TECHNICAL SPECIFICATION
EFFECTIVE DIMENSIONS
The appliances delivered are factory-tested. Upon receipt, remove the packing and check that there is no damage to the appliances. Refer to the
dimensions and weights listed below for transport purposes.
The jacket is fitted by the installer on site
(see the assembly instructions in the wooden protective casing)
.
A
G
H
B
250
190
250
302
338
E
C
D
F
506
HM 200 N
HM 200 F
Fuel
type
Fuel / Gas
Fuel
Input
kW
154.0
196.0
Output
kW
141.7
180.3
Maintenance loss of nominal value at 60°C
%
0.43
0.34
Total capacitye
L
641
641
Primary circuit capacity
L
241
241
Hot water connection
Ø
2”
2”
Heating connection
Ø
2”
2”
Chimney connection
Ø mm
250
250
Water tank heat transfer surface
m
2
5.30
5.30
Drained weight
Kg
530
550
Pressure loss of the primary circuit
mbar
240
240
Combustion efficiency
%
93.5
93.7
Output CO
2
%
12.8
12.9
Net temperature of the flue gases
°C
143
140.5
Mass flow rate of combustion products
g/sec.
65.2
83.0
Nozzle (Fuel oil)
gal/h
3.25 / 60° B
4.00 / 60° B
Pump pressure (Fuel oil)
bar
11.0
11.6
A mm
B mm
C mm
D mm
E mm
F mm
G mm
H mm
HeatMaster
®
200 N
2085
-
1020
-
1020
600
1383
590
HeatMaster
®
200 F
2085
190
1020
1210
1020
600
1383
590
GENERAL CHARACTERISTICS
(*) The HeatMaster
®
200F outputs can only be reached if the boiler is fitted with a “RIELLO” RG4S 396 T1 fuel oil burner.