disconnect the secondary cable from the converter by placing a small flat head screwdriver into the opening located at the other side of the secondary wire and b Release the cable by prying the screwdriver on the cable release opening 3 Unscrew the Strain relief Bolt and its plate Make sure you dispose the old Strain relief Bolt and i...

Страница 48: ...g screwdriver from the opening 9 Close the light Note Refer to the Closing a Light Fixture connecting the Bottom Pan to the Top Cover section 5 3 10 Resetting the Fail open Converter Parts Fuse resistor spare part kit 20210209 20 pcs Info Converter with 1 connector have 2 fuse resistors Converter with 2 connectors have 4 fuse resistors Reset replace the fuse resistors 1 Disconnect and disassemble ...

Страница 49: ... Dispose the old fuse resistor 5 Place the legs of the new fuse resistors in the sockets 6 Assemble the light fixture and perform a functional test 5 3 11 Checking the Light Fixture for Water tightness Tools to be used Flat head screwdriver For water tight testing pressure test fitting tool to be used 44A6104 A Execute the following procedure to test for leaks 1 Remove the Pressure relief Screw Re...

Страница 50: ...t of the light If air leaks out of the light fixture between the Bottom Cover and the top plate or between the prism and top plate or watertightness valve and top plate the light fixture is not watertight and must be repaired Release the air from the light Disassemble the light fixture and re check the mating surfaces and gaskets Assemble the light fixture and perform the water tightness test agai...

Страница 51: ...6 0 Ordering Codes UM 5056 Rev 1 0 17 2022 12 08 41 Copyright ADB Safegate All Rights Reserved ...

Страница 52: ...ectional 2 Bidirectional Toe in N None TA TB TC TD applications C Curved TJ TK applications Color Side 1 Left F F Green Y Yellow R Red6 8 W White6 8 N None7 Color Side 2 Right F F Green Y Yellow R Red6 8 W White6 8 N None Power and Monitoring S 2 8 A 6 6 A Non monitored power only3 M 2 8 A 6 6 A Fail open monitoring3 R 2 8 A 6 6 A EQ integrated LINC 360 Cable and connector6 1 1 x Style 6 2 pole pl...

Страница 53: ... Cable and Connector 4All Style 1 corded fixtures will include a ground lug All Style 6 and 3 pole corded fixtures will be provided with grounding screw s 5 Only available in Digit 13 options S and M and Bi directional configuration 6 Color used with L 852D L for medium intensity runway edge and threshold applications 7 L 852J K L unidirectional applications only 8 Not ETL submitted UM 5056 Rev 1 ...

Страница 54: ... MOS F F Green ICAO STD Y Yellow B Blue N None9 Color Side 2 Right G G Green ICAO and MOS F F Green ICAO STD Y Yellow B Blue N None Power and Monitoring S 2 8 A 6 6 A non monitored power only10 M 2 8 A 6 6 A Fail open monitoring10 R 2 8 A 6 6 A EQ integrated LINC 360 Cable and connector 1 1 x Style 6 2 pole plug 2 individual wires11 2 1 x Style 1 2 pole plug11 12 3 2 x Style 6 2 pole plug 2 indivi...

Страница 55: ...m distribution 6 Includes standards NATO EASA STAC TP 312 and MOS 139 7 TK application only 8 To assure the correct toe in direction per color place the required color option in Side 1 Left and or 2 Right Left and right side determined by standing over fixture while looking towards the taxiway edge in the direction of the curve 9 TK CVR application only 10 2 cord set option available 11 All Style ...

Страница 56: ... Right F F Green B Blue A Amber N None Power and Monitoring S 2 8 A 6 6 A Non Monitored Power Only5 M 2 8 A 6 6 A Fail Open monitoring5 R 2 8 A 6 6 A ILCMS integrated OFDM EQ Cable and Connector 1 1 x Style 6 2 pole plug 2 individual wires6 2 1 x Style 1 2 pole plug 2 jacketed SO 2 core cable6 3 2 x Style 6 2 pole plug 2 individual wires6 7 4 2 x Style 1 2 pole plug 2 jacketed SO 2 core cable6 7 8...

Страница 57: ... cord set option available 6All Style 1 corded fixtures will include a ground lug All Style 6 and 3 pole corded fixtures will be provided with grounding screw s 7Only available in Digit 13 options S and M and bi directional configuration 88 SO cord set option is not compatible with shallow bases UM 5056 Rev 1 0 17 2022 12 08 47 Copyright ADB Safegate All Rights Reserved ...

