4
2 Product Introduction
2.1.
General Characteristics
2.1.1 True online architecture continuously supplies in your critical device with a
stable, regulated, transient-free pure sine wave AC Power.
2.1.2 20KHz PWM sine-wave topology yields an excellent overall performance.
The high crest factor of the inverter handles all high-inrush current loads
without a need to upgrade the power rating.
2.1.3 Multi-functional LCD/LED panel may display various status of the UPS.
The LED display may show UPS working status, Utility Status and UPS
Abnormal status, in the mean while, the LCD display may show Input/Output
Voltage, Frequency, Load Status, Inner cabinet temperature, and Abnormal
Phenomenon.
2.1.4 To protect the unit from overloading, it automatically switches to bypass
mode in 160seconds, app 40msec if loading is at 105%~ 150% of rating and
in case of overloading at 150% of rating, it switches to bypass mode
immediately. It will automatically switch back to inverter mode once overload
condition ceases.
2.1.5 Should the output becomes short-circuit, the UPS holds the system and
cuts the output automatically till the short circuit situation is removed
manually.
2.1.6 Should the unit become overheated, the internal thermal Switch will detect
the heat and switch to bypass mode and vice versa.
2.1.7 Fully digitalized control circuit built in the UPS may upgrade the
functionality Of the UPS as well as reach a high-level protection of the UPS.
Through powerful Communication capability built, it enhances its ability for
remote control and monitoring easily.
2.1.8 Maintenance-free sealed-type battery minimizes after-sales service.
2.1.9 Providing four different working modes, such as Normal, ECO, CF50 and
CF60, it may widely be used in a variety of applications.
2.1.10 DC-start function makes sure of the start-up of UPS during power
outages.
2.1.11 Revolutionary battery management circuit analyzes battery discharging
status to adjust battery cut-off point and extend the life of batteries.
2.1.12 Intelligent temperature-controlled fan may not only extend the life of the
fan, but also reduce annoying noise because of sudden fan spin. It remains
your office quiet and comfortable as usual.
2.1.13 When UPS is out of order, you may read out the possible fault reason
from the LCD screen directly, which may reduce down unnecessary repair
task a lot.
2.1.14 When UPS is out of order, you may read out the possible fault reason
from the LCD screen directly, which may reduce down unnecessary repair
task a lot.
5
2.1.15 In case the UPS is out of order, Fault status will be shown on the LCD
screen
2.1.16
When the UPS is operated under CF50 or CF60 mode, the
recommended
load connected shall be 75% of rated capacity if the input
voltage is 176~280Vac and 50% of the rated capacity if the input voltage is
160~280Vac
2.2.
Symbols on the LCD Display Panel
Item Symbol
Description
1
LINE
Utility or Bypass Source
2
Battery Low
3
Battery Abnormal
4
UPS Overloading
5
UPS Working in specified mode*
6
A Blackout Transfer occurred in UPS Output
7
Bypass Input Abnormal, UPS fails to transfer
to bypass, Bypass Abnormal at ECO mode
8
Utility Input Abnormal
9
OFF
UPS Shutoff
10
LINE OFF
UPS Abnormal Lock
11
UPS Flow Chart
12
4 Digits Measurement Display