Modbus
Register
Loop 0
Modbus
Register
Loop 1
Code
Read/
Write
Decimal
Place
Descriptions
41108 41364
Alarm L limit
(PV Source 1)
Read /
Write
3
Alarm Low Limit Value for PV Source 1
(>RL && > Alarm LL)
41110 41366
Alarm Dead
Band %
(PV Source 1)
Read /
Write
3
Dead band % for PV Source 1
0<(Input Value/1000)%<10 %
41112 41368
Alarm Status
(PV Source 1)
Read
Only
0
Alarm Status for PV Source 1
0
:
Normal
、
1:HH
、
2
:
H
、
3:L
、
4:LL
。
41114 41370
Alarm HH Limit
(PV Source 2)
Read /
Write
3
Alarm High High Limit Value for PV Source 2
(< RH)
41116 41372
Alarm H Limit
(PV Source 2)
Read /
Write
3
Alarm High Limit Value for PV Source 2
(< RH && < Alarm HH)
41118 41374
Alarm LL Limit
(PV Source 2)
Read /
Write
3
Alarm Low Low Limit Value for PV Source 2
(> RL)
41120 41376
Alarm L limit
(PV Source 2)
Read /
Write
3
Alarm Low Limit Value for PV Source 2
(>RL && > Alarm LL)
41122 41378
Alarm Dead
Band %
(PV Source 2)
Read /
Write
3
Dead band % for PV Source 2
0<(Input Value/1000)%<10 %
41124 41380
Alarm Status
(PV Source 2)
Read
Only
0
Alarm Status for PV Source 2
0
:
Normal
、
1:HH
、
2
:
H
、
3:L
、
4:LL
。
41126 41382
Not
used
N/A N/A Not
used
41128 41384
Not
used
N/A N/A Not
used
41130 41386
Not
used
N/A N/A Not
used
41132 41388
Not
used
N/A N/A Not
used
41134 41390
Not
used
N/A N/A Not
used
41136 41392
Not
used
N/A N/A Not
used
41138 41394
MV Output High
Limit
Read /
Write
3
MV Output High Limit
(<MV RH)
41140 41396
MV Output Low
Limit
Read /
Write
3
MV Output Low Limit
(>MV RL)
41142 41398
MV Output
Alarm Status
Read
Only
0
MV Output Alarm Status
0
:
Normal
、
1:H
、
2
:
L
41144 41400
MV Emergency
Value
Read /
Write
3
MV output value while emergency shutdown DI
being active
41146 41402
Open wire flag
(PV Source 1)
Read
Only
0
0
:
Normal
1
:
Open wire
5