Страница 58: ...ower and Monitoring S 2 8 A 6 6 A non monitored power only3 M 2 8 A 6 6 A Fail open monitoring3 R 2 8 A 6 6 A EQ integrated LINC 360 Cable and connector 1 1 x Style 6 2 pole plug 2 individual wires4 2 1 x Style 1 2 pole plug jacketed SO 2 core cable4 3 2 x Style 6 2 pole plug 2 individual wires4 5 6 4 2 x Style 1 2 pole plug jacketed SO 2 core cable4 5 6 5 1 x flat 3 pole plug 3 individual wires4 ...

Страница 59: ...nd MOS 139 2 Curved application only 3 2 Cord set option available for bidirectional fixtures not EQ 4 All Style 1 corded fixtures will include a ground lug All Style 6 and 3 pole corded fixtures will be provided with grounding screw s 5 Only available in Digit 13 options S and M and bi directional configuration 6 Not valid option for unidirectional UM 5056 Rev 1 0 17 2022 12 08 49 Copyright ADB S...

Страница 60: ...nd Monitoring S 2 8 A 6 6 A non monitored power only M 2 8 A 6 6 A Fail open monitoring R 2 8A 6 6 A EQ integrated LINC 360 Cable and connector2 1 1 x Style 6 2 pole plug 2 individual wires4 2 1 x Style 1 2 pole plug jacketed SO 2 core cable4 Options 0 None 1 Arctic Kit Version 1 Version 1 Ordering Code Notes 1 Includes TP 312 2 Required for FAA when using AIP funds 3 Not ETL submitted 4 All Style...

Страница 61: ... 4 bolt2 Prism S Standard prism R Reinforced prism2 Beam Orientation 1 Unidirectional Toe in N None Color Side 1 R Red Color Side 2 N Not applicable Power and Monitoring R 2 8 A 6 6 A EQ integrated LINC 360 Cable and connector1 1 1 x Style 6 2 pole plug 2 individual Wires 2 1 x Style 1 2 pole plug jacketed SO 2 core cable Options 0 None 1 Arctic Kit Version Control 1 Version 1 Ordering Code Notes ...

Страница 62: ...AXON Taxiway Inset Lights 8 inch and 12 inch Ordering Codes 52 Copyright ADB Safegate All Rights Reserved ...

Страница 63: ...ssistance 7 1 Versions and Exploded View Versions 8 inch and 12 inch Insets Figure 21 Taxiway Insets cord set options Taxiway Inset 8 2 bolt version 4 bolt not shown Taxiway Inset 8 with Style 1 jacketed cord set Taxiway Inset 8 with Style 6 cord set Taxiway Inset 12 Taxiway Inset 12 with Style 1 jacketed cord set Taxiway Inset 12 with Style 6 cord set UM 5056 Rev 1 0 17 2022 12 08 53 Copyright AD...

Страница 64: ...Engine Assembly 8 inch and 12 inch no Arctic Kit SP AS00089 XXX B2 not shown Light Engine Assembly 8 inch and 12 inch with Arctic Kit SP AS00137 XXX C Bottom Pan Assembly 8 inch and 12 inch SP AS00021 XXX Note Full assembly numbers are listed in the spare part tables per application starting from page 60 in the user manual AXON Taxiway Inset Lights 8 inch and 12 inch Spare Parts 54 Copyright ADB S...

Страница 65: ... Bottom Pan Mounting Screws 4 pcs shown 12 inch Top Cover Socket Seal Prism Figure 25 Bottom Pan gasket 8 inch and 12 inch Bottom Pan package of 10 pcs gasket available options 8 inch 12 inch for Taxiway applications only 8 inch 12 inch O ring 8 inch O ring gaskets are used Figure 26 Bottom Pan assembly 8 inch 8 inch Taxiway Bottom Pan assembly compatible with both 8 inch and 12 inch top covers UM...

Страница 66: ...res Taxiway 2 replacement prism package of pcs available options Standard Reinforced Sapphire coated Figure 30 Ground lugs package of 5 Figure 31 Style 1 Cord Set Cable Clamp package of 5 Figure 32 Mounting screws package of 100 AXON Taxiway Inset Lights 8 inch and 12 inch Spare Parts 56 Copyright ADB Safegate All Rights Reserved ...

