Modbus
Register
Loop 0
Modbus
Register
Loop 1
Code
Read/
Write
Decimal
Place
Descriptions
41080 41336
Control loop
period setting
(msec)
(PV Source 1)
Read /
Write
0
<=0 : Loop empty
>0 : Loop controlling
41082 41338
Control loop
period setting
(msec)
(PV Source 2)
Read /
Write
0
<=0 : Loop empty
>0 : Loop controlling
41084 41340
Control loop
period setting
(msec)
(PID)
Read
Only
0
<=0 : Loop empty
>0 : Loop controlling
41086 41342
Count down
value of control
loop period
Read
Only
0
Counting value<=0 then calculating PID loop
41088 41344
Previous Loop
Open/Close
status
Read
Only
0
Record the last Loop manual or auto mode for Loop
Initial set
。
41090 41346
NSEC
Read
Only
0
Calculating the newest Loop interval as nsec
41092 41348
OLD
NSEC
Read
Only
0
Calculating the previous Loop interval as old nsec
41094 41350
Power recovery
action setting
Read /
Write
0
0: maintaining the previous MV output and keep
PID open
1: Setting the previous MV output as initial value
and keeping PID close
2: PID open, using MV initial value as MV output
41096
41352 MV Initial Value
Read /
Write
3
MV initial value for power recovery action
41098
41354 Last DI State
Read
Only
0
Previous Scan DI State (reference for control
program)
41100
41356 Last DO State
Read
Only
0
Previous Scan DO State (reference for control
program)
41102 41358
Alarm HH Limit
(PV Source 1)
Read /
Write
3
Alarm High High Limit Value for PV Source 1
(< RH)
41104 41360
Alarm H Limit
(PV Source 1)
Read /
Write
3
Alarm High Limit Value for PV Source 1
(< RH && < Alarm HH)
41106 41362
Alarm LL Limit
(PV Source 1)
Read /
Write
3
Alarm Low Low Limit Value for PV Source 1
(> RL)