ENGLISH
FRANCAIS
NEDERLANDS
ESP
AÑOL
IT
ALIANO
DEUTSCH
EN • 3
664Y2900.C
DESCRIPTION
2085
2370
590
2224
2070
274
1696
510
250
DIMENSIONS
A
B
PACKING
The
HeatMaster
®
200N / 201 Booster
are delivered in several packing:
Pack 1 : HeatMaster insulated body with control panel.
Pack 2 : Complete jacket
Pack 3 : Chimney reduction with horizontal exhaust and gasket.
Pack 4 : Low temperature hydraulic kit including 4-ways valve,
tubes and hydraulic components.
Pack 5 : Motor and temperature sensor kit (to control the
4-ways valve).
Pack 6 : Booster kit including the Booster, bracket and holder,
tubes and hydraulic components for the heating and
shunt loops.
Pack 7 : Gas burner with insulation and gasket
(only HeatMaster 201).
TECHNICAL CHARACTERISTICS
Heating Mode
HeatMaster
®
201 Booster
- Input:
220,0 kW
- Output:
210,1 kW
- 100% load efficiency - 80/60 mode:
95,5%
- 100% load efficiency - 50/30 mode:
106,1%
- 30% load efficiency - return at 30°C:
107,9%
Hot water mode - set point 90°C
HeatMaster
®
201 Booster
- Input:
240,0 kW
- Output:
225,0 kW
- Continuous flow rate at 40°C -
cold water at 10°C:
6425 l/h
Pressure drops (Booster alone)
- Hydraulic (
Δ
T = 20):
20 mbar
- Flue gas circuit:
0,3 mbar
HYDRAULIC CONNECTIONS
A. Heating return Ø 2” M
B. Heating flow Ø 2”