Страница 67: ...ease screws package of 5 Note Pressure release screw O ring is to be replaced with new O ring prior to re installation of the pressure relief screw UM 5056 Rev 1 0 17 2022 12 08 57 Copyright ADB Safegate All Rights Reserved ...

Страница 68: ...1 SP AS00135 S2R 4 bolt unidirectional side 1 curved standard prism 1 1 SP AS00135 C2S 4 bolt unidirectional side 1 curved reinforced prism 1 1 SP AS00135 C2R 4 bolt unidirectional side 2 curved standard prism 1 1 SP AS00135 C4S 4 bolt unidirectional side 2 curved reinforced prism 1 1 SP AS00135 C4R 4 bolt bidirectional straight standard prism 1 1 SP AS00135 S6S 4 bolt bidirectional straight reinf...

Страница 69: ...tored S BAP or EQ R 1 or 2 1 SP AS00137 0YY E F green for L 852D L non monitored S BAP or EQ R 1 or 2 1 SP AS00137 DFF E white for L 852D L non monitored S BAP or EQ R 1 or 2 1 SP AS00137 DWW E yellow for L 852D L non monitored S BAP or EQ R 1 or 2 1 SP AS00137 DYY E F green curved for L 852K L non monitored S BAP or EQ R 1 or 2 1 SP AS00137 CFN E yellow curved for L 852K L non monitored S BAP or ...

Страница 70: ...t 1 1 SP AS00021 M13 monitored converter style 1 SJO jacketed cord set 1 1 SP AS00021 M1J monitored converter 2 con style 6 cord sets 1 1 SP AS00021 M23 monitored converter 2 con style 1 SJO jacketed cord sets 1 1 SP AS00021 M2J EQ converter style 6 cord set 1 1 SP AS00021 R13 EQ converter style 1 SJO jacketed cord set 1 1 SP AS00021 R1J Buy American Preference non monitored converter style 6 cord...

Страница 71: ...r supply to light engine 1 or 2 10 SP EW00070 150 01 Wire harness power supply to heater 1 or 2 10 SP EW00069 150 01 Fuse Quantity per spare part code fitting spare part Fuse resistors only for fixtures with monitoring M 1 or 2 20 6132 00 250 Note All screws for fastening are included Component availability or design may be subject to change due to unforeseen circumstances This document is subject...

Страница 72: ...ting spare part unidirectional straight standard prism 1 1 SP AS00136 S1S unidirectional straight reinforced prism 1 1 SP AS00136 S1R unidirectional side 1 curved standard prism 1 1 SP AS00136 C1S unidirectional side 1 curved reinforced prism 1 1 SP AS00136 C1R unidirectional side 2 curved standard prism 1 1 SP AS00136 C2S unidirectional side 2 curved reinforced prism 1 1 SP AS00136 C2R bidirectio...

Страница 73: ...apid exit non monitored S or monitored M 1 or 2 1 SP AS00137 WYY TRF F green curved non monitored S or monitored M 1 or 2 1 SP AS00137 CFN F yellow curved non monitored S or monitored M 1 or 2 1 SP AS00137 CYN F F green narrow non monitored S or monitored M 1 or 2 1 SP AS00137 NFN F yellow narrow non monitored S or monitored M 1 or 2 1 SP AS00137 NYN F C Bottom Cover Assemblies Quantity per spare ...

Страница 74: ...ty per spare part code fitting spare part Pressure release screw with o ring 1 5 SP MF00090 000 01 Gasket 8 Bottom pan 1 10 SP MS00005 000 01 Screws 8 Bottom pan 100 SP MFPM5PT 714 01 Screws light engine assembly mounting 100 SP MFPM4PT 710 01 Wire harness 8 inch and 12 inch Quantity per spare part code fitting spare part Wire harness power supply to light engine 1 or 2 10 SP EW00070 150 01 Wire h...

Страница 75: ... 1 1 SP AS00136 S1R B1 B2 Light Engine Assembly 8 inch and 12 inch Quantity per spare part code fitting spare part red for L 852S L FAA stop bar and REL without heater 1 1 SP AS00089 SRR red for L 852S L FAA stop bar and REL non monitored S non BAP or monitored M with heater 1 1 SP AS00137 SRR F red for L 852S L FAA stop bar and REL non monitored S BAP or EQ R with heater 1 1 SP AS00137 SRR E C Bo...

