Cold water
Hot water
CONNECTION
Essential instructions for the safety of persons and the environment
•
Refer to the safety instructions for the installation. Failure to comply with these
instructions can result in damages to the system, severe injuries or death.
•
Hot water can burn! ACV recommends using a pre-set thermostatic mixing
valve in order to provide hot water at a maximum of 60°C.
Essential instructions for the correct operation of the system
•
The filling circuit of the DHW tank must be equipped with a safety group,
comprised at least of a stop valve, a check valve, a safety valve set at 7 bar, and
possibly, an expansion vessel of the appropriate size. Make sure that the circuit
between the tank and the safety valve is always open.
•
The third DHW tank connection, if any, can be used for the auxiliary DHW loop. If the
connection is not used, replace the protective plug by a brass plug of the appropriate
size.
General remarks
•
In certain countries the domestic kits must be approved.
•
The circuit illustrations are basic principle diagrams only.
CONNECTION TO THE DHW CIRCUIT (Typical floor installation)
Key
1. Filling valve
2. Pressure reducing valve (set at 4.5 bar)
3. Check valve
4. Expansion vessel
5. Safety valve (set at 7 bar)
6. Drain valve
7. Hot water outlet
8. Pressure gauge
9. Grounding
10. Stop valve
11. Thermostatic mixing valve
Smart SL : A1007846 - 661Y3100 • C
Installation
If there is a risk of low pressure in
the hot water circuit (installation of
the tank on the roof of a building),
it is essential to install a vacuum
breaker device onto the cold water
supply.
19
EN