Appendix B
Input range code mapping
Range code
Range value
0x07 4~20
mA
0x08 -10~10
V
0x0D 0~20
mA
Output range code mapping
Range code
Range value
0x00
0 ~ 20 mA
0x01
4 ~ 20 mA
0x02
0 ~ 10 V
Appendix C
PID Parameters Table for Modbus address
:
Modbus
Register
Loop 0
Modbus
Register
Loop 1
Code
Read/
Write
Decimal
Place
Descriptions
41000 41256
Open/Close
Mode
Read /
Write
0
Enable/Disable PID loop function
0:Free mode -- no PID control,
ADAM-6022 will be a
pure I/O module
1:PID mode – enable PID loop function
2:Manual mode – manual control analog
output
41002 41258
PID
Mode
Read /
Write
0
PID Mode Selection
0:Standard PID Calculation Mode
1:Differential First Mode
41004 41260
PV
Mode
Read /
Write
0
0:Select PV Source 1 as “PV”
(PV-0 for Loop-0; PV-3 for Loop-1)
1:Select PV Source 2 as “PV”
(PV-1 for Loop-0; PV-4 for Loop1)
41006
41262 Not used
N/A
N/A
Not used
41008 41264
PV Source 1
bare data
Read
Only
3
PV Source 1 bare value
(PV-0 for Loop-0; PV-3 for Loop-1)
41010 41266
PV Source 2
bare data
Read
Only
3
PV Source 2 bare value
(PV-1 for Loop-0; PV-4 for Loop1)
1