Страница 76: ...d gaskets 8 inch Quantity per spare part code fitting spare part Pressure release screw with o ring 1 5 SP MF00090 000 01 Gasket 8 Bottom pan 1 10 SP MS00005 000 01 Screws 8 Bottom pan 100 SP MFPM5PT 714 01 Screws light engine assembly mounting 100 SP MFPM4PT 710 01 Wire harness 8 inch and 12 inch Quantity per spare part code fitting spare part Wire harness power supply to light engine 1 or 2 10 S...

Страница 77: ...forced prism 1 1 SP AS00135 S5R bidirectional curved standard prism 1 1 SP AS00135 C5S bidirectional curved reinforced prism 1 1 SP AS00135 C5R A2 Top Cover Assemblies 12 inch Quantity per spare part code fitting spare part unidirectional straight standard prism 1 1 SP AS00136 S1S unidirectional straight reinforced prism 1 1 SP AS00136 S1R unidirectional side 1 curved standard prism 1 1 SP AS00136...

Страница 78: ...r style 1 SJO jacketed cord set 1 1 SP AS00021 L1J non monitored converter 2 con style 6 cord sets 1 1 SP AS00021 L23 non monitored converter 2 con 3 pole cord sets 1 1 SP AS00021 L2F non monitored converter 2 con style 1 SJO jacketed cord sets 1 1 SP AS00021 L2J monitored converter style 6 cord set 1 1 SP AS00021 M13 monitored converter 3 pole cord set 1 1 SP AS00021 M1F monitored converter style...

Страница 79: ... Bottom pan 1 10 SP MS00005 000 01 Screws 8 Bottom pan 100 SP MFPM5PT 714 01 Screws light engine assembly mounting 100 SP MFPM4PT 710 01 Wire harness Quantity per spare part code fitting spare part Wire harness power supply to light engine 1 or 2 10 SP EW00070 150 01 Wire harness power supply to heater 1 or 2 10 SP EW00069 150 01 Fuse Quantity per spare part code fitting spare part Fuse resistors ...

Страница 80: ... 1 1 SP AS00136 S1S unidirectional straight reinforced prism 1 1 SP AS00136 S1R B1 B2 Light Engine Assembly 8 inch and 12 inch Quantity per spare part code fitting spare part red for L 852S L FAA stop bar and REL EQ or monitored no heater 1 1 SP AS00089 SRR red for L 852S L FAA stop bar and REL monitored M with heater 1 1 SP AS00137 SRR F red for L 852S L FAA stop bar and REL EQ R with heater 1 1 ...

Страница 81: ... Bottom pan 100 SP MFPM5PT 714 01 Screws light engine assembly mounting 100 SP MFPM4PT 710 01 Wire harness Quantity per spare part code fitting spare part Wire harness power supply to light engine 1 or 2 10 SP EW00070 150 01 Wire harness power supply to heater 1 or 2 10 SP EW00069 150 01 Fuse Quantity per spare part code fitting spare part Fuse resistors only for fixtures with monitoring M 1 or 2 ...

Страница 82: ...7 8 Spare Parts Triple Line Taxiway Centerline Light AXON Taxiway Inset Lights 8 inch and 12 inch Spare Parts 72 Copyright ADB Safegate All Rights Reserved ...

Страница 83: ...ent and will contaminate the light outlet ADB Safegate light fixtures are tested to work with common chemicals on the airfield such as Potassium Acetate Potassium Formate Sodium Acetate Sodium Formate The pH value of such chemical solutions should not exceed pH 11 to protect the light fixtures from corrosion and other damage Winter Operation Training Most airports conduct dry run winter operations...

Страница 84: ...is important that the snowplows are equipped with plastic cutting edges The plastic cutting edge should be made of polyurethane rubber or material of similar consistence and characteristics The plastic cutting edge should consist of a minimum of plastic segments accurately aligned and free of steps between them Figure 34 Fig 1 Snowplow blade with well aligned segments It is not recommended to have...

Страница 85: ...vement may damage in pavement lights Figure 36 Fig 3 Snowplow blade without clearance Use casters shoes and or support wheels on plow moldboards and on the front of rotary plows to stabilize the plow blade and to support maintaining a pre defined clearance between the snowplow cutting edge and the pavement during operation Figure 37 Fig 4 Snowplow with support wheels Figure 38 Fig 5 Snowplow witho...

