CHECKS BEFORE STARTING UP
•
Check that the safety valves (DHW and primary) are correctly installed and that the out-
lets are connected to the sewer.
• Check that the DHW tank and the primary circuit are filled with water.
• Check that the air has been correctly bled from both circuits.
• Check that the tank’s upper air bleed valve is tight.
• Check that the water side and heat source side pipes are correctly connected and not
leaking.
• Check that the sensor of the thermostat is correctly positioned in the dry well (see figures
below).
STARTING UP
If the tank is used as electric DHW tank only:
1.
Put the electric plug into the mains socket
2. Adjust the required temperature using the control thermostat integrated in the
electrical resistance.
If the tank is used within a heating installation:
To put the installation into service, refer to the heating boiler manual.
1.
Adjust the required temperature using the control thermostat of the tank.