Страница 86: ...will faster scratch and wear out especially the glass prisms of in pavement lights negatively impacting the light photometry When possible avoid using steel bristles or run rotary brooms with a mix of steel and poly bristles e g 1 3 to reduce the wear and damage to in pavement lights Check for adequate contact pressure evaluate during pre winter dry run tests Check for bristle wear according to ma...

Страница 87: ...g washer max height 2mm 1411 20 500 Self locking nut kit 12 in M10 H 100 35 Nm Thorn 12 in 150 mm Thorn 12 in 100 mm O ring D259 3 5 7 7080 90 650 SP 013114 10pc SP 013115 100pc 1411 20 482 Metric screw kit 12 in M10 25 mm 40 Nm locking washer max height 2mm only with non roll over lights 1411 20 500 Metric nut kit 12 in M10 H 100 35 Nm L 868 deep can O ring D259 3 5 7 7080 90 650 SP 013114 10pc S...

Страница 88: ...ut kit 8 H100 21 Nm 1 ADB 8 in HPI Grey O Ring SGE48001264 SGE SP24522 10 pc SGE SP24525 100 pc 1411 20 522 Metric screw kit 25 mm 21 Nm Loctite 2701 or 638 1411 20 430 Self locking nut kit H100 21 Nm 1 Adapter ring SG Thorn ID 8 in 12 in Red O Ring SGE48001298 SGE SP24523 10 pc SGE SP24526 100 pc 1411 20 522 Metric screw kit 25 mm 40 Nm Locking washer max height 2mm 1411 20 430 Self locking nut k...

Страница 89: ...IDM 6494 Base 8 13X Base MK2 8 Base 8 13X HPI ERNI EE08 Eurobase UM 5056 Rev 1 0 17 2022 12 08 79 Copyright ADB Safegate All Rights Reserved ...

Страница 90: ...AXON Taxiway Inset Lights 8 inch and 12 inch INTEROPERABILITY 80 Copyright ADB Safegate All Rights Reserved ...

Страница 91: ...nly LED Taxiway Centerline ICAO TC TK TC TR TW ICAO 8 and 12 inch without Arctic Kit Fixture type 1 cord set 1 Fixture load Isolation transformer CCR load Wattage Load Taxiway Centerline Wide bidirectional 13 5 VA 15 W 7 6 VA 21 1 VA Taxiway Centerline Curved bidirectional 12 4 VA 15 W 7 6 VA 20 VA Taxiway Centerline Narrow unidirectional 7 8 VA 15 W 10 1 VA 18 VA Fixture type 2 cord sets 1 Fixtur...

Страница 92: ...AXON Taxiway Inset Lights 8 inch and 12 inch POWER TABLE 82 Copyright ADB Safegate All Rights Reserved ...

Страница 93: ...te Secondary cable for a 2 5 mm2 Cu wire 2 conductors 0 6 W m Secondary cable for a 4 mm2 Cu wire 2 conductors 0 4 W m Primary cable for a 6 mm2 Cu wire 1 conductor 0 12 W m The cable between the isolation transformer and the lamp adds losses that cannot be ignored when dimensioning the circuits and selecting rating for secondary transformers and regulators WARNING Cable lengths should not exceed ...

Страница 94: ...AXON Taxiway Inset Lights 8 inch and 12 inch CABLE LOSS 84 Copyright ADB Safegate All Rights Reserved ...

Страница 95: ...irport then company name prefer customer id number Contact phone number and email address Product with part number preferable or product number Have you reviewed the product s manual and troubleshooting guide Do you have a True RMS meter available and any other necessary tools Be located with the product ready to troubleshoot Note For more information see www adbsafegate com or contact ADB SAFEGAT...

Страница 96: ...hich are fully removed separated from any customer equipment and returned will be accepted for our recycling program All items returned must be clearly labeled as follows For ROHS WEEE Recycling Sender contact information Name Business Address Phone number Main Unit Serial Number ADB SAFEGATE will continue to monitor and update according for any future requirements for EU directives as and when EU...

Страница 97: ...n Contact Tel 46 0 40 699 17 00 Fax 46 0 40 699 17 30 Email marketing adbsafegate com Internet www adbsafegate com ADB SAFEGATE China ADB SAFEGATE Airfield Technologies Ltd China Unit 603 D Block CAMIC International Convention Center No 3 Hua Jia Di East road ChaoYang district Beijing 100102 P R China Contact Tel 86 10 8476 0106 Fax 86 10 8476 0090 Email china safegate com Internet www adbsafegate...

Страница 98: ......

Отзывы: